Installation and user guide PLATINUM Inverter 7000 R3, 9000 R3, 11000 R3, 14000 R3, 16000 R3
Installation
L1
L2
L3
PE
N
5. Connect the AC voltage connection
line in the inverter. To do so, insert the
prepared wires in the terminal board.
Terminal Assignment
L1 black
phase 1
L2 black
phase 2
L3 black
phase 3
N
blue
neutral wire
PE yellow
protective conductor
3.4.3 Connect DC voltage
DANGER
Risk of death due to high DC voltage! As soon as the sun shines, voltage
is applied to the PV modules.
f
Before connecting the inverter, check whether voltage is applied to
the generator's DC voltage connection.
f
Before connecting the inverter, check whether the polarity of the DC
voltage is correct.
f
If voltage is applied, wear insulating protective clothing and face
protection.
f
Ensure that the cable plug has engaged completely with the socket.
f
Detach the DC voltage cable only if the inverter is not in operation.
f
Make sure that the DC isolator or a central isolation device can be
accessed freely.
f
Do not earth PV modules. The inverter does not have a transformer.