Polyaire Zonemaster Unipoint RF Owner’S Manual & Setup Manual Download Page 1

UNIPOINT RF DAMPER CONTROL SYSTEM

Owner’s Manual & Setup Guide

Summary of Contents for Zonemaster Unipoint RF

Page 1: ...UNIPOINT RF DAMPER CONTROL SYSTEM Owner s Manual Setup Guide ...

Page 2: ...d the instructions before installing this Zonemaster Zoning Control System Polyaire Pty Ltd does not accept any responsibility for loss or damage that may occur as a result of the installation of this Zoning Control System ...

Page 3: ... 8 1 Features Page 8 2 Application Page 8 3 Components Page 9 4 Configuration Page 10 5 Spill bypass modes air setpoint Page 11 6 Installation Page 12 a Zone address and allocation Page 12 b Initiating and exiting the setting process Page 13 c Setting system code Page 13 14 d Number of zones in the system Page 14 e Supply air safety high low limits Page 14 f Turbo Page 15 g Naming zones Page 15 h ...

Page 4: ... to enter into zoning mode The first way is to press or button the other one is to press button to get into the function selection mode and then press button again after selecting zoning by using or button 1 In Zoning mode the handset displays zone name and the on off status of up to six zones as shown on the right figure 2 Use the or button to select a zone to be controlled The on off status of t...

Page 5: ...er UniPoint RF system This system has a 5 1 1 program capability that means the system has an individual program for weekdays Monday to Friday Saturdays and Sundays respectively The system allows you to create 4 separate programs and then allocate any one of these to each of the up to 8 zones Each of the 4 main programmes has 4 sub programmable events per day On time 1 Off time 1 On time 2 and Off...

Page 6: ...e sleep mode itself in 15 seconds with no key being pressed 3b Adjust program time 1 Press the button once to enter into the Function Screen 2 Use the or button to select the program to be modified and then press button to enter into its sub menu 3 Use the or button to select Monday Fri day Saturday or Sunday program Then press button to enter into its sub menu 4 Press button to enable the setting...

Page 7: ...ous zones should have been given names by your installer that correspond with the particular rooms in your house If this has not happened call your installer to get this rectified 1 Make sure that at least one of the four programs is enabled by setting up all the parameters in the program 2 Press the button to get into zoning screen and then press or button to select the zone 3 Use and button to s...

Page 8: ... the dampers will remain open These will usually be low numbered zones close to the return air duct Zones 1 or 2 that open into frequently used space 5 Turbo feature The RF UniPoint allows one zone to be selected as the Turbo zone This will usually be a zone which might require heavy airflow at certain times due to a rapid influx of people The family dining games room are examples Turbo ing a zone...

Page 9: ...turday Sunday 6 Information sheet Use the following tables to record your settings PROGRAM 2 On time 1 Off time 1 On time 2 Off time 2 Monday to Friday Saturday Sunday PROGRAM 3 On time 1 Off time 1 On time 2 Off time 2 Monday to Friday Saturday Sunday PROGRAM 4 On time 1 Off time 1 On time 2 Off time 2 Monday to Friday Saturday Sunday ...

Page 10: ...ne s opening position can be programmed for balancing purpose One selectable turbo zone Auto spill bypass the designated zones bypass are forced open when all zones are turned off Safety system Opens all dampers if the supply air temperature is less than low limit or more than high limit All zones automatically return their original on off state once power up 2 Application Zonemaster UniPoint RF c...

Page 11: ...d controls the position of motorized damper of each zone 3 Motorized Damper Bright Green Motorized damper drives the blade of the damper to turn on off the air from ducting to a zone 4 Cable Cable connects the main control board and the motorized damper together 5 Supply Air Sensor Supply air sensor measures the temperature of the supply air for safety purposes 6 Power Supply The 24 VAC transforme...

Page 12: ...est all cables prior to connecting with the Zonemaster Cable Tester 4 Configuration Eight motorised dampers can be connected to the Main Control Board If the bypass mode in which a damper is used to return the air directly to the return air duct is selected in the system there will be only 7 zones in the system and the 8th zone becomes the bypass Otherwise there are independent 8 zones in a spill ...

Page 13: ... to open to spill excess air This process will continue until the spill air setpoint is satisfied in the system Such a spill air control strategy implemented in the Zonemaster UniPoint RF control system requires the installer to allocate the zone 1 near the return air grilles Spill mode uses the zones with lowest address in the system as spill zones that will be automatically forced to turn on if ...

Page 14: ... that all the LEDs and sockets for zones are shown 4 Use a pre tested cable to connect the 1st output port on the main control board to the motorised damper of the 1st zone in the system 5 Repeat step 4 to connect other zones to its relevant output ports on the main control 6 Mount the supply air sensor in the supply air duct between the fan coil and the first damper 7 Connect supply air temperatu...

Page 15: ...ferent code There are 8 codes in total 0 1 2 3 4 5 6 7 Setting system code on remote handset 1 At the setting mode select Parameter by pressing button to display its sub menu 2 Use or button to select the System Code high lightened 3 Use and button to increase or decrease the code Setting system code on main control module 1 Remove the two side covers on the main control board a push button and 8 ...

Page 16: ...electable zone number is 1 to 8 6e Supply air safety high low limits For safety reasons the system monitors the supply air temperature of the system closely If the temperature moves outside of the limits all dampers in the system are forced open The factory default setting is that the safety control is disabled 1 At the setting mode in Parameter screen press or buttons to select Hi limit and press...

Page 17: ...s called Zone_addr in default setting For example Zone 1 which has an address of 1 is called Zone_1 on its factory default The names can be customised as you prefer as follows 1 In Setting mode press or button to select Naming and press button to enter the sub menu of the naming screen 2 Press or button to select the zone to be named 3 Press and button to select one of the preset zone names for th...

Page 18: ...cing screen 2 Press or button to select the zone to be balanced 3 Press and button to increase or decrease the percentage of opening positions for the zone 4 Follow step 2 and 3 to adjust the settings for the other zones Please note that once the zone is balanced with a percentage opening it is treated as a complete zone when calculating spilling setpoint For example a 5 zone system with a 20 spil...

Page 19: ...ave no response when turned on or off Check if the LEDs on the main control board light up If not check that system codes for handset and main control boards are the same Check the cable to the main control board with cable tester Some zones cannot be turned off Check if it is spill zone with lower address Check spill setpoint Check the battery level of the remote controller No display on the LCD ...

Page 20: ...rating temperature 0 C to 60 C Altitude 0 to 2000 meters Operating relative humidity 10 to 80 Avoid static electricity hazards Avoid electromagnetic radiation sources Avoid dust contamination Avoid highly corrosive environments Zone Output Output voltage 24VAC 50Hz Current 500mA 2 damper motors Transformer Input Voltage 240VAC 50Hz Output Voltage 24VAC 50Hz Wattage 24W Supply Air Sensor NTC type 1...

Page 21: ......

Page 22: ......

Page 23: ......

Page 24: ...POLYAIRE PTY LTD 11 13 WHITE ROAD GEPPS CROSS SOUTH AUSTRALIA 5094 TEL 08 8349 8466 FAX 08 8349 8446 www zonemaster com au www polyaire com au ...