MODEL PS40 (VdS)

SUPERVISORY PRESSURE SWITCH

Pressure type supervisory switches; shall be a Model PS40 as 

manufactured by Potter Electric Signal Company, St. Louis, MO., 

and shall be installed on the fire sprinkler system as shown and or 

specified herein.

Switches shall be provided with a 1/2" NPT male pressure 

connection to be connected into the air supply line on the system 

side of any shut-off valve.  A Model BVL bleeder valve as supplied 

by Potter Electric Signal Company of St. Louis, MO., or equivalent 

shall be connected in line with the PS40 to provide a means of 

testing the operation of the supervisory switch. (See Fig. 3)
The switch unit shall contain SPdT (Form C)  switch(es).  One 

switch shall be set to operate at a pressure decrease of 0,7 BAR (10 

PSI) from normal.  If two switches are provided, the second switch 

shall be set to operate at a pressure increase of 0,7 BAR (10 PSI) 

from normal.

Ordering Information 

 

 

 

 

 

 

 

Model 

 

Description 

 

 

 

 

Stock No.

PS40-1 

Pressure switch with one set SPdT contacts 

 

1320031

PS40-2 

Pressure switch with two sets SPdT contacts 

 

1320041    

 

Hex Key 

 

5250062

 

Cover Tamper Switch Kit 

 

0090200   

BVL 

Bleeder valve 

 

1000018

Engineer/architect Specifications Pressure Type Waterflow Switch

•  Installation must be performed by qualified personnel and in accordance with all   

   national and local codes and ordinances.

•  Shock hazard.  Disconnect power source before servicing.  Serious injury or death  

   could result.

•  Read all instructions carefully and understand them before starting installation.  Save  

   instructions for future use.  Failure to read and understand instructions could result   

   in improper operation of device resulting in serious injury or death. 

 

•  Risk of explosion.  Not for use is hazardous locations.  Serious injury or death could result.

•  Do not tighten by grasping the switch enclosure.  Use wrenching flats on the   

   bushing only.  Failure to install properly could damage the switch and cause  

   improper operation resulting in damage to equipment and property. 

 

•  To seal threads, apply Teflon tape to male threads only.  Using joint compounds or  

   cement can obstruct the pressure port inlet and result in improper device operation  

   and damage to equipment. 

 

 

 

 

•  Do not over tighten the device, standard piping practices apply.

•  Do not apply any lubricant to any component of the pressure switch. 

Switch contacts shall be rated at 10.1 Amps at 125/250VAC and 2.0 

Amps at 30VDC.  The units shall have a maximum pressure rating 

of 17,2 BAR (250 PSI) and shall be adjustable from 0,7 to 4,1 BAR 

(10 to 60 PSI).
Pressure switches shall have two conduit entrances, one for each 

individual switch compartment to facilitate the use of dissimilar 

voltages for each individual switch.

The cover of the pressure switch shall be zinc die-cast with rain 

lip and shall attach with one tamper resistant screw.  The pressure 

switch shall be suitable for indoor or outdoor service with a NEMA-

4/IP66 rating.

The pressure switch shall be UL, ULC, and CSFM listed, FM and 

LPC approved and NYMEA accepted.

Summary of Contents for PS40 SERIES

Page 1: ... supplied with each device For optional cover tamper switch kit order Stock No 0090200 See bulletin 5401200 PSCTSK Switch Contacts SPDT Form C 10 1 Amps at 125 250VAC 2 0 Amps at 30VDC One SPDT in PS40 1 Two SPDT in PS40 2 Environmental Specifications NEMA 4 IP66 Rated Enclosure indoor or outdoor when used with NEMA 4 conduit fittings Temperature range 40 C to 60 C 40 F 140 F Pressure Range 0 7 4 ...

Page 2: ...RE DROP WITH NORMAL SYSTEM PRESSURE APPLIED HIGH TERMINAL 1 WILL CLOSE ON PRESSURE INCREASE NOTE To prevent leakage apply teflon tape sealant to male threads only ADJUSTMENT KNOB 2 87 72 97 4 22 107 19 2 48 62 87 3 78 95 89 3 20 81 28 1 60 40 64 Fig 4 An uninsulated section of a single conductor should not be looped around the terminal and serve as two separate connections The wire must be severed...

Page 3: ...RESSURE SWITCH Switch Operation Low Pressure Signal Connection EOLR TO FIRE ALARM PANEL EOLR TO FIRE ALARM PANEL High Pressure Signal Connection Fig 5 Fig 7 With normal system pressure Terminal C Common 1 Closed when installed under normal system pressure 2 Open when installed under normal system pressure Closes on pressure drop Use for low air signal Terminal 1 Open when installed under normal sy...

Page 4: ...ce before servicing Serious injury or death could result Read all instructions carefully and understand them before starting installation Save instructions for future use Failure to read and understand instructions could result in improper operation of device resulting in serious injury or death Risk of explosion Not for use is hazardous locations Serious injury or death could result Do not tighte...

Page 5: ...gewindeverbindungen verwenden 3 Die Vorrichtung sollte in aufrechter Position montiert werden Gewindeanschluss nach unten 4 Ziehen Sie die Vorrichtung an indem Sie nur die flachen Seiten eines Schraubenschlüssels am Gerät ansetzen 1 Entfernen Sie die manipulationsresistente Schraube mit dem beiliegenden Spezialschlüssel 2 Führen Sie am Rand derAusbrechöffnung vorsichtig einen Schraubendreher ein u...

Page 6: ...MDRUCK HOCH ANSCHLUSS 1 SCHLIESST BEI DRUCKANSTIEG Abb 4 ERDUNGS SCHRAUBEN 1 2 NPT HINWEIS Bringen Sie an den Außengewinden Teflonband an um Leckagen zu vermeiden EINSTELLKNOPF 2 87 72 97 4 22 107 19 2 48 62 87 3 78 95 89 3 20 81 28 1 60 40 64 Ein abisolierter Abschnitt eines einzelnen Leiters sollte nicht um dieAnschlussklemme geschlungen werden um ihn anstelle von zwei separaten Verbindungen zu ...

Page 7: ...rucksignal Anschluss Für Hochdrucksignal Abb 5 Abb 7 bei normalem Systemdruck Anschluss C Gemeinsame Leitung 1 Geschlossen bei Installation unter normalem Systemdruck 2 Geöffnet bei Installation unter normalem Systemdruck Schließt bei Druckabfall Verwendung für Signal bei niedrigem Luftdruck Anschluss 1 Geöffnet bei Installation unter normalem Systemdruck Schließt bei Druckanstieg Verwendung für S...

Page 8: ...rleitungsöffnungen eine für jede Schalterkammer um die Verwendung unterschiedlicher Spannungen für die einzelnen Schalter zu erleichtern Die Abdeckung des Druckschalters besteht aus Zinkdruckguss mit Regenschutz und ist mit einer manipulationsresistenten Schraube zu befestigen Der Druckschalter kann sowohl im Innenbereich als auch imAußenbereich mit NEMA 4 IP66 Klassifizierung verwendet werden Der...

Reviews: