background image

3

 

INSINTRIC

 

SAFETY

 

PARAMETERS

 

Supply

 

line

 

marginal

 

parameters:

 

Maximum

 

input

 

voltage

 

 

 

 

 

U

I

 

25

 

V

 

Maximum

 

input

 

current

  

 

 

 

 

I

I

 

 

99

 

mA

 

Maximum

 

input

 

power

    

 

 

 

 

P

I

  

0,613

 

W

 

Maximum

 

inner

 

capacity

 

  

 

 

 

C

I

 

 

16,5

 

nF

 

Maximum

 

inner

  

inductance

 

 

  

 

 

L

I

 

 

0*

 

Maximum

 

outer

 

capacity

  

 

 

 

 

C

o

 

 

110

 

nF

 

**

 

Maximum

 

outer

  

inductance

    

 

 

 

L

O

  

2,5

 

mH**

 

 

Detector

alarm

 

indicator

 

connecting

 

line

 

parameters:

 

Maximum

 

output

 

voltage

  

 

 

 

 

U

O

  

25

 

V***

 

Maximum

 

output

 

current

   

 

 

 

 

I

O

 

 

99

 

mA***

 

Maximum

 

output

 

power

  

 

 

 

 

P

O

  

0,613

 

W***

 

 

*

 

negligible

 

parameters

  

**

 

represents

 

the

 

sum

 

of

 

capacity

 

and

 

inductance

 

resulting

 

from

 

the

 

length

 

of

 

cables

 

that

 

may

 

be

 

connected

  

     

to

 

the

 

detector

 

***

 

values

 

that

 

may

 

occur

 

in

 

case

 

of

 

uncountable

 

damages

 

 

Intrinsically

 

safe

 

barrier

 

or

 

separator

 

parameters:

 

Maximum

 

output

 

voltage

 

 

 

 

 

U

O

  

25

 

V

 

Maximum

 

output

 

current

  

 

 

 

 

I

O

  

99

 

mA

 

Maximum

 

output

 

power

 

 

 

 

 

P

O

  

0,613

 

W

 

Minimum

 

output

 

resistance

 

 

 

 

 

R

I

  

300

 Ω  

Maximum

 

outer

 

capacity

 

  

 

 

 

C

O

  

110

 

nF

 

Maximum

 

inner

 

inductance

 

 

 

 

 

L

O

  

2,5

 

mH

 

 

Connecting

 

cable

 

example

 

(

 

YnTKSY):

 

Core

 

diameter

    

 

 

 

mm

  

 

0,8

  

1,0

 

Single

 

core

 

resistance

    

 

 

/km

    

37,5

  

24

 

Pair

 

of

 

cores

 

capacity

    

 

 

nF/Km

   

120

  

120

 

Inductance

   

 

 

 

 

mH/km

  

0,7

  

0,7

 

 

Note:

 

The

 

total

 

line

 

capacity

 

and

 

line

 

inductance

 

as

 

well

 

as

 

total

 

inner

 

inductance

 

of

 

the

 

detectors

 

installed

 

behind

 

an

 

intrinsically

 

safe

 

barrier

 

of

 

separator

 

must

 

not

 

exceed

 

the

 

level

 

of

  

110

 

nF

 

and

 

2,5

 

mH.

 

As

 

a

 

result

 

in

 

practice

 

it

 

is

 

not

 

possible

 

to

 

connect

 

more

 

than

 

five

 

TUN

38Ex

 

detectors

 

behind

 

an

 

intrinsically

 

safe

 

barrier

 

of

 

separator.

  

4

 

SAFETY

 

CONDITIONS

  

4.1

 

Repairs

 

and

 

maintenance

  

Any

 

maintenance

 

works

 

or

 

periodic

 

inspection

 

shall

 

be

 

executed

 

by

 

skilled

 

personnel

 

employed

 

by

  

companies

 

authorised

 

and

 

trained

 

by

 

POLON

ALFA.

  

Any

 

repairs

 

must

 

be

 

carried

 

out

 

by

 

the

 

manufacturer.

 

POLON

ALFA

 

bears

 

no

 

responsibility

 

for

 

the

 

operation

 

of

 

any

 

apparatus

 

being

 

repaired

 

by

 

unauthorised

 

personnel.

 

 

4.2

 

Works

 

at

 

height

  

Any

 

detector

 

installation

 

works

 

carried

 

out

 

at

 

height

 

must

 

be

 

executed

 

with

 

particular

 

care

 

utilising

 

tools

 

and

 

machinery

 

in

 

good

 

working

 

condition.

  

Summary of Contents for TUN-38Ex

Page 1: ...TUN 38Ex Intrinsically Safe HEAT DETECTOR Installation and Maintenance Manual IK E280 001GB IIIC Issue ...

Page 2: ...WE type Inspection Certificate No KDB 04ATEX172X Supplement No 1 Quality Assurance Acknowledgement No GIG 04 ATEXQ 021 WE Conformity Declaration No 3 E280 2010 The Certificates may be downloaded from www polon alfa pl web site 1438 1453 Polon Alfa Limited Partnership 155 Glinki Street PL 85 861 Bydgoszcz POLAND 05 1438 CPD 0025 EN 54 5 TUN 38Ex Heat Detector conventional universal non detachable A...

Page 3: ...nes qualified as 1st and 2nd explosive hazard category resulting from potential explosion danger of explosive gases or inflammable liquid vapours that are ranked at IIA IIB and IIC explosiveness subgroups and T1 up to T6 temperature classes Allowable ambient temperature range 25 C up to 65 C for T6 temperature class 25 C up to 85 C for T1 T5 temperature classes 2 TECHNICAL SPECIFICATIONS Operating...

Page 4: ...m inner inductance LO 2 5 mH Connecting cable example YnTKSY Core diameter mm 0 8 1 0 Single core resistance Ω km 37 5 24 Pair of cores capacity nF Km 120 120 Inductance mH km 0 7 0 7 Note The total line capacity and line inductance as well as total inner inductance of the detectors installed behind an intrinsically safe barrier of separator must not exceed the level of 110 nF and 2 5 mH As a resu...

Page 5: ...perational environment this protection assures detector s in proper work explosive atmosphere 6 PRINCIPLES OF OPERATION The TUN 38Ex heat detector reacts to a rise of temperature occurring during initial phase of fire The detector operates as a fixed temperature detector after exceeding its set off operation threshold according to its given class It operates also as a rate of rise heat detector wh...

Page 6: ...tion Temperature C Maximum Static Activation Temperature C A1 25 50 54 65 B 40 65 69 85 The terms used in the tables have the following meaning Normal Operating Temperature Maximum Operating Temperature maximum temperature level at which detector operates for a short period of time provided no fire hazard occurs Static Activation Temperature temperature level at which detector transmits a warning ...

Page 7: ...N Determine the detector class with the cramps that are accessible after the cover removal Cramp positions corresponding to various classes is shown on Figure 2 Fig 2 Cramp positioning for various detector class example of A1R H Detectors shall be connected to detecting lines in accordance with Figure 3 ...

Page 8: ... etc removal periodic device functioning test The TUN 38Ex detector is required to pass periodic controls carried out at least once in 6 months to prove that the detector operates properly and works together with the fire control panel properly Any damaged detector must be passed for repair to the manufacturer During renovation or painting works detectors shall be protected from damage or dirt 9 S...

Page 9: ...IK E280 001GB 9 Fig 4 TUN 38Ex detector basic dimensions IK E280 001GB 07 2009 ...