VSR

VANE TYPE WATERFLOW

ALARM SWITCH WITH RETARD

MFG. #5401146 - REV M

11/15

To remove knockouts: Place screwdriver at 

inside edge of knockouts, not in the center.

DWG 1146-4

Fig. 2

Do not drill into the base as this creates 

metal shavings which can create 

electrical hazards and damage the 

device. Drilling voids the warranty.

Fig. 4   Switch Terminal Connections Clamping 

   

Plate Terminal

Fig. 3

Break out thin section of cover when 

wiring both switches from one conduit 

entrance. 

Testing 

 

          

The frequency of inspection and testing for the Model VSR and  its associated protective monitoring system shall be in accordance with applicable 

NFPA Codes and Standards and/or the authority having jurisdiction (manufacturer recommends quarterly or more frequently).
If provided, the inspector’s test valve shall always be used for test purposes. If there are no provisions for testing the operation of the flow detection 

device on the system, application of the VSR is not recommended or advisable.

A minimum flow of 10 GPM (38 LPM) is required to activate this device.

Advise the person responsible for testing of the fire protection system that this system must be tested in accordance 

with the testing instructions.

Fig. 6 Mounting Dimensions

DWG. 1146-14

3.50 in

 (89.0 mm)

2.34 in

 (59.4 mm)

PIPE DIA.

+ 5.25 in

 (+ 133.4 mm)

5.56 in

 (141.2 mm)

2.00 in

 (50.8 mm)

U-BOLT NUT

U-BOLT WASHER

PIPE SADDLE

PIPE

PLASTIC PADDLE

U-BOLT

NOMINAL PIPE DIA. +1.75 in (+44.5 MM) FOR DN 50 – DN 65 2–2.5 in

NOMINAL PIPE DIA. +2.125 in (+54.0 MM) FOR DN 80 – DN 200 3–8 in

DWG 1146-15

GREEN GROUND 

SCREWS

Fig. 7

An uninsulated section of a single conductor should not be looped 

around the terminal and serve as two separate connections.  The 

wire must be severed, thereby providing supervision of the 

connection in the event that the wire become dislodged from under 

the terminal.  Failure to sever the wire may render the device 

inoperable risking severe property damage and loss of life.

Do not strip wire beyond 3/8" of length or expose an uninsulated 

conductor beyond the edge of the terminal block. When using 

stranded wire, capture all strands under the clamping plate. 

Notes: 

 

1.  The Model VSR has two switches, one can be used to operate a central 

station, proprietary or remote signaling unit, while the other contact 

is used to operate a local audible or visual annunciator.

2.  For supervised circuits, see “Switch Terminal Connections” 

drawing and warning note (Fig. 4).    

Fig. 5   Typical Electrical Connections

LO
AD 
TO
 BELL

NEUTRAL FROM BELL

CONNECTOR

EOL (End Of Line Resistor)

BELL

NEUTRAL FROM 
BREAKER

BREAKER

LINE FROM BREAKER

NOTE: 
When connecting to a UL Listed
control panel, use the panel’s 
resistor value for circuit supervision.

Summary of Contents for VSR-2

Page 1: ...d Switch Assembly stock no 1029030 Waterflowswitchesthataremonitoringwetpipesprinklersystemsshall not be used as the sole initiating device to discharge AFFF deluge or chemical suppression systems Waterflow switches used for this application may result in unintended discharges caused by surges trapped air or short retard times Potter Electric Signal Company LLC St Louis MO Phone 866 956 1211 Canad...

Page 2: ...nt false alarms Flowing water activates device in one direction only DO NOT LEAVE COVER OFF FOR AN EXTENDED PERIOD OF TIME TIGHTEN NUTS ALTERNATELY MOUNT ON PIPE SO ARROW ON SADDLE POINTS IN DIRECTION OF WATERFLOW ROLL PADDLE IN OPPOSITE DIRECTION OF WATERFLOW DIRECTION OF WATERFLOW Hole must be drilled perpendicular to the pipe and vertically centered Refer to the Compatible Pipe Installation Req...

Page 3: ...nsions DWG 1146 14 3 50 in 89 0 mm 2 34 in 59 4 mm PIPE DIA 5 25 in 133 4 mm 5 56 in 141 2 mm 2 00 in 50 8 mm U BOLT NUT U BOLT WASHER PIPE SADDLE PIPE PLASTIC PADDLE U BOLT NOMINAL PIPE DIA 1 75 in 44 5 MM FOR DN 50 DN 65 2 2 5 in NOMINAL PIPE DIA 2 125 in 54 0 MM FOR DN 80 DN 200 3 8 in DWG 1146 15 GREEN GROUND SCREWS Fig 7 An uninsulated section of a single conductor should not be looped around...

Page 4: ...e waterflow switch 4 Remove the 2 mounting screws holding retard switch assembly to the base Do not remove the 2 retard housing screws 5 Remove the retard assembly by lifting it straight up over the tripstem 6 Install the new retard assembly Make sure the locating pins on the retard switch assembly fit into the locating pin bosses on the base 7 Re install the 2 original mounting screws 8 Reconnect...

Page 5: ...Mouser Electronics Authorized Distributor Click to View Pricing Inventory Delivery Lifecycle Information AMSECO VSR 4 ...

Reviews: