35
Safety Check
DANGER: Check thoroughly, all operations in the installation, ensuring the
system is installed correctly. Pay special attention that DC and AC voltages
are in the specified ranges of iCAN NetZero Plus.
Items
Notes
PV connection
External breaker is installed.
The appropriate breaker is installed as specified.
The breaker is turned OFF.
Open-circuit voltage of PV arrays is within the
allowed range.
Positive and negative polarities are correct.
Battery connection
There is no voltage to the battery ports.
Positive, negative, and REF polarities are correct.
AC breaker
AC breaker is turned OFF.
Grid connection
External breaker is installed.
The appropriate breaker is installed as specified.
The breaker is turned OFF.
N, L2, L1 are wired correctly.
Voltage is within the allowed range.
Generator connection External breaker is installed.
The appropriate breaker is installed as specified.
The breaker is turned OFF.
N, L2, L1 are wired correctly.
Voltage is within the allowed range.
Wiring
All cables are wired tightly.
Wiring box covers
All wiring covers are screwed tightly.
Conduit
All conduits are tightly installed and sealed.
Wire protection
Insulated cover of wires is not at risk of being cut or
damaged.