Planet IPM-4220 User Manual Download Page 1

IP-based 4-/8-port Switched 

Power Manager 

  

 

IPM-4220/IPM-8220

 

Summary of Contents for IPM-4220

Page 1: ...IP based 4 8 port Switched Power Manager IPM 4220 IPM 8220 ...

Page 2: ...eral Communication Commission Interference Statement This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to Part 15 of FCC Rules These limits are designed to provide reasonable protection against harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used i...

Page 3: ...gers of electric shock and static electricity when working with electrical equipment All guidelines of this and of the computer manufacture must therefore be allowed at all times to ensure the safe use of the equipment CE Mark Warning This is a Class B product In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures WEEE R...

Page 4: ...22 2 5 Initial Utility Installation 23 Chapter 3 Quick Setup 24 3 1 Network Connection 24 3 2 Setup Wizard 24 Chapter 4 Web based Management 28 4 1 Monitor 28 4 1 1 Infeed 28 4 1 2 Outlet For IPM 4220 30 4 1 3 Outlet For IPM 8220 32 4 1 4 Temperature 35 4 1 5 RH Sensor 37 4 1 6 Daisy Chain 38 4 2 Outlet Power Setup 39 4 2 1 Power 39 4 2 2 Safe Shutdown 40 4 2 3 Schedule 41 4 2 4 Auto Ping 41 4 2 5...

Page 5: ...c Info 58 4 5 2 Outlet Authority 59 4 5 3 Email 59 4 5 4 SMS 60 4 6 Time 62 4 7 Chart 63 4 8 Event 64 4 9 Upgrade 64 Chapter 5 Console Operation 66 5 1 Online Set 66 5 2 Power Control 68 5 3 System Preferences 69 5 3 1 Network Preferences 69 5 3 2 Account Preference 69 5 4 Firewall Preference 70 5 5 RELOAD Preference 71 5 6 Parameter Saving 72 5 7 Logout 73 Appendix A Resetting to Default via Rese...

Page 6: ...roduct Introduction 1 1 Package Contents The package should contain the following 1 x Switched IPM 1 x Quick Installation Guide 1 x Power cord 1 x Quick Rack mounting Kit Installation Guide For IPM 8220 If any of the above items are missing please contact your seller immediately ...

Page 7: ...ces Intelligent Power Management The IPM 4220 8220 offers 4 8 power outlets each of which can be controlled or monitored individually by the console or SNMP manager software or web interfaces They allow users to access configure and manage many networking devices at the same time from remote locations to save valuable time Electric Current Monitored on Display The aggregate current draw per rack P...

Page 8: ...t of time to allow users to finish their work and sign off Overload Protection Securing you against the risk of getting the entire circuit cut off commonly happened with ordinary power distribution units PDUs when there is overloaded power PLANET PDU with a built in circuit breaker and reset switch ensures the stability of power distribution among its equipment Its 16 amp circuit breaker prevents ...

Page 9: ...Power IPM 4220 IPM 8220 9 Energy and Cost Saving You can also check the current energy consumption in your office within the configuration interface of the IPM 4220 8220 It helps you reduce energy consumption thus saving expenses on utilities ...

Page 10: ...ximum Amps Inlet IEC 16A for 1 inlet Maximum Amps for 4 8 Outlets IEC 16A for 4 8 outlets Full Frequency Range 50 60Hz Supports multiple power control methods Wake on LAN System After AC Back Kill the Power Remote Access Remote power control via TCP IP and a built in 10 100Mbps Ethernet port Multi browsers support IE Google Firefox Safari Opera Netscape Management Provides Install Wizard to ease u...

Page 11: ...age supports 1024 bit SSL security encryption transmission Supports Secure Socket Layer V3 and Secure Shell V1 protocols Administrator and multiple users with password protection for double layer security IP Filtering Address specific IP security masks to prevent unauthorized access ...

Page 12: ...button 1 reset button LED 1 IP LED 1 alarm LED 1 system LED 1 reset and warning LED 4 outlet status LEDs 1 alarm LED 1 system LED 1 reset and warning LED 8 outlet status LEDs LCD Panel Displays total current and IP Displays total current max alarm voltage and IP Housing Metal Dimensions W x D x H 332 x 153 x 44 mm 432 x 153 x 44 mm Weight 1 6kg 2 5kg Installation Desktop 1U rack mountable desktop ...

Page 13: ...y Web browser SNMP software Windows based utility Telnet Security IP filter MAC filter Secure 128 bit SSL encryption Standards Conformance Computer Interface IEEE 802 3 10BASE T IEEE 802 3u 10 100BASE TX Regulatory Compliance CE FCC Environments Operating Temperature 0 60 degrees C Operating Humidity 0 90 Operating Altitude 0 4500 meters ...

