MGC2-20
PolyGard
®
Multi-Point Controller
User Manual - MGC2-20
Page 14
3.6 Menu SP Setup
Display and Change Parameters, Assign Stage value, Assign relays to stages and activate each Sensor Point
(SP).
(Main Menu)
(Selection of a sensor point)
Activate or deactivate SP
See 3.6.1
Define Type
See 3.6.2
Define Measuring range
See 3.6.3
Define signal type of transmitter
See 3.6.4
Define Stage/Setpoint 1
See 3.6.5
Define Stage/Setpoint 2
See 3.6.5
Define Stage/Setpoint 3
See 3.6.5
Define Stage/Setpoint 4
See 3.6.5 Stage/Setpoint
Define Stage/Setpoint 5
See 3.6.5
Hysteresis
See 3.6.5
Set Delay ON time
See 3.6.6
SP Mode
active
SP Type
NH3
SP Setup
SP 01
active
Measuring range
300 ppm
SP-Signal
linear
Stage 1
100 ppm
Stage 2
100 ppm
Stage 3
200 ppm
Stage 4
200 ppm
Stage 5
300 ppm
Hysteresis
15 ppm
Delay ON time
0 s