background image

Page 21 of 27

The test setups run at the BRE consisted of a simulated furniture fire and a kitchen fire.  All fires were run 
in either a 4 m x 4 m x 2.5 m room or a larger 8 m x 4 m x 2.5 m room with doors open or closed.  The door 
openings were 1m wide and 2.1 m high. The tests by BRE measured the gas concentrations to determine 
FED Asphyxia at a position 3 m away from the fire and at heights of 0.6 m and of 1.8 m.  Temperatures were 
measured at a position 2 m away from the fire and at heights of 0.6 m and of 1.8 m. 

Furniture Test Setup

The furniture fire used the same configuration of fuel load and room layout as in the proposed watermist 
draft standard (DD 8458-1), the traditional sprinkler standards (EN 12845 2004 and BS 9251:2005) and 
the Scandinavian SRSA/DSB standard.  This is the industry’s well established fire test setup originated by 
the International Maritime Organisation (IMO). Below is a detail of the furniture test layout.

The setup consists of two polyurethane foam sheets and a wood crib placed above a fuel tray containing 
water and heptane and positioned in the corner of the test room. Four marine grade untreated plywood 
panels, each measuring 1.2 m x 2.4 m in size and 12 mm thick forms the walls in the corner of the test room.  
The foam sheets consist of two 100 mm thick pieces of polyurethane foam with a density of approximately 
18 kg/m

3

. The sheets are 810 mm wide, 760 mm high and were glued onto a 4 mm thick board of untreated 

plywood using contact adhesive. The distance from the edge of the board to the foam is 30 mm at the 
bottom edge and 15 mm along the edge of each side. The sheets of plywood were 840 mm wide and 790 mm 
high and are securely bolted to a supporting structure which holds them in an upright position.

Kitchen Test Setup

The simulated kitchen fire setup represents a simple kitchen arrangement made of ‘standard’ materials 
commonly found in domestic kitchens. The cupboards consist of laminated chipboard panels and the 
worktop is made of solid wood. The empty kitchen units are 1800 mm wide and divided into three sections 
of 600 mm each. The upper cupboards were 700 mm high and 300 mm deep. The lower cupboards are 700 
mm high and 600 mm deep.  No shelves are installed in any of the cupboards.  The worktop is 880 mm 
above the floor. The distance between the worktop and the underside of the upper cupboards is 580 mm. 
The kitchen fitted is typical of standard styles available at leading furniture outlets.

Summary of Contents for Automist Series

Page 1: ...sults from a test suite at BRE Global to enable building control and fire industry professionals to assess or specify Automist Plumis Ltd Seamless Fire Protection www plumis co uk A technical guide fo...

Page 2: ...correctly installed and maintained in accordance with its instruction manual Automist is designed to operate in a manner similar to that demonstrated in the testing performed at BRE Global subject to...

Page 3: ...d Details Scheme Automist is covered by Registered Detail RD171 Those wishing to compare Automist directly to a conventional BS9251 sprinkler system in greater detail should refer to section 8 2 of th...

Page 4: ...d as our recommendations however these may need modification during the course of negotiation with approving authorities with regard to a specific project specification a Automist wall mount kit 3N 3...

Page 5: ...watermist nozzles High pressure hose Stainless steel braided 3 4 water supply hot cold water supply pipes Fused connection unit on a separate circuit Automist supply label cable tie Wired or wireless...

Page 6: ...ip pan fire can greatly exacerbate the fire the same is not true for water mist as the updraught from the flame and the evaporation of the tiny droplets prevents water from reaching and collecting in...

Page 7: ...00 mm gaps are gap between the pump perimeter and the enclosures Protected electrically by suitable fusing and powered by an independent circuit either via a delayed action RCD or no RCD 1 7kW 230V an...

Page 8: ...ked so that any heat alarm sounding in the protected areas will activate the Automist unit Where multiple Automist units serve a single area these must be similarly interlinked with a separate relay o...

Page 9: ...ocally excluding oxygen reducing temperatures and thus inhibiting the combustion reactions of the fire Fire growth is restricted This is achieved through the reduction in temperatures and slowing of c...

Page 10: ...g design flexibility Whilst the above guides have focused specifically on residential sprinklers they do not exclude any form of fire suppression as a potential alternative Paragraph 0 18 of Approved...

Page 11: ...ly Fractional Effective Dosage FED measurements and free burn control tests were included to allow a complete and objective assessment These tests were run in BRE Global s Watford UK Burn Hall and mim...

Page 12: ...Configuration At a system performance level it is necessary to demonstrate that Automist is fit for purpose in domestic buildings As discussed earlier at a component level the Automist system is CE m...

Page 13: ...rt 2 Heat Detector Sounder linked to the Automist control panel and water mains supply valve Achieved Areas of Coverage Whole house apartment coverage Identified fire risk room s Achieved As a fire en...

Page 14: ...ts the Automist is capable for being run for extended periods more easily than residential sprinklers with less potential water damage Commissioning Pressure test to 1 5 times the working pressure or...

Page 15: ...he fire at an early stage minimising heat and smoke generation and providing cooling to improve the potential for escape Providing a protected route out from the loft rooms to a final exit at the grou...

Page 16: ...his guidance cannot be achieved there is the potential for debate over the most appropriate and practical solutions Approved Document B would suggest that dry rising water mains be provided where basi...

Page 17: ...that a single pump can cover an area of up to 32m2 with a maximum ceiling height of 5m Based on Plumis s experimental data from BRE spray heads must be located within 5m line of sight of any possible...

Page 18: ...ry Automist designs can be recommended by specifiers by following these recommendations however Plumis accredited installers are trained to specify install commission and maintain the Automist system...

Page 19: ...aining Automist is an innovative fire suppression unit which can be installed as a compensatory measure for layouts that don t match the conventional prescriptive guidance from Approved Document B or...

Page 20: ...of asphyxiant gases results in cerebral hypoxia insufficient oxygen available to brain tissue which leads to collapse with loss of consciousness followed by death if the exposure is prolonged The inha...

Page 21: ...ntreated plywood panels each measuring 1 2 m x 2 4 m in size and 12 mm thick forms the walls in the corner of the test room The foam sheets consist of two 100 mm thick pieces of polyurethane foam with...

Page 22: ...hroughout the 30 minutes of test period highlighting Automist s ability to provide vital time for a rescue to take place from a severe furniture fire 2 0 2 0 FED Heat FED Asphyxia 1 8 1 8 1 6 1 6 1 4...

Page 23: ...tably FED Asphyxia also remains below 0 3 for 15 minutes 2 0 2 0 FED Heat FED Asphyxia 1 8 1 8 1 6 1 6 1 4 1 4 1 2 1 2 1 0 1 0 0 8 0 8 0 6 0 6 0 4 0 4 0 2 0 2 0 0 0 0 0 0 0 0 5 0 5 0 10 0 10 0 15 0 15...

Page 24: ...cent doors left open Automist is located either 5 m or 8 m away from the fire In an unsuppressed scenario with fresh oxygen to feed the fire the heat exposure became lethal after just 2 5 minutes This...

Page 25: ...1 5 1 0 0 5 0 0 Time mins control automist 5m automist 8m 8m x 4m x 2 5m Open Room FED Asphyxia loss of consciousness is expected when the FED of asphyxiant gases FEDAG reaches 1 while death is expect...

Page 26: ...s the difference in temperature at 1 8 m height between the suppressed and unsuppressed kitchen fire Automist significantly reduced the temperature and therefore the damage and chance of the fire spre...

Page 27: ...Automist improved survivability in both room sizes increasing time to incapacitation by a factor of 6 and avoiding fatal conditions In an open room scenario Automist at a distance of 5 m was able to...

Page 28: ...rved Ref Plu6 v 1 LABC For further information please contact Plumis Ltd HMS President 1918 Victoria Embankment London United Kingdom EC4Y 0HJ www plumis co uk fireprotection plumis co uk COMM I S S I...

Reviews: