PRINCIPLES

 

OF

 

OPERATION

 

 

The

 

detector

 

monitoring

 

activity

 

begins

 

when

 

a

 

battery

 

power

 

supply

 

is

 

connected.

 

An

 

information

 

about

 

the

 

detector

 

mode

 

is

 

communicated

 

by

 

acoustic

 

and

 

optical

 

signals

 

as

 

per

 

the

 

following

 

table:

 

 

Detector

 

mode

 

Modulated

 

audio

 

signal

 

LED

  

flashing

 

Short

 

audio

 

signal

 

40

 

s

 

interval

 

LED

 

flashing

 

40

 

s

 

interval

 

Supervision,

 

smoke

 

detection

 

 

 

 

x

 

Alarm

  

after

 

smoke

 

detection

 

x

 

x

 

 

 

Low

  

power

 

supply

 

voltage

 

 

 

x

 

x

 

Detector

 

testing

 

with

 

the

 

TEST

 

button

 

x

 

x

 

 

 

Fault

 

 

 

x

 

 

 

In

 

case

 

a

 

factor

 

that

 

causes

 

a

 

particular

 

mode

 

decays,

 

the

 

detector

 

automatically

 

returns

 

to

 

its

 

supervision

 

mode.

 

Depending

 

on

 

the

 

type

 

of

 

a

 

battery

 

used,

 

the

 

detector

 

operation

 

period

 

may

 

vary:

 

 

ordinary

 

batteries

 

 

min.

 

1

 

year;

 

the

 

detector

 

will

 

work

 

normally

 

for

 

at

 

least

 

30

 

days

 

since

 

the

 

first

 

low

 

battery

 

signal

 

has

 

been

 

transmitted

 

 

alkaline

 

batteries

 

 

min.

 

2

 

years;

 

low

 

battery

 

signal

 

for

 

min.

 

30

 

days

 

 

lithium

 

batteries

 

 

min.

 

3

 

years;

 

low

 

battery

 

signal

 

for

 

min.

 

60

 

days.

 

Frequent

 

detector

 

tests

 

and

 

its

 

activation

 

inspections

 

will

 

result

 

in

 

the

 

operation

 

period

 

shortening.

 

 

Summary of Contents for ADR-20N

Page 1: ...ADR 20N SELF CONTAINED OPTICAL SMOKE DETECTOR Installation and Maintenance Manual IK E289 003GB Issue 1A ...

Page 2: ...etector Application fire security Technical data IK E289 003GB manual Read the manual carefully before assembling and operation of the detector Any nonconformity with the instructions contained in the manual may be harmful or may cause violation of the law in force POLON ALFA shall not bear responsibility for any harms resulted from the unit application discordantly to the requirements of this ins...

Page 3: ... 38 Audio alarm volume 85 dB at 3 m distance Battery operation life 1 3 years depending on type 3 SAFETY CONDITIONS 3 1 Repairs and maintenance Any repair must be carried out by the manufacturer POLON ALFA bears no responsibility for the operation of any apparatus being serviced and repaired by unauthorised personnel 3 2 Works at height Any detector installation works carried out at height must be...

Page 4: ... inside the bottom The casing encloses a wire grid that prevents irruption of small insects or pieces of dirt Fig 1 The bottom is fixed to the casing with two screws 10 Two small devices protrude from the casing a test button 4 and an illuminating LED 8 that indicates the detector mode Fragments of a printed ...

Page 5: ...s are shown on Fig 1 leaving the minimum distance from the bottom The cables should be placed into the holes and then the base should be fixed in the place intended for installation The detectors may be interconnected using a typical telecommunication PVC insulated cable of 0 12 0 5 mm2 cross section 0 4 0 9 mm diameter Two wires may be connected to one contact wire and resistor endings It is allo...

Page 6: ...after smoke detection x x Low power supply voltage x x Detector testing with the TEST button x x Fault x In case a factor that causes a particular mode decays the detector automatically returns to its supervision mode Depending on the type of a battery used the detector operation period may vary ordinary batteries min 1 year the detector will work normally for at least 30 days since the first low ...

Page 7: ...ning is not effective it is allowed to wash the labyrinth with warm water with an addition of washing up liquid after cleaning and drying no water stain may be left on the labyrinth internal surfaces After cleaning reassemble the detector in the following order check whether the metal cover does not conceal the acoustic signalling device opening press the labyrinth down until its catches snap in t...

Reviews: