source. If the gas is lighter than air, position the gas detector at a height of 0.3 - 1.0 m from the ceiling, within 

a radius of max. 1.5 m from gas source.

3. Fix the screws securely to the wall, then position the gas detector.

4. Avoid installing the gas detector near the following sources: direct air flow caused by wind, fans, open doors 

or windows, steam sources, oil vapors, etc.

5. Any installation of a wired device must comply with the national laws in force. The wires must have the 

correct size and color, to avoid wrong connections. A wrong wiring connection can have repercussions in the 

event of an alarm caused by gas leaks.

CONNECTIONS

   Power input                Valve

INSTRUCTIONS FOR USE

The gas detector can be used independently or together with an solenoid valve.

USE OF GAS DETECTOR INDEPENDENTLY

1. Choose the right place to install the gas detector. Follow the installation instructions.

2. Power the gas detector to a 230V power source. The green LED will blink once per second for 3 minutes, 

the time required to heat the sensor. After priming the sensor, the detector will emit a short sound to alert you 

that it has entered normal operating state. The LED will continue to flash.

USE OF GAS DETECTOR TOGETHER WITH SOLENOID VALVE 

1. Choose the right place to install the gas detector. Follow the installation instructions.

2. Power the gas detector to a 230V power source. The green LED will blink once per second for 3 minutes, 

the time required to start the sensor. After priming the sensor, the detector will emit a short sound to alert you 

that it has entered normal operating state. The LED will continue to flash.

3. If the detector identifies a gas leak, the red LED blinks, while the built-in siren emits a repetitive “Di ... Di” 

alarm sound. If the detector is connected to a solenoid valve, it will transmit a pulse to it, which will cause this 

device to stop the gas supply. The gas detector will return to its initial state of operation after the gas dispersion 

or after restarting the detector.

4. If the siren emits a long sound and the red LED is on - indicates an internal sensor error. Turn off the power 

and contact a service center.

5. If the detector is operating in a discordant manner, switch off the power supply and contact a service center.

Summary of Contents for PNI-SH200

Page 1: ...PNI SAFE HOUSE 200 Gas detector and valve Rivelatore di gas e valvola Senzor de gas si electrovalva EN User manual 2 IT Manuale utente 7 RO Manual de utilizare 12...

Page 2: ...t 230V Sensor priming time about 180 seconds Sound intensity 85dB m Alarm level 20 LEL Lower Explosive Limit Gas density alarm level 0 1 0 5 Alarm indicator Flashing red LED Error indicator Red LED an...

Page 3: ...sensor After priming the sensor the detector will emit a short sound to alert you that it has entered normal operating state The LED will continue to flash USE OF GAS DETECTOR TOGETHER WITH SOLENOID...

Page 4: ...shing red LED Gas leakage Red LED on Sensor error Flashing green LED 0 5s on 0 5s off Sensor warming up WARNINGS 1 The gas detector must be installed and connected correctly 2 The gas detector must be...

Page 5: ...of the gas installation will be performed Use caution when the solenoid valve needs to be restarted RECOMMENDATIONS FOR INSTALLATION 1 The solenoid valve will only be installed by qualified personnel...

Page 6: ...transparent cover has the role of protection against accidental actuation of the red button SENSOR CONNECTION WITH SOLENOID VALVE The connection between the gas sensor and the solenoid valve is play...

Page 7: ...mpo di adescamento del sensore 180 secondi Intensit del suono 85dB m Livello di allarme 20 LEL Lower Explosive Limit Densit del gas di allarme 0 1 0 5 Indicatore di allarme LED rosso lampeggiante Indi...

Page 8: ...l tempo necessario per avviare il sensore Dopo aver innescato il sensore il rilevatore emetter un breve suono per avvisare che entrato nel normale stato operativo Il LED continuer a lampeggiare USO DE...

Page 9: ...tamente le istituzioni specializzate o una persona qualificata INFORMAZIONI SUI LED LED rosso lampeggiante Perdita di gas LED rosso acceso Errore del sensore LED verde lampeggiante 0 5 secondi acceso...

Page 10: ...iparazioni 4 Dopo aver chiuso l elettrovalvola verr eseguita un ispezione dell installazione del gas Prestare attenzione quando necessario riavviare l elettrovalvola CONSIGLI PER L INSTALLAZIONE 1 L e...

Page 11: ...dentale del pulsante rosso dell attuatore COLLEGAMENTO DEL SENSORE CON ELETTROVALVOLA Il collegamento del sensore di gas con l elettrovalvola viene inserito nella presa play plug senza altre regolazio...

Page 12: ...p amorsare senzor Aprox 180 secunde Intensitate sonora 85dB m Nivel de alarma 20 LEL Lower Explosive Limit Densitate gaz nivel alarma 0 1 0 5 Indicator alarma LED rosu intermitent Indicator eroare LED...

Page 13: ...te timp necesar amorsarii senzorului Dupa amorsarea senzorului detectorul va emite un sunet scurt pentru a atentiona ca a intrat in starea normala de functionare Ledul va continua sa clipeasca FOLOSIR...

Page 14: ...itent Scurgere de gaz LED rosu aprins Eroare senzor LED verde intermitent 0 5s aprins 0 5s stins Incalzirea senzorului AVERTIZARI 1 Detectorul de gaz trebuie instalat si conectat in mod corect 2 Detec...

Page 15: ...hiderea electrovalvei se va realiza o inspectie a instalatiei de gaz Umblati cu prudenta atunci cand electrovalva trebuie repornita RECOMANDARI PENTRU INSTALARE 1 Electrovalva se va instala numai de c...

Page 16: ...e a butonului rosu de actionare CONECTAREA SENZORULUI CU ELECTROVALVA Conectarea senzorul de gaz cu electrovalva se face mufa in mufa plug play fara alte ajustari insa ambele produse se pot adapta si...

Reviews: