39
Installation and user guide PLATINUM Inverter 7000 R3, 9000 R3, 11000 R3, 14000 R3, 16000 R3
Errors and troubleshooting
8.2 Event list
The Event list in the service menu (see Page 33) displays the last 100 events
detected.
Structure of the event list
1
2
3
4
(1) Sequential numbers
(2) Date
(3) Time
(4) Error code
▪
The complete event list can be downloaded from our website www.
diehl.com/photovoltaics.
▪
When making contact with the PLATINUM service, have the serial
number and event code to hand.
▪
To exit the event list, press the
ESC
button.
No.
Meaning
Measure
Serious errors
900
AC voltage too high
▪
Isolate inverter from network
▪
Check AC connection
910
DC voltage too high
▪
Isolate inverter from network
▪
Isolate inverter from DC connection
▪
Check inverter for damage
▪
Check the module connections
920
DC connection has incorrect
polarity
▪
Set DC isolator to 0
▪
Check DC connection
930
Isolation error between
PV+ and earth / PV– and earth
▪
Check isolation of PV modules
▪
Check isolation of PV cables