Page 14: ...Light Slow flashing Normal operating Rapid flashing Normal updating 2 Reset and Warning Indicating Light 3 Temperature Humidity Port for IPM ESB Connection 4 Reset Button 5 RJ45 Ethernet Port 6 USB Connected Port Future Feature 7 COM2 1 2 Com Ports provided to enable terminal control API control and 2 mutual cascading 8 Circuit Breaker Protection 9 Power Inlet 10 Power On Off Switch ...

Page 15: ... total current and IP set alarm current 14 IP Indicating Light Lights remaining lit IP displaying 15 Alarm Indicating Light Lights remaining lit Alarm has occurred Slow flashing There is current overloading 16 Buzzering 17 Power Outlet Indicating Light IPM 4220 Panel Operation The first mode of LCD is total current switching with the Switch Set button to show the regular sequence of total current ...

Page 16: ...etting Press the Switch Set button to increase the alarm current by 0 5A in each press Hold the Switch Set button for 3 seconds until a beep is heard to save the setting Press the Switch Set button until it shows the maximum current Hold the Switch Set button for 3 seconds until a long beep is heard to adjust to a zero point Press the Switch Set button to switch the display of each IP address ...

Page 17: ...Port 6 USB Connected Port Future Feature 7 COM2 1 2 Com Ports provided to enable terminal control API control and 2 mutual cascading 8 Circuit Breaker Protection 9 Power Inlet 10 Power Outlet Note The maximum output current is 16 amps 11 LCD Panel To display total current branch 1 branch 2 voltage and IP 12 Switch Button Provide LCD panel in order to switch the total current power switch control a...

Page 18: ...ays figures and the sign of A AMP it means total current Switch with the Set button to show the following sequence LCD menu shows total current and current values of branch 1 and branch 2 Hold the Set button for 3 seconds until a long beep is heard to enter alarm current setting Enter flash mode LCD will flash after entering setting mode S and W will display at the bottom of LCD Press the Set butt...

Page 19: ... beep is heard to enter power outlet alarm current setting Enter flash mode LCD will flash after entering setting mode S O and W will display at the bottom of LCD Press the Set button to increase the alarm current by 0 5A in each press Hold the Set button for 3 seconds until a beep is heard to save the setting Press the Set button to show maximal power outlet current record Hold the Set button for...

Page 20: ...isplay of each IP address IP can only be set by the web page rather than the LCD panel 2 2 Product Concatenation If the controlled device and server have the function of redundant power then shut down of the device requires power off of both two power supplies Therefore product concatenation is provided to reach the goal of power on off at the same time as two power supplies 1 For concatenation of...

Page 21: ... power off protection allowed by power circuit as per the rated current information indicated on the device with reference to the local state rules safety procedures and disconnection or deviation The unit can only be connected to a grounded power outlet or system Make sure the total current output of all the connected systems is within the rated current indicated on the device The test results of...

Page 22: ...a fire or electric shock 2 4 Hardware Installation The IPM 8220 provides a standard 19 inch rack for the installation of devices Please use the rack installation accessories attached with the product package standard accessory for the IPM 8220 First install the accessories to the device and then the device to the rack Please make sure all the units connected are powered off before the installation...

Page 23: ... a network quickly and with ease Step 1 Please download the IP Search tool from PLANET Download Center Step 2 Please press the Refresh button to find out your IP Metered PDU 1 Before searching the IP please make sure your PC is in the same IP segment as control gateway 2 Do not set double IP addresses on the same LAN card Step 3 Enter the IP address and log in to the homepage of IPM ...

Page 24: ...hed by IP Search Utility Default DHCP Client On Default IP Address 192 168 0 10 if no DHCP existed in the network Default Port 80 Default Login User Name Set itself Default Login Password Set itself Search Tools ip_search 3 2 Setup Wizard When you use the Switched IPM for the first time after it is connected to the Internet browser would pop up Setup Wizard asking you to provide language account p...

Page 25: ... DNS server provided by ISP providers and then you can set up two DNS servers Press Next to continue Step 5 Web Server Https can help protect streaming data transmission over the internal on the higher security level You can select the connection type Https means user cannot connect the camera via Http protocol The Https path will be https IP address If you select Http Https both the Http and Http...

Page 26: ...xt to continue Step 8 Time zone Please fill in the time zone where the device is The system is based on Greenwich Mean Time and thus an accuracy setting to time zone may affect the time record of events and chart Press Next to continue Step 9 Daylight Saving Time Set the Daylight saving time from Sunday to Saturday Press Next to continue Step 10 General Setting You may set up operational overtime ...

