46
14
Technical data
Supply
230V~, 50Hz
Controller current consumption
0,4 A
9
Maximum rated current
6 (6) A
Fuse type
5x20, T 6.3A, 230V~,
ceramic
Controller protection class
IP20
Ambient temperature
0...45
C
Storage temperature
-10...65
C
Relative humidity
5…85% without water
vapor condensation
CT-10 sensor temperature
measurement range
0...100
C
CT6-P and CT6-W sensor
temperature measurement
range
-40...40
C
Temp. measurement accuracy
±2
C
Connectors
Screw terminals at
supply voltage side -
2.5mm
2
Screw terminals at
control voltage side -
1.5mm
2
Display
480x272 pix
graphical with touch
panel
External dimensions
Module:
340x225x60 mm
Control panel:
148x97x23 mm
Weight
1,6 kg
Standards
PN-EN 60730-2-9
PN-EN 60730-1
Software class
A
Degree of contamination
2
nd
degree acc. to
PN-EN 60730-1
Installation method
Wall-mounted
15
Transportation and storage
conditions
The controller cannot be subjected to direct
influence of atmospheric conditions, i.e. rain
and solar radiation. During transportation the
controller cannot be subjected to vibrations
exceeding normal vibrations generated
during wheel transportation.
9
It is a current consumed only by the controller. Overall
current consumption depends on devices connected to
the controller.
16
Temperature sensors check
Temperature sensors can be checked by
measuring its resistance in a specified
temperature. During the measuring period,
sensor should be disconnected from the
controller. Change the sensor in case of
considerable differences between measured
resistance and values listed in the table
below.
CT-10 (NTC 10K)
Temp.
otoczenia [°C]
Nom.
[Ω]
0
33620
10
20174
20
12535
30
8037
40
5301
50
3588
60
2486
70
1759
80
1270
90
933
100
697
110
529
120
407
CT6-W, CT6-P (Pt1000)
Temp.
otoczenia
[°C]
Min.
[Ω]
Nom.
[Ω]
Max.
[Ω]
0
999,7
1000,0
1000,3
25
1096,9
1097,3
1097,7
50
1193,4
1194,0
1194,6
100
1384,2
1385,0
1385,8
17
Replacement of mains fuse
Mains fuse is located in the Operating Unit. It
protects the regulator and other equipment.
In case of replacement, use 6.3A.
In order to take out the fuse, raise the fuse
holder using flat-blade screwdriver and take
out the fuse.
Modifications register:
Summary of Contents for ecoMAX920P2-I
Page 2: ......
Page 6: ...6...
Page 7: ...CONTROLLER OPERATION MANUAL ecoMAX920P2 I FOR THE USER...
Page 18: ......
Page 19: ...CONTROLLER ASSEMBLY AND SERVICE SETTINGS MANUAL ecoMAX920P2 I FOR THE INSTALLER...
Page 47: ...47...
Page 48: ...ul Wsp lna 19 Ignatki 16 001 Kleosin Poland plum plum pl www plum pl...