Polaris PG10* 100-199-3NV Installation Instructions Manual Download Page 8

8

Vent Termination Locations

The air inlet and exhaust outlet must be installed with the 
following minimum clearances (see figure 6):

 

Twelve inches above grade or maximum anticipated 
snow level.

 

Twelve inches from any opening through which flue 
gases could enter the structure.

 

Four feet horizontally and vertically from gas or electric 
meters, gas regulators, dryer vents, vent hoods, bath-
room fan exhaust, attic fans and turbines.

 

Two feet from an inside corner formed by two exterior 
walls. 

 

Two feet from porches, decks, overhangs and  other 
obstructions.

In addition to maintaining the minimum clearances , the 
vent should terminate according to the following guidelines:

1.  

  Use only 2 inch pipe or a 2 inch concentric vent on 

the vent termination for 100,000 - 150,000 BTU/Hr 
models. For inputs of 175,000 BTU/Hr or more, use 
only 3 inch pipe or a 3 inch concentric vent. Do not 
expose any 3” X 2” reducers or bushings to out-
door ambient temperatures.

 

2.    The air inlet and exhaust outlet must not terminate 

under a patio, deck or any covered area.

3.   Do not terminate the vent near walkways or into alleys 

or other publicly accessible areas.

4.    Do not terminate the vent in an area where children      

or animals could block pipes.

5.    Do not locate the vent terminal too close to shrubs or 

bushes.

6.  Caulk all cracks, seams and joints within 6 feet horizon-

tally above and below the vent.

7.  Combustion air inlet termination and exhaust air termi-

nation must be located in the same pressure zone.

Figure 6: Minimum Clearances for Inlet/Outlet and Concentric Vent

A.

  12 in (30 cm) min. clearance above grade, 

veranda, porch, deck, balcony, or maximum 

anticipated snow level.

B.

  12 in (30 cm) min. clearance on top and side of 

window or door that may be opened. Do not install 

below a window or door that may be opened.

C.

  Clearance to permanently closed window.**

D.

  12 in (30 cm) min vertical clearance to ventilated 

soffit located above the terminal within a horizontal  

distance of 2 ft (61 cm) from the center line of the  

terminal.

E.

  12 in (30 cm) min. clearance to unventilated soffit.

F.

  Clearance to outside corner **

G.

  2 ft (61 cm) clearance to inside corner formed by 

two exterior walls.

H.

  4 ft (122 cm) clearance to each side of center line 

extending above meter/regulator assembly.

I.

 

4 ft (122 cm) clearance to service regulator vent 

outlet.

J.

  12 in (30 cm) clearance to nonmechanical air 

supply inlet to building or the combustion air inlet 

to any other appliance.

K.

  3 ft (91 cm) above if within 10 ft (3 m) horizontally of 

mechanical air supply inlet.

**Clearance in accordance with local installation codes and the requirements of the gas supplier. 

A.

  12 in (30 cm) min. clearance above grade,    

 

veranda, porch, deck, balcony, or maximum    

 

anticipated snow level.

B.

  12 in (30 cm) min. clearance on top and side of  

 

window or door that may be opened. Do not install  

 

below a window or door that may be opened.

C.

  Clearance to permanently closed window.**

D.

  12 in (30 cm) min vertical clearance to ventilated  

 

soffit located above the terminal within a horizontal  

 

distance of 2 ft (61 cm) from the center line of the  

 terminal.

E.

  12 in (30 cm) min. clearance to unventilated soffit.

F.

  Clearance to outside corner. **

G.

  2 ft (61 cm) clearance to inside corner formed by  

 

two exterior walls.

H.

  3 ft (91 cm) within a height 15 ft (4.57 m) above the  

 meter/regulator 

assembly.

I.

  4 ft (122 cm) clearance to service regulator vent outlet.

J.

  12 in (30 cm) clearance to nonmechanical air  

 

supply inlet to building or the combustion air inlet to  

 

any other appliance.

K.

  6 ft (1.83 m) clearance to mechanical air supply inlet.

US Installations

Canadian Installations

Summary of Contents for PG10* 100-199-3NV

Page 1: ...have the following information ready 1 Model number 2 7 Digit product number 3 Serial number 4 Date of installation 5 Place of Purchase Table of Contents 2 Do not store or use gasoline or other flamm...

Page 2: ...mend the hot water faucet be opened for several minutes at the kitchen sink before using any electrical appliance which is connected to the hot water system If hydrogen is present there will probably...

Page 3: ...ples of qualified service technicians include those trained in the plumbing and heating industry local gas utility personnel or an authorized service person The manufacturer and seller of this water h...

Page 4: ...ce Maintain proper clearances as specified on the data plate Figure 1 Garage Installation Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other applia...

Page 5: ...sembly should be glued to the exhaust pipe see figure 3C Note The trap should be aligned so that the exhaust pipe is in a vertical position close to the surface of the water heater Figure 2 Minimum Cl...

Page 6: ...ctions can be found in this manual in state or local codes or the authority having jurisdiction or in the absence of such the National Fuel Gas Code ANSI Z223 1 NFPA 54 Latest Edition Canadian install...

Page 7: ...ipe 4 Concentric Vent Through the Wall 5 Concentric Vent Through the Roof All pipe fittings pipe cement primers and procedures must conform to American National Standard Institute and American Society...

Page 8: ...op and side of window or door that may be opened Do not install below a window or door that may be opened C Clearance to permanently closed window D 12 in 30 cm min vertical clearance to ventilated so...

