The  controller  regulates  temperature  of  the 
HUW 

container, 

providing 

that 

the 

temperature  sensor  is  connected.  When  the 
sensor  is  disconnected  –  the  information 
about it is displayed in the main window. By 
selecting:   
HUW  settings 

    HUW  Pump  mode  the 

user is able to: 

 

deactivate  feeding  the  HUW  container, 
parameter Off

 

setting  HUW  priority,  by  parameter 
Priority – then CH pump is deactivated to 
load the HUW container quicker, 

 

set  simultaneous  operation  of  CH  and 
HUW  pump  with  the  parameter  No 
priority
. 

8.14

 

 HUW preset temperature settings 

Preset  temperature  HUW  is  defined  by 
parameter: 
HUW settings 

 Preset HUW temp. 

8.15

 

Hysteresis of HUW 

Below temperature Preset HUW temp. minus 
HUW  hysteresis  the  HUW  pump  will  activate 
to feed the HUW container. 

 

By  small  hysteresis  value  HUW 
pump will activate faster after HUW 
temperature decrease. 

8.16

 

 SUMMER function start up 

To  activate  SUMMER  function  which  allows 
feeding  the  silo  during  summer,  without 
necessity  to  activate  CH  installation  and 
mixers  periods,  it  is  required  to  set  the 
menu: 
Summer/Winter 

→ 

SUMMER  mode  for 

Summer 

 

Attention:  when  boiler  operates 
without  heating  buffer  and  the 
controller is switched into SUMMER 
mode, 

than 

Standard 

mode 

operation is recommended.  

 

It  is  not  allowed  to  activate 
function summer when HW pump is 
disconnected or damaged. 

Function 

SUMMER 

can 

be 

activated 

automatically,  on  the  basis  of  readings  from 
weather sensor. Use following parameters to 
activate this function: 

Summer/Winter 

→ 

SUMMER  Mode

  → 

Auto 
If  the  automatic  detection  of  summer  mode 
is switched on, user can set the parameters: 
Activ.  temperature  SUMMER,  so  outdoor 
temp. above which the summer mode will be 
switched  on  and  Deactv.  temperature 
SUMMER
 , so outdoor temp. below which the 
SUMMER mode will be switched off.  

8.17

 

 HUW container disinfection 

The controller can automatically, periodically 
make HUW container warm up to 70ºC. It is 
done to remove bacterial flora.  

 

It  is  absolutely  important  to  inform 
all the inmates about activating the 
disinfection  function.  There  is  a 
danger of scalding with hot water. 

Once  a  week  at  night,  in  Monday  at  2  a.m. 
the controller increases temperature of HUW 
container.  After  10minutes  of  keeping  the 
silo  at  70ºC  the  HUW  pump  is  deactivated 
and  the  silo  returns  to  its  normal  operation. 
It  is  not  advisable  to  activate  disinfection 
function  while  the  service  of  HUW  is 
deactivated. 

8.18

 

 Mixer circle settings 

Settings of first mixer circle are in the menu: 
Mixer 1 settings  
Settings  for  other  mixers  are  in  following 
sections  of  the  menu  and  are  identical  in 
each cycle. 
 

 

Mixer  settings 

without 

weather 

sensor 

It  is  required  to  set  manually  desired 
temperature  in  mixer’s  heating  cycle  using 
parameter  Preset  mixer  temp.,  e.g.  50ºC. 
Such  should  be  a  value  to  provide  required 
room temperature. 
After connecting a room thermostat, value of 
decline  in  preset  mixer  temperature  from 
thermostat should be set. (parameters Mixer 
room thermostat
, e.g. 5ºC. This value should 
be 

chosen 

experimentally. 

room 

thermostat  can  be  a  traditional  one  or  a 
room  panel.  After  activating  the  thermostat, 
mixer  preset  temperature  will  be  reduced. 
When  this  value  is  reduced  correctly  then 
room temperature increase will be stopped.  

Summary of Contents for ecoMAX860P3-KL

Page 1: ...EN_DRAFT OLNY APPLIES TO SOFTWARE MODULE A B PANEL v01 XX XX v01 XX XX 09 2019 functions available in the additional module B the ecoSTER TOUCH or ecoSTER200 room panel and ecoNET300 Internet module i...

Page 2: ...lation etc check if the controller is not connected to the mains Installation should be done by a person with appropriate electrical qualifications Improper cables connection could result in the contr...

Page 3: ...OUNTING OF MODULE 24 12 5 IP PROTECTION RATE 25 12 6 CONNECTING ELECTRICAL SYSTEM 25 12 7 ELECTRIC SCHEME 27 12 8 CONNECTION OF TEMPERATURE SENSORS 29 12 9 CONNECTION OF WEATHER TEMPERATURE SENSOR 29...

Page 4: ...er and whether it can cause danger The controller is not an intrinsically safe device which means that in the case of malfunction it can be the source of a spark or high temperature which in the prese...

Page 5: ...e manual We are not responsible for any damages caused by failure to observe these instructions 4 Storage of documentation This assembly and operation manual as well as any other applicable documentat...

Page 6: ......

Page 7: ...USER SETTINGS ecoMAX860P3 KL...

Page 8: ...l level calibration Burner cleaning Lambda sensor calibration HUW settings Preset HUW temp HUW pump mode Off Priority No priority HUW cont hysteresis HUW disinfection Night time decrease Boiler Off Re...

Page 9: ...oiler circuit active return protection increasing the preset temperature to load the buffer 5 signaling blowing operation 6 signaling fuel feeder operation 7 signaling CH pump operation 8 signaling HU...

Page 10: ...the hot user water tank and power heating circuits of mixers 8 5 FIRE UP mode The FIRE UP mode is for automatic firing up of furnace in boiler Total time of firing up proces is dependand on controller...

Page 11: ...uses power levels defined in Standard mode In this mode the parameters Average hysteresis H2 and MIN hysteresis H1 do not have to be set The Fuzzy Logic mode unlike the Standard mode is not faulty in...

Page 12: ...ffer decrease of top buffer temperature below preset value Loading start temperature 8 11 GRATE Some boilers have an additional grate to burn other fuels such as wood waste etc To activate the grid mo...

Page 13: ...automatic detection of summer mode is switched on user can set the parameters Activ temperature SUMMER so outdoor temp above which the summer mode will be switched on and Deactv temperature SUMMER so...

Page 14: ...e it was described in previous point not recommended or automatically constantly correct heating cycle temperature It is not recommended to use both these possibilities at the same time Automatic corr...

Page 15: ...time intervals is indicated by the symbol on the main screen To activate time intervals set the parameter Night time decrease for the given heating circuit to ON The parameter Reduction value set the...

Page 16: ...y settings will not always correspond to actual fuel consumption so to work correctly this method needs level calibration by controller s user No additional fuel sensors are required Calibration Fill...

Page 17: ...feeder or other device may cause danger 8 27 Cooperation with room panel The controller can cooperate with room panels All panels has a built in room thermostat This room panels shows useful informati...

Page 18: ...18...

Page 19: ...19 INSTALLATION AND SERVICE SETTINGS ecoMAX860P3 KL...

Page 20: ...figure use large nominal diameter pipes and four way valve avoid unnecessary angles and reductions maintain a min 2 horizontal pipe slope etc If the sensor 3 is attached to the pipe isolate it with f...

Page 21: ...CH and HUW settings Boiler pump YES Service settings CH and HUW settings Mixer 1 support CH ON Service settings Mixer 1 settings Max mixer 1 temp 70 C Service settings Mixer 1 settings Mixer 1 heatin...

Page 22: ...gs Loading end temp 75 C Service settings Buffer settings Mixer 1 support CH ON Service settings Mixer 1 settings Max mixer 1 temp 70 C Service settings Mixer 1 settings Mixer 1 heating curve 0 8 1 4...

Page 23: ...es connected to the controller During transport the device cannot be exposed to vibrations greater than those typical of normal road transport 12 Controller installation 12 1 Environmental conditions...

Page 24: ...t exceeded the ventilation holes do not always guarantee that the temperature of the panel surroundings will be lowered in such case use other methods 12 4 Mounting of module Working module has to be...

Page 25: ...sary to access the part with the terminals disconnect the mains supply make sure that there is no voltage on terminals and leads and remove the executive module enclosure 12 6 Connecting electrical sy...

Page 26: ...served Controller should be equipped with a set of pins connected to the 230 VAC mains Connect protective wire of power supply cable to ground strip linked with metal boiler housing Connect coupling t...

Page 27: ...P control panel HW HUW temp sensor type CT4 M1 mixer 1 temp sensor type CT4 WS weather temp sensor type CT6 P RS boiler water return temperature sensor type CT4 FS feeder temp sensor type CT4 OS flam...

Page 28: ...ower 230 VAC GR grounding strip FU fuse PM2 PM3 mixer pump SM2 SM3 mixer servomotor CPU controlling A main controller connect exclusively with two cables do not connect with four cables as it may lead...

Page 29: ...contact hot parts of the boiler and heating system Wires of temperature sensors are heat resistant to the temperature not exceeding 100 C 12 9 Connection of weather temperature sensor The controller...

Page 30: ...5 0 1385 8 125 1478 5 1479 4 1480 3 150 1572 0 1573 1 1574 2 CT2S 2 exhaust Temp C Min Nom Max 0 999 7 1000 0 1000 3 25 1096 9 1097 3 1097 7 50 1193 4 1194 0 1194 6 100 1384 2 1385 0 1385 8 125 1478 5...

Page 31: ...elay 12VDC consisting of relay RM 84 2012 35 1012 and base GZT80 RELPOL Standard version of the controller is not equipped with a relay Assembly of relay should be done by a person with proper qualifi...

Page 32: ...r 2 external alarm annunciator 3 relay 12 17 Connectino of mixer servo During assembly works for mixer servomotor pay attention not to overheat the boiler This may happen when there is a limited flow...

Page 33: ...properly connected 12 18 Connection of STB temperature limiter In order to prevent the boiler from overheating due to the controller malfunction an STB safety temperature limiter or any other appropr...

Page 34: ...g time bunrnig off Cleaning airflow Cleaning exh fan Cleaning time Cleaning pause Supervision Supervision time Boiler output Cycle time Blow in output Exh fan output Grate Fuel detection time Flush ti...

Page 35: ...er temp Max mixer temp Proportional range Integration time constant Valve opening time Pump off by therm Mixer input dead zone Output H OFF Cleaning Alarm Reserve boiler Shunt pump Additional feeder n...

Page 36: ...to calibrate fuel level The controller process this data if calibration process of fuel level was not done After successful calibration of fuel level the controller does not process this value Feeder...

Page 37: ...ctivates room thermostat for boiler ecoSTER T1 option available after connecting room panel boiler operation is dependent on room thermostat No1 in ecoSTER ecoSTER T2 option available after connecting...

Page 38: ...sensor Parameter determines to what maximum temperature HUW container will be heated during cooling the boiler in alarm situations It is a very important parameter because setting too high value of i...

Page 39: ...he movement of the mixer actuator Increasing this value results in the mixer reaching the set temperature faster Setting this parameter to excessive values causes deregulation of the temperature and u...

Page 40: ...ing power to the controller Checking the temperature sensor is described in point 12 11 15 4 Feeder temp sensor damage Alarm appears when feeder sensor is damaged or by exceeding measuring scope of th...

Page 41: ...was before stoppage 16 2 Antifreezing protection When temperature of the boiler decreases below 5 C CH pump will be activated enforcing circulation of boiler water It will delay the process of freezi...

Page 42: ...umes It is not recommended to change these parameters if regulation time and stability of keeping preset amount of air on required level Periodical calibration of Lambda sensor readings can be necessa...

Page 43: ...miter STB is connected to terminals 1 2 then check if the circuit is not cut off due to boiler overheating Check if feeder engine is not broken or damaged In case when engine work can be heard and fue...

Page 44: ...44...

Page 45: ...45...

Page 46: ...46...

Page 47: ...47...

Page 48: ...48 ul Wsp lna 19 Ignatki 16 001 Kleosin Poland plum plum pl www pum pl...

Reviews: