Page 18 of 27
Small potentially blocked or shadowed floor areas shall be permitted on a horizontal plane in compartments
of 64 m
2
(two pump units) or less as long as the maximum area of the total contiguous shadowed floor area,
regardless of geometric configuration, does not exceed 2 m
2
.
Preliminary Automist designs can be recommended by specifiers by following these recommendations,
however, Plumis accredited installers are trained to specify, install, commission and maintain the Automist
system. Their early involvement in the project is recommended as they are required to verify installation
proposals, provide critical supporting technical information and also commissioning certificates for project
approval by Building Control or other involved third parties.
5m
5m
Correct
Incorrect