background image

7

 

 

 

 

 

        

IP

E282

001GB

 

 

 

b)

 

remove

 

two

 

screws

 

that

 

fix

 

the

 

labyrinth

 

and

 

take

 

the

 

labyrinth

 

out;

 

c)

 

perform

 

the

 

necessary

 

cleaning.

 

A

 

delicate

 

brush

 

as

 

well

 

as

 

vacuum

 

cleaner

 

are

 

recommended

 

for

 

cleaning.

 

Compressed

 

air

 

can

 

be

 

possibly

 

used.

 

It

 

is

 

permitted

 

to

 

wash

 

the

 

labyrinth

 

with

 

warm

 

water

 

with

 

addition

 

of

 

washing

up

 

liquid.

 

No

 

damp

 

patches

 

should

 

remain

 

on

 

the

 

labyrinth

 

internal

 

surfaces

 

after

 

washing

 

and

 

drying.

  

After

 

cleaning

 

the

 

detector

 

should

 

be

 

assembled,

 

its

 

functioning

 

should

 

be

 

tested

 

using

 

a

 

smoke

 

imitator

 

or

 

smoke

 

generator

 

and

 

installed

 

again

 

into

 

the

 

detection

 

line.

  

In

 

this

 

order

 

to

 

assemble

 

the

 

detector,

 

it

 

is

 

necessary

 

to:

  

a)

 

fasten

 

the

  

labyrinth

 

with

 

two

 

screws;

 

b)

 

place

 

the

 

basket

 

in

 

the

 

reverse

 

position

 

as

 

that

 

shown

 

in

 

the

 

figure;

 

c)

 

insert

 

the

 

net

 

into

 

the

 

basket

 

paying

 

attention

 

to

 

its

 

positioning

 

 

alignment

 

with

 

the

 

juts;

 

d)

 

insert

 

the

 

cover

 

into

 

the

 

basket

 

so

 

that

 

the

 

illuminating

 

diode

 

is

 

placed

   

a

 

little

 

to

 

the

 

right

 

in

 

relation

 

to

 

the

 

glass;

 

e)

 

turn

 

the

 

cover

 

to

 

the

 

left.

 

 

Note

 

 

In

 

case

 

the

 

cleaning

 

does

 

not

 

produce

 

the

 

required

 

result,

 

it

 

is

 

necessary

 

to

 

send

 

the

 

detector

 

to

 

the

 

manufacturer

 

for

 

repair.

 

  

7

  

DETECTOR

 

INSTALLATION

 

The

 

DOR

4046

 

detectors

 

are

 

installed

 

(height,

 

arrangement)

 

according

 

to

 

the

 

guidelines

 

settled

 

by

 

the

 

Scientific

 

and

 

Research

 

Centre

 

for

 

Fire

 

Protection.

 

They

 

are

 

mounted

 

in

 

premises

 

where

 

the

 

working

 

equipment

 

or

 

stored

 

materials

 

may

 

emit

 

visible

 

smoke

 

when

 

a

 

fire

 

occurs.

 

In

 

case

 

it

 

is

 

difficult

 

to

 

determine

 

the

 

most

 

probable

 

fire

 

factor

 

(smoke

 

type)

 

that

 

is

 

likely

 

to

 

occur

 

in

 

the

 

first

 

fire

 

development

 

phase,

 

special

 

tests

 

should

 

be

 

carried

 

out

 

(at

 

a

 

designing

 

stage)

 

using

 

various

 

type

 

detectors

 

or

 

mixed

 

protection

 

(e.

 

g.

 

with

 

optical

 

and

 

ionisation

 

detectors)

 

should

 

be

 

applied.

  

The

 

detectors

 

are

 

intended

 

to

 

operate

 

in

 

loops,

 

in

 

loops

 

with

 

straight

 

branches

 

or

 

in

 

radial

 

detection

 

lines

 

of

 

the

 

POLON

 

4100

 

and

 

POLON

 

4200

 

control

 

panels

 

(see

 

the

 

POLON

 

4100/POLON

 

4200

 

control

 

panel

 

Operation

 

and

 

Maintenance

 

Documentation).

 

The

 

detectors

 

are

 

installed

 

in

 

the

 

40

 

model

 

range

 

bases.

 

The

 

detection

 

line

 

connection

 

is

 

presented

 

in

 

the

 

G

40

 

base

 

Installation

 

and

 

Maintenance

 

Manual.

