background image

DES-P Digital Engine Supervisor 

 
 

Cat_DES-P-09-GSM new Ver 2.0 
  

Page 

4/9 

 

 

1.0

 

Introduction 

 

16 Bit RISC, state of art, 
microcontroller based System. 

 

True RMS measurement of all 
measured parameters with 1% accuracy 
of measured value (Not full scale) 

 

Backlit LCD Display for easy reading 
and parameter settings. No need to 
consult the manual while programming 
the unit. 

 

All the inputs, such as Generator and 
Battery voltages are fully isolated, 
providing the freedom to design a 
totally isolated system. This avoids and 
prevents malfunctioning/ burning of the 
unit. 

 

Fully operational up to 4V. Can 
withstand a voltage dip up to 0V for 
1sec. 

 

All system parameters are user 
programmable 

 

Measurement and display of LLOP, 
Fuel Level and HWT 

 

Records last 20 faults  

 

Suitable for all types of engines 

 

All digital inputs are optically isolated 
for enhanced reliability 

 

All outputs are through potential free 
contacts for system stability and 
reliability 

 

All contacts are protected by TVS to 
strengthen the EMI/EMC capabilities of 
the unit. 

 

Housed in 92X92mm Din Standard 
housing. 

 

2.0

 

Protection, Supervision Salient features  

 

Oil Pressure 

 

HWT 

 

RWL 

 

Emergency  

 

 

 

Low Fuel 

 

Charging Alternator Fail/V-Belt 

 

Choice of selective sensor measurement 
display 
 

3.0

 

Measurement & Display 

DES-P equipped with LCD display and displays 

 

Battery Voltage 

 

Generator Run Hour 

 

RPM 

 

Oil Pressure in KG/cm2 
 

 

Water Temp in degree centigrade  

 

Fuel Level in % 

 

Programmed settings 

 

Service Hour 

 

Normally the display auto scrolls and displays a set of parameter for 10 seconds, but any time the 

Next key (

Ï

) can be pressed to select the next parameter window. 

 

4.0

 

Annunciations  

DES-P is equipped with the following annunciations for system status and faults: 

 

LLOP  

 

HWT 

 

Low Fuel  
 

 

RWL  

 

Charging Alternator/ V-Belt 

 

Emergency 

 

 

5.0

 

Contacts  

The following digital Output are provided. Annunciation contacts are available in models requested 
with Annunciation features.

 

Crank (NO Contact) 

 

Solenoid (NO Contact) 
 

 

Hooter  (NO Contact) 

 

Electrical Feed for Charger ON (+12V) 

 

 
 

Summary of Contents for Procom DES-P

Page 1: ...organization Works Unit1 E 41 5 Okhla Industrial Area Phase II New Delhi 110020 Unit2 T 13 Okhla Industrial Area Phase II New Delhi 110020 Ph 011 30883538 41 9810344265 9310883837 Fax 0 1130883536 Em...

Page 2: ...DES P Digital Engine Supervisor Cat_DES P 09 GSM new Ver 2 0 Page 2 9...

Page 3: ...nnunciations 5 0 Contacts 6 0 Timers 7 0 Switches Description 8 0 Operation 9 0 Setting Procedure 9 1 Parameter Settings 9 2 Fault History Viewing 9 3 Service Hour Resetting 9 4 Programming Solenoid M...

Page 4: ...acts for system stability and reliability All contacts are protected by TVS to strengthen the EMI EMC capabilities of the unit Housed in 92X92mm Din Standard housing 2 0 Protection Supervision Salient...

Page 5: ...f 1 Sec shall reset both 5 R Programming Mode Entry Press R Key and than press while the R Key is pressed to enter the programming mode 8 0 Operation DES P is an engine monitoring and supervisor unit...

Page 6: ...sure switch and not through the oil pressure sensor linear measurement All sensors All sensors Fuel HWT Fuel LLOP LLOP HWT Fuel Only HWT Only LLOP Only No sensor 7 Fuel Level in Level of fuel at which...

Page 7: ...Service Hours Service due warning is issued by DES P by flashing the Ser LED This LED shall keep flashing till it is not reset by entering this mode Pls refer Para 9 for procedure to reset service hou...

Page 8: ...1 Auxiliary supply ve 12 Crank NO Contact 13 Solenoid NO Contact 14 Charging Alternator On 15 Hooter 16 Common for All Contacts 17 Remote Start 18 Remote Stop 19 Not Connected 20 Not Connected 21 Not...

Page 9: ...8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 Not Connected Not Connected Not Connected Not Connected Oil Pressure Sensor Switch Water Temp Sensor Switch Low Fuel Sensor Switch RWL Switch Ch Alt Ve W...