Plum ecoSTER TOUCH Operation And Assembly Manual Download Page 11

11 

 

4.5

 

Electrical connection with ecoMAX 
controller module 

 
Recommended  supply  voltage  of  the  room 
panel is 

+12VDC

.  

 

Panel 

can 

be 

supplied 

with 

+5÷12V.  However,  it  is  not 
recommended due to voltage losses 
in long connection wires. 

4-wire cable with a max. length of 

30m 

and 

cross-section  of  ≥ 

0.5  mm

2

  is  required  to 

connect to the controller module terminals. 
Terminal  signal  outputs  in  the  rear  side  of 
the panel: 
 

 

 

Be  careful  to  connect  the  poles 
correctly. Incorrect connection may 
cause damage to devices. 

 

Depending  on  the  type  of  ecoMAX 
controller,  room  panel  can  be 
supplied  directly  from  the  boiler 
controller module terminals.  If not, 
use  an  additional  power  adaptor 

+12VDC

I≥0.5A

.  

 

 

Depending  on  the  ecoMAX  boiler 
controller  software  version,  it  can 
cooperate  with  only  one  or  max. 
three ecoSTER TOUCH room panels. 

 
Further  chapters  describe  the  method  of 
connecting  the  ecoSTER  TOUCH  room 
panel/panels to various ecoMAX series boiler 
controller modules. 

 

 

4.5.1

 

Connection with ecoMAX800P1, 
P2, D1, D2 and ecoMAXX800R2, 
T2 

 
All  1,2,3  room  panels  require  application  of 
an  additional  power  adapter 

+12VDC

I≥0.5A

 

 

 

ec

oMAX8

00
 

Summary of Contents for ecoSTER TOUCH

Page 1: ...ROOM PANEL ecoSTER TOUCH FOR ECOMAX BOILER CONTROLLER OPERATION AND ASSEMBLY MANUAL ISSUE 1 0 SOFTWARE VERSION v01 XX XX 10 2015...

Page 2: ......

Page 3: ...rature correction 7 3 12 3 Screen brightness 8 3 12 4 Changing the language 8 3 12 5 PARENTAL LOCK 8 3 12 6 SOFTWARE UPDATE 8 3 12 7 SERVICE SETTINGS 8 3 12 8 Sound 8 3 12 9 Clock 8 3 12 10 Date 8 3 1...

Page 4: ...e inside compartments in a simple way serves the function of an additional control panel for the boiler controller displays all parameters of the boiler controller with a touch panel or remote screen...

Page 5: ...Menu Operation made 3 3 1 Schedule Preset room temperature is determined in accordance with a time schedule Preset night temperature economic or Preset day temperature comfort is set in the following...

Page 6: ...his mode will additionally result in setting a preset temperature of hot utility water on the ecoMAX boiler controller to 8 C symbol is displayed on the screen 3 3 8 Antifreeze Controller works with a...

Page 7: ...on off are optional and available only in case of connecting the ecoSTER TOUCH panel to the controller with compatible software 3 10 Boiler controller remote screen If the boiler controller is equipp...

Page 8: ...l 3 12 8 Sound Activation deactivation of sound in alarms and notifications sent by the boiler controller 3 12 9 Clock Setting the current time Panel has a function of time synchronization with other...

Page 9: ...Selected panel Address at 2 or 3 connected panels is displayed on the main screen as further digits 2 3 Name is displayed also for other panels in the upper bar of the screen on the left 3 12 12 Info...

Page 10: ...ecommendations 1 Panel is intended for wall installation inside compartments 2 Assemble the panel at a height of approx 1 5 m above the floor 3 Avoid highly insolated areas with poor air circulation n...

Page 11: ...orrect connection may cause damage to devices Depending on the type of ecoMAX controller room panel can be supplied directly from the boiler controller module terminals If not use an additional power...

Page 12: ...dule terminal 31 Third panel has to be supplied by the additional power adapter 12V I 0 5A If the boiler controller is equipped with ecoTOUCH control panel colored with a touch panel only one ecoSTER...

Page 13: ...UCH room panels can be supplied directly from the controller module terminal 40 Third panel has to be supplied by the additional power adapter 12V I 0 5A If the boiler controller is equipped with ecoT...

Page 14: ...nels can be supplied directly from the controller module terminal 46 Third panel has to be supplied by the additional power adapter 12V I 0 5A If the boiler controller is equipped with ecoTOUCH contro...

Page 15: ...e supplied directly from the controller module socket G4 Third panel has to be supplied by the additional power adapter 12V I 0 5A If the boiler controller is equipped with ecoTOUCH control panel colo...

Page 16: ...20 office feroterm ro www feroterm ro Tel 0264 241 234 Str Armeneasca Nr 59 Gherla Jud Cluj plum plum pl www plum pl www plumelectronics eu...

Reviews: