DES-P Digital Engine Supervisor
Cat_DES-P-09-GSM new Ver 2.0
Page
7/9
19
Disp Auto Scroll Setting ON will enable Auto Scroll of
display.
OFF: No scroll and next parameter can
be viewed by pressing next
ON ON/OFF
20
Emer Sol Time
This setting is to protect the fuel solenoid
in case the Stop button or Emergency is
kept pressed. In such a case the solenoid
shall be released after this time.
22 Sec
1-100Sec
21
RPM Ratio
Gear ratio multiplier for charging
alternator.
1.00 0.5-1.5
22
Crank Time
Maximum Permissible Crank Time
5 Sec
1-25 Sec
* This parameter can be disabled while programming
9.2
Fault History.
To view the last 20 fault history enters in this mode as explained above. Maximum of last 20
faults along with Run Hour stamp shall be displayed on the LCD. The first row shall display
the fault and the next row shall display the run hour at which the fault has occurred. The next
fault can be viewed by pressing “NEXT”. The mode shall exit to normal mode after the last
fault recording is displayed. Absence of any fault recoding shall not display any fault data.
9.3
Resting Service Hours.
Service due, warning is issued by DES-P, by flashing the Ser LED. This LED shall keep
flashing till it is not reset by entering this mode. Pls refer Para 9 for procedure to reset service
hour
9.4
Programming Solenoid Mode
For changing the solenoid mode first press
(R) (reset) button, than press + button while
the reset button is pressed.
Fuel Solenoid:
In this mode fuel solenoid contact changes from Open to Close at the
time of cranking and remains close till the engine is running. For stopping the generator
this contact opens.
Stop Solenoid:
In this mode fuel solenoid contact remains open at the time of cranking
and till the genset is running. For stopping the engine this contact closes for a user
programmed time.
Don’t change the mode while engine is running. It’s a good practice to switch OFF and
than switch ON the battery supply after changing this mode.
10.0
Faults
There are two categories of faults
Internal Faults
External faults
10.1
Internal Faults
Internal faults are the faults, which do not need any external signals and are detected by the system
itself. They are:
LLOP
Fuel
HWT
10.2
External Faults
Those faults which cannot be sensed by the unit itself (these faults are not reflected by the engine
directly) and are to be provided externally. They are:
RWL