Politec S.r.l. | Installation manual NAT SENSOR – Ver. 1.10.1
8
4.
PROGRAMMIN AND OPERATION
Install the sensor Nat between 2 and 3 meters in height from the floor concerned following the
instructions on page 4. Connect the power supply according to polarity (10-16Vdc) and connect the
outputs Alarm, Tamper and Anti-Mask in central according to their usage requirements.
1
2
+/
GND
Power supply of NAT 10/16Vdc.
3
ANTI-
MASK
Negative open collector. Opens in
the event of masking.
4
LR
Aumento sensibilità microonda
se fornito un positivo
5
6
TMP
N.C. Tamper output. It opens in
case of sensor tampering.
7
8
ALARM
N.C. Alarm output. It opens in
case of detection MW+IR.
POWER LED ON FOR DETECTION TEST
Turn on the dipswitch number 4 for the
functionality of the LEDs detection.
1 2 3 4
ON
NB:
power on for the duration of about 30
seconds if the DIP4 of the LEDs is activated you
will see an alternate flashing of these, to stabilize
the system. Term of flashes you can proceed with
the following settings.
PIR RANGE (SENSITIVITY) 1-12m
REGULATION TRIMMER:
Adjust the PIR
range through the trimmer, implementing with
crossing test. Submitting ORANGE LED will
help to verify the detection of the passage in
different areas (exp. 0m, 4m, 7m, 12m). Test the
goodness of the coverage of the affected areas, by
adjusting the MW.
MW RANGE
(SENSITIVITY) 1-12m
REGULATION
TRIMMER:
Adjust the
microwave range through
the trimmer, implementing
with crossing test.
Submitting GREEN LED
will help to verify the
detection of the passage in
different areas (exp. 0m, 4m,
7m, 12m). Test the goodness
of the coverage of the
affected areas, by adjusting
the PIR.
1
2
3
4
5 6
7
8