OPERATION mode
This parameter switches ON and OFF the boiler return
protection function performed using mixing valve with
electric servo. Note: do not switch on this function if the
valve is not provided with electric servo!
→
Min. return temp
Boiler return temperature below the value at which
electric servo closes mixing valve.
→
Return temp. hyst.
Electric servo returns to normal operation at the return
temperature ≥
min.return temperature + Return temp.
hyst.
→
Valve closing
It is % opening of mixing valve during active return
protection function. Note: the valve closes with accuracy
of +/-1%.
Reserve boiler
The temperature of retort boiler at which reserve boiler
(e.g. gas fired boiler) will be OFF is set using this
parameter. Details - see sec. 11.12
Alarms
Details - see sec. 11.13
Feeder Efficiency
Parameter used to rough calculation of boiler output
(displayed in INFO window) and of fuel level and it has
no effect on control of combustion process [kg/h].
Energy Density
Parameter used to rough calculation of boiler output; it
has no effect on control of combustion process. Its value
for hard coal amounts to approx. 6.5 [kWh/kg]
Tank Capacity
Parameter used to calculate fuel level [kg]. Note:
Change and confirmation of the value using the knob
replaces previously completed fuel level calibration with
calculation of fuel level using
Tank Capacity and Feeder
Efficiency
parameters.
13
SERVIS SETTINGS OF PUMPS
CH pump standstill at HUW
supply
Parameter available upon connection of HUW sensor. Too
long time of HUW container filling at active HUW priority
may lead to excessive cooling down of CH system
because boiler pump (CH pump) is switched off at this
time. Parameter of
CH pump standstill time during HUW
filling
prevents it by periodic CH pump switch-on during
HUW container filling. After that time, CH pump will
switch on for a fixed time set at 30s.
Min. HUW temperature
This parameter is available upon connection of HUW
sensor and prevents the user to set too low preset HUW
temperature.