VSR

VANE TYPE WATERFLOW

ALARM SWITCH WITH RETARD

Installation  (

see Fig. 1)

These devices may be mounted on horizontal or vertical pipe.  On horizontal pipe they shall be installed on the top side of the pipe where they 

will be accessible.  The device should not be installed within 6" (15 cm) of a fitting which changes the direction of the waterflow or within 24" 

(60 cm) of a valve or drain.

NOTE

:

 Do not leave cover off for an extended period of time.

Drain the system and drill a hole in the pipe using a hole saw in a slow speed drill (see Fig. 1). Clean the inside pipe of all growth or other 

material for a distance equal to the pipe diameter on either side of the hole. Roll the vane so that it may be inserted into the hole; do not bend 

or crease it. Insert the vane so that the arrow on the saddle points in the direction of the waterflow. Take care not to damage the non-corrosive 

bushing in the saddle. The bushing should fit inside the hole in the pipe. Install the saddle strap and tighten nuts alternately to required torque 

(see the chart in Fig. 1). The vane must not rub the inside of the pipe or bind in any way.

ADAPTER

USE (2) 5180162 ADAPTERS AS SHOWN ABOVE

        DN50 ONLY

ADAPTER

50mm

20mm ±2mm MAX.

DWG# 1146-1F

Fig. 1

NOTE

: For copper or plastic pipe use Model VSR-CF.

Retard Adjustment

The delay can be adjusted by rotating the retard adjustment knob from 

0 to the max setting (60-90 seconds). The time delay should be set at 

the minimum required to prevent false alarms

(Flowing water activates 

device in one direction only.)

DO NOT LEAVE COVER OFF FOR 

AN EXTENDED PERIOD OF TIME

TIGHTEN NUTS 

ALTERNATELY

MOUNT ON PIPE SO 

ARROW ON SADDLE 

POINTS IN DIRECTION 

OF WATERFLOW

ROLL PADDLE IN 

OPPOSITE DIRECTION 

OF WATERFLOW

DIRECTION OF 

WATERFLOW

Hole must be drilled perpendicular to the pipe and vertically centered. 

Refer to the Compatible Pipe/Installation Requirements chart for size. 

Correct

Incorrect

Compatible Pipe/ Installation Requirements

Model

Nominal Pipe 

Size

Nominal Pipe 

O.D.

Pipe Wall Thickness

Hole Size

U-Bolt Nuts 

Torque

Lightwall

Schedule 10 (UL) Schedule 40 (UL)

BS-1387 (LPC)

DN (VDS)

inch

mm

inch

mm

inch

mm

inch

mm

inch

mm

inch

mm

inch

mm

inch

mm

ft-lb n-m

VSR-2

2

DN50

2.375

60.3

.065

1.651

0.109

2.77

0.154

3.91

0.142

3.6

0.091

2.3

1.25 + .125/-

.062

33.0 ± 2.0

20

27

VSR-2 1/2

2.5

-

2.875

73.0

.084

2.134

0.120

3.05

0.203

5.16

 -

-

-

-

VSR-2 1/2

 -

DN65

3.000

76.1

-

-

-

-

-

-

0.142

3.6

0.102

2.6

VSR-3

3

DN80

3.500

88.9

.083

2.108

0.120

3.05

0.216

5.49

0.157

4.0

0.114

2.9

2.00 ± .125

50.8 ± 2.0

VSR-3 1/2

3.5

 -

4.000

101.6

-

-

0.120

3.05

0.226

5.74

-

-

-

-

VSR-4

4

DN100

4.500 114.3 .084

2.134

0.120

3.05

0.237

6.02

0.177

4.5

0.126

3.2

VSR-5

5

-

5.563

141.3

-

-

0.134

3.40

0.258

6.55

-

-

-

-

VSR-6

6

DN150

6.625 168.3

.115

2.921

0.134

3.40

0.280

7.11

0.197

5.0

0.157

4.0

VSR-8

8

DN200

8.625 219.1

-

-

0.148

3.76

0.322

8.18

0.248

6.3

0.177

4.5

Do not trim the paddle. Failure to follow these instructions may prevent the device from operating and will void the warranty. Do not obstruct or otherwise prevent 

the trip stem of the flow switch from moving when water flows as this could damage the flow switch and prevent an alarm. If an alarm is not desired, a qualified 

technician should disable the alarm system. 

Summary of Contents for VSR-2

Page 1: ...d Switch Assembly stock no 1029030 Waterflowswitchesthataremonitoringwetpipesprinklersystemsshall not be used as the sole initiating device to discharge AFFF deluge or chemical suppression systems Waterflow switches used for this application may result in unintended discharges caused by surges trapped air or short retard times Potter Electric Signal Company LLC St Louis MO Phone 866 956 1211 Canad...

Page 2: ...nt false alarms Flowing water activates device in one direction only DO NOT LEAVE COVER OFF FOR AN EXTENDED PERIOD OF TIME TIGHTEN NUTS ALTERNATELY MOUNT ON PIPE SO ARROW ON SADDLE POINTS IN DIRECTION OF WATERFLOW ROLL PADDLE IN OPPOSITE DIRECTION OF WATERFLOW DIRECTION OF WATERFLOW Hole must be drilled perpendicular to the pipe and vertically centered Refer to the Compatible Pipe Installation Req...

Page 3: ...nsions DWG 1146 14 3 50 in 89 0 mm 2 34 in 59 4 mm PIPE DIA 5 25 in 133 4 mm 5 56 in 141 2 mm 2 00 in 50 8 mm U BOLT NUT U BOLT WASHER PIPE SADDLE PIPE PLASTIC PADDLE U BOLT NOMINAL PIPE DIA 1 75 in 44 5 MM FOR DN 50 DN 65 2 2 5 in NOMINAL PIPE DIA 2 125 in 54 0 MM FOR DN 80 DN 200 3 8 in DWG 1146 15 GREEN GROUND SCREWS Fig 7 An uninsulated section of a single conductor should not be looped around...

Page 4: ...e waterflow switch 4 Remove the 2 mounting screws holding retard switch assembly to the base Do not remove the 2 retard housing screws 5 Remove the retard assembly by lifting it straight up over the tripstem 6 Install the new retard assembly Make sure the locating pins on the retard switch assembly fit into the locating pin bosses on the base 7 Re install the 2 original mounting screws 8 Reconnect...

Page 5: ...Mouser Electronics Authorized Distributor Click to View Pricing Inventory Delivery Lifecycle Information AMSECO VSR 4 ...

Reviews: