background image

 IK-E322-001GB 

_____________________________________________________________________________ 

circuit

 

board

 

(PCB)

 

with

 

contact

 

pins

 

are

 

visible

 

from

 

the

 

bottom

 

side.

 

These

 

contact

 

pins

 

hold

 

a

 

connector

 

(11)

 

to

 

interconnect

 

several

 

detectors

 

in

 

a

 

network.

 

 

 

5

 

INSTALLATION

 

 

The

 

detectors

 

are

 

recommended

 

to

 

be

 

installed

 

in

 

all

 

rooms

 

exposed

 

to

 

a

 

high

 

fire

 

hazard

 

level.

 

They

 

may

 

be

 

mounted

 

in

 

hallways,

 

staircases

 

as

 

well

 

as

 

in

 

passages

 

between

 

rooms

 

endangered

 

by

 

a

 

fire

 

occurrence.

 

It

 

is

 

recommended

 

to

 

install

 

the

 

detector

 

on

 

ceilings,

 

leaving

 

at

 

least

 

20

 

cm

 

of

 

unobstructed

 

space

 

from

 

walls

 

or

 

other

 

elements

 

that

 

may

 

hamper

 

free

 

smoke

 

access

 

to

 

the

 

detector.

  

Two

 

holes

 

(with

 

72

mm

 

spacing)

 

should

 

be

 

drilled

 

in

 

order

 

to

 

install

 

extension

 

anchor

 

bolts

 

fixing

 

the

 

detector

 

to

 

the

 

ceiling.

 

In

 

case

 

the

 

detectors

 

are

 

intended

 

to

 

work

 

in

 

a

 

network,

 

they

 

should

 

be

 

linked

 

 

all

 

detector

 

GND

 

clamps

 

must

 

be

 

interconnected;

 

the

 

same

 

concerns

 

the

 

I/O

 

clamps.

 

When

 

cables

 

are

 

led

 

under

 

the

 

wall

 

plaster

 

(semi

flush

 

mounting),

 

the

 

base

 

should

 

be

 

drilled

 

in

 

its

 

centre;

 

in

 

case

 

of

 

on

plaster

 

cable

 

leading

 

(surface

 

mounting),

 

the

 

hole

 

should

 

be

 

drilled

 

in

 

the

 

base

 

side

 

wall

 

(suggested

 

hole

 

locations

 

are

 

shown

 

on

 

Fig.

 

1)

 

leaving

 

the

 

minimum

 

distance

 

from

 

the

 

bottom.

 

The

 

cables

 

should

 

be

 

placed

 

into

 

the

 

holes

 

and

 

then

 

the

 

base

 

should

 

be

 

fixed

 

in

 

the

 

place

 

intended

 

for

 

installation.

 

The

 

detectors

 

may

 

be

 

interconnected

 

using

 

a

 

typical

 

telecommunication

 

PVC

 

insulated

 

cable

 

of

 

0.12

 

 

0.5

 

mm

2

 

cross

 

section

 

(0.4

 

 

0.9

 

mm

 

diameter).

 

Two

 

wires

 

may

 

be

 

connected

 

to

 

one

 

contact

 

(wire

 

and

 

resistor

 

endings).

 

It

 

is

 

allowed

 

to

 

use

 

different

 

size

 

wires

 

(within

 

0.4

 

 

0.9

 

mm

 

range)

 

in

 

one

 

contact.

 

The

 

minimum

 

length

 

of

 

the

 

wire

 

protruding

 

from

 

the

 

base

 

is

 

5

 

cm.

 

Bare

 

(un

insulated)

 

ends

 

of

 

wires

 

(at

 

least

 

8

 

mm

 

long)

 

should

 

be

 

pushed

 

in

 

the

 

connector

 

taken

 

out

 

from

 

the

 

base

 

as

 

it

 

is

 

shown

 

on

 

Fig.

 

2.

 

The

 

clamps

 

of

 

the

 

connector

 

will

 

clench

 

the

 

wires

 

automatically.

 

 
 

 

Fig.

 

2

  

 

A

 

removal

 

of

 

a

 

wire

 

from

 

the

 

connector

 

is

 

possible

 

after

 

pressing

 

down

 

an

 

orange

 

blocking

 

push

button

 

with

 

a

 

finger

 

nail.

 

The

 

connector

 

with

 

the

 

wires

 

should

 

be

 

pushed

 

on

 

the

 

contact

 

pins

 

protruding

 

from

 

the

 

detector.

 

The

 

battery

 

should

 

be

 

connected

 

and

 

inserted

 

so

 

that

 

the

 

red

 

blocking

 

plate

 

pulls

 

back

 

according

 

to

 

the

 

Figure

 

3.

 

The

 

detector

 

operation

 

should

 

be

 

checked

 

by

 

pressing

 

down

 

the

 

test

 

push

 

button

 

for

 

few

 

seconds.

 

The

 

test

 

result

 

is

 

positive

 

when

 

a

 

LED

 

flashes

 

several

 

times

 

and

 

subsequently

 

an

 

acoustic

 

signal

 

is

 

heard.

 

The

 

inspected

 

detector

 

can

 

be

 

installed

 

in

 

the

 

base

 

turning

 

it

 

clockwise

 

until

 

the

 

catches

 

snap.

 

Summary of Contents for ADR-20N

Page 1: ...ADR 20N SELF CONTAINED OPTICAL SMOKE DETECTOR Installation and Maintenance Manual IK E289 003GB Issue 1A ...

Page 2: ...etector Application fire security Technical data IK E289 003GB manual Read the manual carefully before assembling and operation of the detector Any nonconformity with the instructions contained in the manual may be harmful or may cause violation of the law in force POLON ALFA shall not bear responsibility for any harms resulted from the unit application discordantly to the requirements of this ins...

Page 3: ... 38 Audio alarm volume 85 dB at 3 m distance Battery operation life 1 3 years depending on type 3 SAFETY CONDITIONS 3 1 Repairs and maintenance Any repair must be carried out by the manufacturer POLON ALFA bears no responsibility for the operation of any apparatus being serviced and repaired by unauthorised personnel 3 2 Works at height Any detector installation works carried out at height must be...

Page 4: ... inside the bottom The casing encloses a wire grid that prevents irruption of small insects or pieces of dirt Fig 1 The bottom is fixed to the casing with two screws 10 Two small devices protrude from the casing a test button 4 and an illuminating LED 8 that indicates the detector mode Fragments of a printed ...

Page 5: ...s are shown on Fig 1 leaving the minimum distance from the bottom The cables should be placed into the holes and then the base should be fixed in the place intended for installation The detectors may be interconnected using a typical telecommunication PVC insulated cable of 0 12 0 5 mm2 cross section 0 4 0 9 mm diameter Two wires may be connected to one contact wire and resistor endings It is allo...

Page 6: ...after smoke detection x x Low power supply voltage x x Detector testing with the TEST button x x Fault x In case a factor that causes a particular mode decays the detector automatically returns to its supervision mode Depending on the type of a battery used the detector operation period may vary ordinary batteries min 1 year the detector will work normally for at least 30 days since the first low ...

Page 7: ...ning is not effective it is allowed to wash the labyrinth with warm water with an addition of washing up liquid after cleaning and drying no water stain may be left on the labyrinth internal surfaces After cleaning reassemble the detector in the following order check whether the metal cover does not conceal the acoustic signalling device opening press the labyrinth down until its catches snap in t...

Reviews: