User manual
26
En
gli
sh
18
Floating load
24V model default settings: 27.0V
If “User-Defined” is selected in program 14, this
program can be set. The range that can be set is
between 24.0V and 29.2V for 24Vdc. Each click
increases the value by 0.1V
19
Low DC voltage
setting (cut off
voltage)
24V model default settings: 20.4V
If “User-Defined” is selected in program 14, this
program can be set. The range that can be set is
between 20.0V and 24.0V for the 24Vdc model.
Each click increases the value by 0.1V.
20
Battery discharge
voltage interruption
when power from
the public grid is
available
Options for the 24V model:
23V (default)
Range 22.0V - 29.0V
Each click increases the
value by 0.1V
21
Interruption of the
battery charging
voltage when the
power from the
Utility is available
Options for the 24V model:
27.0V (default)
Range 22.0V - 29.0V.
Each click increases the
value by 0.1V
22
Display interface
The screen will display the
main interface
The last page used by the
user is displayed on the
screen