CONFIGURABLE PROCESS DATA

MODULES

Module a (I/O):

process data

read

process value (xeff)

output value (yeff)

set-point (weff)

status

write

set-point (w)

output value (yman)

auto/manual

no parameter channel

Module b (I/O + parameter channel):

process data

read

process value (xeff)

output value (yeff)

set-point (weff)

status

write

set-point (w)

output value (yman)

auto(manual

parameter channel

Module c (extended I/O + parameter):

process data

read

process value (xeff)

output value (yeff)

set-point (weff)

status

inputs (INP+di)

write

set-point (w)

output value (yman)

auto(manual

outputs (OUT+do)

parameter channel

Module d (ext.. I/O + f

parameter):

process data

read

process value (xeff)

output value (yeff)

set-point (weff)

status

inputs (INP+di)

write

set-point (w)

output value (yman)

auto(manual

inputs (INP+di)

parameter channel

Module e (va para. channel):

process data

read

status word1+2

IN1...IN16

write

control word 1+2

OUT1...OUT16

parameter channel

Module f (va para. channel):

process data

read

status word1+2

IN1...IN6

write

control word 1+2

OUT1...OUT6

parameter channel

Module g (multiplex transmission):

process data

read

status word1+2

Index IN (1...16)

IN

write

control word 1+2

Index OUT (1...16)

OUT

no parameter channel

Memory requirements (byte):

Module

read

write

FIX

REAL

FIX

REAL

a

8

14

6

10

b

16

22

14

18

c

30

46

20

28

d

30

46

26

40

e

44

76

44

76

f

24

36

24

36

g

8

10

8

10

Writing of inputs/outputs can be acti-

vated individually for each input and

output.

DATA CONTENTS (MODULES

E,F,G)

Status words 1 and 2

·

Reading the digital inputs

·

Sensor break/short-circuit status

·

Error and status information

·

Alarms and controller outputs

·

Automatic or manual operation

Control words 1 and 2

·

Automatic/Manual switch-over

·

Controller off/Set-point switch-over

·

Forcing of digital inputs

·

Forcing/enabling of digital outputs

·

Local/Remote switch-over

Inputs IN1...IN16

The data to be read from the KS 94 can

be defined by means of the Engineering

Tool ET/KS 94 (Version 4.0 upwards).

It is possible to access all signals and pa-

rameters (

ð

Fig.4).

Outputs OUT1...OUT16

The data to be transmitted to the KS 94

can be defined by means of the Engi-

neering Tool ET/KS 94 (Version 4.0

upwards). It is possible to access all sig-

nals and parameters (

ð

Fig.4).

FUNCTIONS

Enabling the controller outputs

The control word allows you to en-

able/disable the digital controller outputs.

De-centralized I/O

All inputs and outputs of the KS 94 are

directly accessible via the I/O memory

area. In this way it is possible to make

use of additional input/output functions

apart from the control function. Analog

values are transmitted in the scaled for-

mat.

Input forcing

All physical inputs can be overwritten via

the PROFIBUS-DP. In this way it is pos-

sible e.g. to define individual elements of

a multi-element control loop via the bus,

or to let the PLC compute corrections for

process value/set-point.

Back-up controller mode

During “normal” operation, the control

output is computed by the master. The

KS 94 is used to measure the process

values, to generate the control output

signal, and for display.

If the master or the bus communication

should fail, the KS 94 takes over auto-

matically and bumplessly.

CONNECTION

AMP flat-pin terminals 1 x 6,3 mm or

2 x 2,8 mm.
By needs of an adapter (

ð

Accessories)

Sub-D connectors or screw terminals

can be used.

2

KS 94 PROFIBUS

&

controller

digital output

(do, OUT)