Page 27: ...IP based 4 8 port Switched Power Manager Power IPM 4220 IPM 8220 27 ...

Page 28: ...onfigure and control the IP Power Manager remotely 4 1 Monitor After a successful login the web page will display the following operation menu where each part is illustrated below 1 User login information 2 Reset the logout time 3 System logout 4 Function bar 5 Operation block 4 1 1 Infeed Display the current voltage power frequency power factor watts and such information ...

Page 29: ... over the signal light for its detailed information and the menu is displayed as follows Total Display the total current consumption of the device Voltage Display the voltage of the current input power Power Display the consumption power value of the current input power Frequency Display the voltage frequency of current input power Power factor Display the power factor of current input power KWh D...

Page 30: ...et the input power voltage and when the device has no watt hour module this value will be taken as computing power and relevant information 4 1 2 Outlet For IPM 4220 Display PC connected with device statement and switch info power on off can be directly operated on the menu Parameters Description Name If user has no access to this route after signing in the name will be No Access PC When the power...

Page 31: ...catenation is enabled representing the power outlet of this line will be linked with the outlet displayed in the Sync Port of concatenated device All To operate many switched IPM at once please follow these steps Step 1 Mark on the checkbox of switches or All that you want to operate Step 2 Select the action you want ON OFF REBOOT or SHORT ON Step 3 Click Confirm to control the switch you select S...

Page 32: ...rts you expect to manage and press Add to build the group continuously adding is permitted here Press Cancel to return to main tab 4 1 3 Outlet For IPM 8220 Display the current voltage power of power outlet and states of computer and switch power on off can be directly operated on the menu Parameters Description Name If user has no access to this route after signing in then the name will be No Acc...

Page 33: ...tlet Voltage Display the voltage of the power outlet VA Display the consumption power value of the current power outlet PC When the power outlet connects with a computer in order to allow the computer to shut down normally before powering off the computer must be installed and execute a safe shutdown program Please go to PLANET website to download this program After relevant parameters are set saf...

Page 34: ...OT or SHORT ON Step 3 Click Confirm to control the switch you select Setup Press Setup and the following window will appear and users can set the outlet power safe shutdown work schedule auto ping monitoring parameter and copy Please refer to the 4 2 Outlet Power Setup for more understanding Group Management You may Add Delete Modify the group and also assign them with special switch Descriptions ...

Page 35: ...emperature sensor has 6 states Monitor Normal Monitor Alert Monitor Off line the Non monitor Normal Non monitor Alert and Non monitor Off line Monitor Normal Offline Monitor is checked And external temperature is not higher than High Alarm or lower than Low Alarm setting Monitor Alert Offline Monitor is checked And external temperature is higher than High Alarm or lower than Low Alarm setting Moni...

Page 36: ...menu This drop down list offers four states for inquiry All Abnormal Alert and Normal that will be displayed as per the temperature sensor state Setup Name Temperature sensor name High Alarm Set up the values of high temp alarm When temp is higher than you set the alarm will occur Low Alarm Set up the values of low temp alarm When temp is lower than you set the alarm will occur Offline Monitor Che...

Page 37: ... 1 5 RH Sensor Display the information of Offline Monitor Status and Humidity Value of the sensor Parameters Description Name Humidity sensor name Offline Monitor Enabled to start monitoring the device will send alarm data automatically through message or email whenever the humidity sensor name detects any abnormality Status Humidity sensor has 6 states Monitor Normal Monitor Alert Monitor Off lin...

Page 38: ...e mouse over the icons for its detailed information and the menu is displayed as follows RH Refer to the humidity value detected by the current humidity sensor State dropdown menu This drop down list offers four states for inquiry All Abnormal Alert and Normal that will be displayed as per the temperature sensor state Setup Name Humidity sensor name High RH Alarm Set up the values of high RH alarm...

Page 39: ...rt Normal online state Abnormal online state Move the mouse over the icons for its detailed information and the menu is displayed as follows 4 2 Outlet Power Setup Press Setup and the following window will appear users can set the outlet power safe shutdown schedule auto ping monitor Only for IPM 8220 parameter and copy 4 2 1 Power Power setting list is mainly for setting the relevant information ...

Page 40: ...he statuses from the drop down list are 1 ON 2 OFF 3 Last statuses before power was lost 4 2 2 Safe Shutdown This page is for setting the computer device name connected to the power outlet When users want to power off the outlet firstly the computer connected should be shut down and then switch off the power within the preset delay time Parameters Description MAC Please enter the Computer MAC addr...

