Getting Started with the Eagle™
••••
16
Eagle™ Specifications
Input
AC Voltage 0 to 600VAC
AC Current 0 to 5000 Amps
Sample rate: 15,360 samples
per second per
channel (256
samples/cycle)
Measured Quantities
RMS Voltage
(Volts)
RMS Current
(Amps)
Real Power
(Watts)
Apparent Power
(VA)
Reactive Power
(VAR)
Phase Angle
(Degrees)
Power Factor
(Watts/VA)
Displacement PF
(cos(phase angle))
Power Usage
kWh, kVARh, kVAh
Frequency Hz
Accuracy (-20°F to 135°F)
Accuracy
Percent of full scale
Voltage
0.33 %
Current
1.0 %
Power
1.0 %
Phase Angle
1 degree
Power Factor
±
0.02
Information Storage
Memory
RAM
128K (battery-
backed)
FLASH EPROM
8MB
DSP Waveform RAM up to 256K
Waveform capture:
Triggered
Harmonics
Voltage
Measures to the 51
st
Current
Measures to the 51
st
Measures:
Magnitude, Phase,
THD
Capacity
Summary data
Over 1 year
Event data
1000 records
Flicker data
1000 records
Interval Graphs
4 hrs to over 1 yr
Record Settings
Interval Graphs
1 cycle to 4 hours
Significant change
1V to 8V
Flicker settings
User-defined or
standard (IEEE141)
Communications
Type USB
Bluetooth
®
Wireless
Power Supply Requirements
Voltage
60-600VAC Chan 1
Power
1.5 Watts max
Environmental
Operating temperature -30C to +55C
Relative Humidity
≤
85%
Max Altitude
2.0km (6560 ft)
Case Protection
IP65
Physical Dimensions
Size 5.40”L x 3.00”W x 1.25”H
Weigh <1.0 lbs.
Case NEMA 4X
Power Fail Operation
The device operates with no input voltage
for more than 2 hours. This allows it to
measure down to 0 volts on all channels
during power outage periods.
Internal Batteries
Not user replaceable
Memory Backup: 3V Lithium coin
Battery voltage check: Automatic
Implementation of new developments and product improvements may result in specification
changes in this document