 

An

 

additional

 

optical

 

alarm

 

signal

 

of

 

a

 

detector

 

or

 

a

 

group

 

of

 

detectors

 

can

 

be

 

obtained

 

by

 

connecting

 

the

 

WZ

31

 

alarm

 

indicator.

  

Alarm

 

system

 

cables

 

are

 

routed

 

in

 

accordance

 

with

 

the

 

regulations

 

obligatory

 

for

 

low

 

voltage

 

(below

 

42

 

V)

 

systems.

 

 

Note

 

 

The

 

detectors

 

should

 

not

 

be

 

installed

 

in

 

corrosive

 

atmosphere

 

that

 

contains

 

caustic

 

gases

 

and

 

vapours

 

as

 

well

 

as

 

dust.

 

Steam

 

condensation

 

on

 

detectors

 

is

 

impermissible.

  

 

 

8

  

STORAGE

 

AND

 

TRANSPORTATION

 

 

8.1

 

Storage

 

The

 

DOR

4046

 

detectors

 

must

 

be

 

stored

 

in

 

closed

 

rooms

 

free

 

of

 

any

 

caustic

 

gases

 

and

 

vapours,

 

at

 

ambient

 

temperature

 

between

 

0

 

°C

 

and

 

+40

 

°C

 

and

 

relative

 

humidity

 

not

 

exceeding

 

80

 

%

 

at

 

+

 

35

 

o

C.

  

Summary of Contents for DOR-4046

Page 1: ...POLON 4000 INTERACTIVE FIRE DETECTION AND ALARM SYSTEM DOR 4046 ADDRESSABLE MULTI STATE OPTICAL SMOKE DETECTOR Installation and Maintenance Manual IK E282 001GB IIIA Edition ...

Page 2: ...fa Spółka z ograniczoną odpowiedzialnością Sp k 155 Glinki Street PL 85 861 Bydgoszcz POLAND 05 1438 CPD 0013 EN 54 7 DOR 4046 Optical Smoke Detector addressable multi state detachable utilising diffused light effect Application fire security Technical data IK E282 001GB manual Read the manual carefully before assembling and activation of the detector Any nonconformity with the instructions contai...

Page 3: ... supervised area 60 80 m2 Operating temperature range from 25 C to 55 C Allowable relative humidity up to 95 at 40 C Dimensions without base Ø 115 mm x 43 mm Number of sensitivity levels 3 Mass without base 0 2 kg Standard colour white Address coding method programmable at the control panel see the design guidelines 3 SAFETY CONDITIONS 3 1 Repairs and maintenance Any maintenance works or periodic ...

Page 4: ... G 40 base where detection line cables are connected to Fig 1 DOR 4046 detector main elements 5 PRINCIPLE OF OPERATION The DOR 4046 is a Tyndall effect based optical smoke detector light ray scattering on smoke particles Its basic element is a detecting optical module consisting of an electroluminescence diode that transmits infrared radiation and an optical receiving diode The optical module and ...

Page 5: ...echnical alarm and an actuation of a short circuit isolator are signalled with yellow flashes of the diode The detector sensitivity level is adjustable Its sensitivity is settled from the control panel level choosing one of available sensitivity levels 1st operation mode normal sensitivity 2nd operation mode increased sensitivity 3rd operation mode decreased sensitivity The detector operation mode...

Page 6: ... labyrinth and the lenses of both diodes transmitting one and photodiode A failure to carry out the servicing works may result in false alarm evoking in future Fig 2 Detector elements after dismantling The detector assembling and dismantling is shown in Fig 2 In order to dismantle the detector it is necessary to a pressing the net long tongue turn the cover right in the basket until it is taken ou...

Page 7: ...for Fire Protection They are mounted in premises where the working equipment or stored materials may emit visible smoke when a fire occurs In case it is difficult to determine the most probable fire factor smoke type that is likely to occur in the first fire development phase special tests should be carried out at a designing stage using various type detectors or mixed protection e g with optical ...

Page 8: ...ths 8 2 Transportation The DOR 4046 detectors should be carried in closed spaces of transport means in proper packing that meet appropriate transport regulations Transport temperature shall not be lower than 40 C and higher than 70 C relative humidity shall not exceed 95 at 45 C or 80 at 70 C Fig 3 Clamps of base interoperating with DOR 4046 plug IK E282 001GB 05 2011 01 2012 ...