DIAGNOSIS/BEHAVIOR ON ERROR
If the master fails or the bus connection
is interupted (communication error) the
last setpoint remains active and the
KS 94 works independently. If the mas-
ter PLC is switched in stop-mode the
Clear Data Signal will be suppressed and
the last setpoint remains active, too! In
case of a fault on the bus, the KS 94 can
activate an alarm relay.
Plain-text display on the controller front:
·
Master missing
·
Parameter error
·
Configuration error
·
Loss of master
CABLE
According to EN 50170 Vol. 2
TRANSMISSION SPEEDS AND
CABLE LENGTHS
Automatic transmission speed detection
Speed
Max. cable length
9,6 kbit/s
1200 m
31,25 kbit/s
1200 m
45,45 kbit/s
1200 m
187,5 kbit/s
1200 m
500 kbit/s
400 m
1,5 Mbit/s
200 m
3 Mbit/s *
100 m
6 MBit/s *
100 m
12 Mbit/s *
100 m
*
Sub-D adapter 9407-998- 00031 required!
ADDRESSES
0...126 (factory setting: 126)
Remote setting of address allowed
OTHER FUNCTIONS
Sync and Freeze
TERMINATING RESISTORS
Internally selectable with wire-hook
switches
Required Accessories
ENGINEERING SET
Content:
·
GSD-file
·
Manual, data description
·
Function blocks for Step5, Step7 used
for reading and writing of parameter
and configuration data via parameter
channel.
Universal S5 Function Block for
Parameter Channel
By needs of this FB the parameter chan-
nel can be used in P- and Q-tiles,
extended P-area and together with the
special function block FB IM380C.
KS 94 PROFIBUS
3
C
}
}
Option C
Option B
PROFIBUS-DP
VP (5V)
GND
RxD/TxD-N
RxD/TxD-P
Adapter
OUT2
oder
or
24 V
di 1 ( )
di 2 ( )
+ Volt
+ mA
_ Volt / mA
-
+
+
24 V
di 8 ( )
di 9 ( )
di 10 ( )
di 11 ( )
di 12 ( )
do 5
do 6
GND
+
_
+
_
+
_
-
+
+
+
+
+
+
.
-
+
+
+
+
+
+
24 V
di 3 ( )
di 4 ( )
di 5 ( )
di 6 ( )
di 7 ( )
do 1
do 2
do 3
do 4
90...250V
24 V UC
Fig. 1 Connection diagram KS 94/DP:
galvanic isolation
Fig. 2 Sub-D adapter:
96
96
96
105
min.
0 C
60 C
max.
%
max.
95% rel.
92
+0,8
92
+0,8
1...16
160
8.8.8.8
8.8.8.8
M3/h
Y:ûûûûûî
55%
Fig. 3 Dimensions (in mm):
Fig. 4 Selection of data content by means of the Engineering Tool (process data module e, f, g):