Page 9: ...the water heater as possible This is to drain any water that may be in the combustion air pipe and prevent it from entering the blower Connect the trap drain line to a suitable drain or downstream of...

Page 10: ...gure 9A for the proper location of the air inlet with respect to the exhaust outlet termination The vertical exhaust outlet termination is a 2 inch pipe which terminates at least 12 inches above the i...

Page 11: ...ures 10A 13Abelow for vent terminal specifications Note For replacement installations previously installed American Water Heater Company supplied concentric vent kits are acceptable for use on 100 000...

Page 12: ...d inward Install a drain tee assembly and trap in the inlet vent as close to the water heater as possible This is to drain any water that may be in the combustion air pipe and prevent it from entering...

Page 13: ...for the proper location of the air inlet with respect to the exhaust outlet termination The vertical exhaust outlet termination is a 3 inch pipe which terminates at least 12 inches above the inlet ai...

Page 14: ...for vent terminal specifications Figure 11B Through the Wall Termination Figure 12B Through the Roof Termination Figure 13B Concentric Vent Piping Installation Note For concentric venting terminations...

Page 15: ...in along the top side of the nipple 34 50 gal models only Connect the hot water supply 50 gal and below use 1 NPT 100 gal use 1 1 2 NPT to the fitting marked HOT OUTLET 2 Always use a suitable grade o...

Page 16: ...ng which will contaminate the potable water supply Closed System Thermal Expansion When a backflow prevention device or check valve is installed it can create a Closed System Heating water in a closed...

Page 17: ...empering valve or supply line to the heating system to remove air bubbles from the system Do not connect the water heater to any system or components previously used with non potable water heating app...

Page 18: ...ter than or equal to the input rating of the water heater The Discharge Line Must not be smaller than the pipe size of the relief valve or have any reducing coupling installed in the discharge line Mu...

Page 19: ...ence figure 19 for gas piping installation 1 Install a readily accessible manual shut off valve in the gas supply line as recommended by the local utility Know the location of this valve and how to tu...

Page 20: ...Nationally listed recognized fuel gas and carbon monoxide CO detectors are recommended in all applications and should be installed using the manufacturer s instructions and local codes rules or regula...

Page 21: ...ervice box 2 Loosen the screws securing the access panel to the electrical compartment The electrical wiring diagram for 34 50 gal models can be found on the inside of the access panel at the base of...

Page 22: ...ND GND GND FUSED DISCONNECT L1 NEUTRAL GND PSI PSO PRESSURE SWITCH BLACK WHITE WHITE RED LED YELLOW LED GREEN LED BROWN YELLOW RED THERMOSTAT DIAL ORANGE GAS VALVE BROWN BLUE BLUE WHITE IGNITER RED GR...

Page 23: ...ds the heater at 1 8 per foot Away from corners other vents windows etc Alternate Horizontal Correct relationship outlet to inlet 12 Min above anticipated snow level 2 exhaust outlet air inlet pipe sl...

Page 24: ...calling for heat which signals the beginning of the ignition sequence see figure 21 and Red Ignition control is signaling the gas valve to open Figure 21 Sequence of Operation When the thermostat call...

Page 25: ...systems used with this water heater are designed for temperatures higher than 130 F Refer to the manufacturer s instruction manuals supplied with this type of equipment for recommended temperature se...

Page 26: ...nnect a hose to the drain valve and terminate it to an adequate drain Note The drain hose should be rated for at least 200 F If the drain hose does not have this rating open the cold water inlet valve...

Page 27: ...umber 6903775 7 Remove the gas valve from the unit keeping the rubber gasket with the gas valve 8 Remove the flange from the gas inlet side of the valve by removing the four 4 attachment screws Figure...

Page 28: ...y Detection SC SL Soft Lockout Control Automatically resets after 60 minutes SL3 Soft Lockout Hard Lockout Control automatically resets after 60 minutes with a maximum of 3 resets followed by hard loc...

Page 29: ...OFTWARE OPERATION SEQUENCE IGNITION CONTROL MODULE SOFTWARE OPERATION SEQUENCE For 175 000 BTU Hr models and above the flame establishing period is six seconds For the first 3 seconds the gas valve is...

Page 30: ...34 DRAIN VALVE 35 POTENTIOMETER 36 VENTURI GASKET not pictured 37 BLOWER ISOLATION RELAY 150 000 BTU Hr TOOLS REQUIRED FOR SERVICING TOOL FUNCTION VOLT OHMMETER MEASURE VOLTAGE RESISTANCE CLAMP ONAMM...

Page 31: ...34 DRAIN VALVE 35 TEMPERATURE AND PRESSURE RELIEF VALVE TOOLS REQUIRED FOR SERVICING TOOL FUNCTION VOLT OHMMETER MEASURE VOLTAGE RESISTANCE CLAMP ONAMMETER MEASURE CURRENT STOPWATCH CLOCK GAS CONSUMPT...

Page 32: ...3 48 1 2 22 15 3 4 40 1 2 41 6 3 8 5 1 2 6 5 8 150 PG10 50 130 2NV OR 2PV 50 130 2 OR 3 62 3 8 22 15 3 4 54 1 2 55 6 3 8 5 1 2 6 5 8 176 PG10 34 150 2NV OR 2PV 34 150 2 OR 3 48 1 2 22 15 3 4 40 1 2 4...

Reviews: