3.2. NOTES ON THE INSTALLATION
•
Choosing the right place for the humidifier:
•
Vibration-free.
•
Water-protected.
•
Free from temperature fluctuations.
•
Near the humidifying line.
•
As close as possible to the room ventilation unit.
•
Water and wastewater connection available.
•
Before installing the humidifier, take the distances to
ceiling, ducts and wall into account in order to provide
for any additional material if necessary.
•
The humidifier must be freely accessible for all mainte-
nance work.
•
The humidifier and the humidifying line must be fixed to
a bearing wall or ceiling respectively.
When fixing the humidifier to plasterboard, appropriate
fixing material must be used.
•
The humidifying line must be installed horizontally.
•
Connect the humidifier using the shortest possible
steam hose (1.5 m) and few bows to the humidifying line.
Shorten steam hose if necessary. A 5-meter steam hose
is available as an option.
•
Protect the steam hose against external influences such
as bending and deformation.
•
Avoid condensate pockets in the steam hose.
•
Install an aquastop (not included in delivery) as safety
device.
•
If no fine filter is installed at the water meter, Pluggit
recommends that you install one before installing the
humidifier.
•
Install a funnel or siphon for the discharge of conden-
sate and blowdown water. When the condensate is dis-
charged into a funnel, a minimum slope of 5 % must be
observed.
•
The water pressure in the line for the water supply must
be 1-10 bar. When it is above 10 bar a pressure reducing
valve must be installed and set to 4 bar.