vane type waterflow

alarM swItCH wItH retarD 

anD Glue-In unIon

for CpvC pIpe

notes: 

 

1.  The Model VSR-SG has two switches, one can be used to operate a 

central station, proprietary or remote signaling unit, while the other 

contact is used to operate a local audible or visual annunciator.

2.  For supervised circuits, see “Switch Terminal Connections” 

drawing and warning note (Fig. 6).     

fig. 4   typical electrical Connections

Break out thin section of cover when wiring both switches from one 

conduit entrance. 

testing  

 

 

 

 

 

 

 

 

 

 

The frequency of inspection and testing for the Model VSR-SG and  its associated protective monitoring system shall be in accordance with applicable 

NFPA Codes and Standards and/or the authority having jurisdiction (manufacturer recommends quarterly or more frequently).
A method of testing the VSR-SG must be provided. The valve used for testing shall be easily reached and shall produce a minimum flow of 10 

GPM to activate the switch. The discharge orifice shall be equal to the smallest sprinkler used in the system. 

fig. 2

Important:

11  paddles  are  furnished  with  each  unit 

to  accommodate  the  various  sizes  and 

manufacturers  of  TEES. 

The  paddles  have 

raised lettering that show the pipe size and 

the  TEE  manufacturer  they  are  to  be  used 

with. The proper paddle must be used.

 The 

paddle must be properly attached (see Fig. 3) 

and the screw that holds the paddle must be 

securely tightened.

fig. 1

Glue the 1" male fitting into the TEE following 

the  TEE  manufacturer's  instructions  for 

preparation  and  gluing  of  CPVC  piping 

systems. Wait 2 to 4 hours to allow the glue 

to dry before attaching the VSR-SG to the 1" 

male fitting.

fig. 3

DWG# 1205-4

Advise the person responsible for testing of the fire protection system that this system must be tested in accordance 

with the testing instructions.

LO

AD 
TO BELL

NEUTRAL FROM BELL

CONNECTOR

EOL (End Of Line Resistor)

BELL

NEUTRAL FROM BREAKER

BREAKER

LINE FROM BREAKER

NOTE: 
When connecting to a UL Listed
control panel, use the panel’s 
resistor value for circuit supervision.

Summary of Contents for VSR-SG

Page 1: ...fications subject to change without notice Stock Number 1144460 Optional Cover Tamper Switch Kit stock no 0090148 Replaceable Components Retard Switch Assembly stock no 1029030 Enclosure The VSR SG switches and retard switch are enclosed in a general purpose die cast housing The cover is held in place with two tamper resistant screws which require a special key for removal A field installable cove...

Page 2: ...duce a minimum flow of 10 GPM to activate the switch The discharge orifice shall be equal to the smallest sprinkler used in the system Fig 2 Important 11 paddles are furnished with each unit to accommodate the various sizes and manufacturers of TEES The paddles have raised lettering that show the pipe size and the TEE manufacturer they are to be used with The proper paddle must be used The paddle ...

Page 3: ...lowing water activates switch in one direction only DWG 1205 15 DWG 1190 1 5 56 in 141 2 mm PIPE PLASTIC PADDLE 2 00 in 50 8 mm 3 91 in 99 33 mm 3 50 in 89 0 mm An uninsulated section of a single conductor should not be looped around the terminal and serve as two separate connections The wire must be severed thereby providing supervision of the connection in the event that the wire become dislodge...

Page 4: ... wires from the waterflow switch 3 Remove the 2 mounting screws holding retard switch assembly to the base 4 Do not remove the 2 retard housing screws Remove the retard assembly by lifting it straight up over the tripstem 5 Install the new retard assembly Make sure the locating pins on the retard switch assembly fit into the locating pin bosses on the base 6 Re install the 2 original mounting scre...

Reviews: