3.6.9 Assign Relay to a Stage
Any of the 5 Relays can be assigned freely to any Stage.
Stages that do not activate relays receive an
assignment of 00.
Symbol Description
Default
Status Function
SP 01
Sensor Point
Selection SP No.
1
S1
S2
S3
S4
S5
01
02
03
00
05
01 = Stage 1 activate relay R 01
02 = Stage 2 activate relay R 02
03 = Stage 3 activate relay R 03
00 = Stage 4 does not activate a relay
05 = Stage 5 activate relay R 20 (internal horn)
3.6.10 Assigned SP Signal to analog Output
The sensor point signal can be assigned to one of the ten analog Outputs. The signal defined in the control
mode (Current Value or Average Value) is transmitted.
Analog output see also: 3.7.2
Symbol Description
Default
Status Function
SP 01
Sensor Point
Selection SP No.
0
A
0
0 = SP Signal not assigned to any analog output
1 = SP Signal assigned to analog output 1
X = SP Signal assigned to analog output X