![Ponovo PNS630 User Manual Download Page 21](http://html1.mh-extra.com/html/ponovo/pns630/pns630_user-manual_1578950021.webp)
PNS630 Handheld Analyzer User Manual
21
6.2 SMV output
SMV output is valid only in Quick Test and Sequence modules. The ASDU and sample
rate can be edited.
There are 16 channels of voltage, 16 virtual current channels, in 4 groups.
G1: Ua1/Ub1/Uc1/Uz1, Ia1/Ib1/Ic1/Iz1
G2: Ua2/Ub2/Uc2/Uz2, Ia2/Ib2/Ic2/Iz2
G3: Ua3/Ub3/Uc3/Uz3, Ia3/Ib3/Ic3/Iz3
G4: Ua4/Ub4/Uc4/Uz4, Ia4/Ib4/Ic4/Iz4
The voltage/ current channels could be mapped to different SMV control block. The
below is the general test schedule.
SMV configuration-> Add SMV block-> Set SMV parameter and channel-> choose the
SMV block to be sent-> Set voltage-> current or binary in QuickTest or State Sequence->
Set GOOSE subscribe and BI mapping channel-> Send or modify the SMV-> Get SMV
result
In SMV output, the SMV standard, sample rate and ASDU can be set here.
SMV output
SMV type:
the standard
IEC61850-9-2, IEC60044-7/8(FT3), IEC60044-7/8(FT3),