Page 41: ...lete the schedule click the icon of Delete of the schedule 4 2 4 Auto Ping When the power supply connects with network devices this menu can set the address of the network device detect time interval detection frequency time of reboot and re detection Parameters Description Ping Enable Disable network detection Host Network device address to be detected Ping Interval Time Min Execute the time inte...

Page 42: ...ill be given when the input power current exceeds this alarm value High alarm Current value to be alerted when the power outlet current is too high Low alarm Current value to be alerted when the power outlet current is too low 4 2 6 Peripheral You may set up peripheral at this tab to monitor device and command it with On Off Reboot and Short on set up different conditions with different peripheral...

Page 43: ...s Delete After clicking the icon X it would pop up a confirm window your condition would be deleted To command device please reset the command All of the newly added conditions should match or the device will not do as you command if only one condition is matched device will unmove either 4 2 7 Copy To quickly set up the power outlet parameter of each line after setting the first line the paramete...

Page 44: ...P SysLog Peripheral parameters and other relevant data 4 3 1 Network Setting This menu is mainly for setting the basic data of network Parameters Description Enabled DHCP Use checkbox to enable DHCP It will assign IP address Host Assign the Network IP address for the power switch Subnet Mask Set up the subnet mask info of this equipment Gateway Set up the gateway port of this equipment MAC Display...

Page 45: ...ary DNS Server Configure the IP and DNS server addresses for Network Adapter 2 Parameters Description Enabled Http Allows browser to connect with smart monitor by HTTP Enabled Https Allows browser to connect with smart monitor by HTTP SSL Http Port Provides browser to communicate by HTTP with smart monitor Https Port Provides browser to communicate by HTTP SSL with smart monitor ...

Page 46: ...ge to the preset email accounts Parameters Description Host It is the Host IP address of the e mail sending an alarm e mail when an event occurs Port It is the port of SMTP mail server Default is 25 SMTP TLS secure connection Check to enable e mail encryption From Address It shows the sender s email address Subject It shows the subject of the email Authorization If the mail server needs to identif...

Page 47: ... ISP API System will send out account password time and related info via HTTP to the SMS server of ISP supplier or preset SMS server Parameters Description Host Host IP address of SMS Server Transmission Mode Follow ISP suppliers rules to send out short message via GET or POST protocol to sender s server Device Name The name user wants to reveal Account The account to fill in when sending SMS The ...

Page 48: ...l Parameters Description DEVICENAME The device name will show when sending a message ACCOUNT The account to send the message PASSWORD The password to send the message GSMNUM The number to send the message MSG Message content will show when sending a message IP Device IP will show when sending a message Message Format is related to your message content a content may not stay the same as well ...

Page 49: ...ommunity Name field Default is public SNMP Writing Select the checkbox to enable SNMP Write in Write Community Key in passwords in the Community Name field Default is private Parameters Description SNMP v3 Enable Enable SNMP v3 User Name The name is SNMP v3 command Type There are two types Read Only Read and Write Authorization Type There are two types MD5 and SHA Authorization Password The passwo...

Page 50: ...on SNMPAgent sysLocation The location displayed on SNMPAgent Parameters Description Host The Host IP address of SNMP Trap SNMP Trap Port The phase connects to SNMP Trap Default is 162 Authentication String The authentication string to access SNMP Trap SNMP Test After setting up the above info you can send a test mail to make sure this function is normal 4 3 5 Syslog Remote Power Manager will send ...

Page 51: ...he above info test it to make sure this function is normal 4 3 6 Serial Port UART This menu is mainly for setting the data of COM 1 UART 1 and COM 2 UART 2 Parameters Description Kind Serial Port 1 There are four UART types Disable Console API and UPS Serial Port 2 There are four UART types Disable Daisy Chain API and UPS Disable Cancel UART function Console Computer connects with the device throu...

Page 52: ... window will be displayed press search to search the device after selecting the type Daisy Chain When the device is to be concatenated with the other IPM to link with the power outlet please enable this as for the usage and limitations of Daisy Chain please see 2 2 Product Concatenation Data Rate Set UART Bob rate parameter Data Set UART bit parameter Parity Set UART Parity Check parameter Stop Bi...

Page 53: ...or Fahrenheit Released Temp Range You may set up threshold temp to avoid floating power triggered warning reaction The warning will be dismissed by system when temp is lower than threshold temp Released RH Range You may set up threshold RH to avoid floating power triggered warning reaction The warning will be dismissed by system when the humidity is lower than threshold RH Parameters Description V...

Page 54: ...w Temp Display the RCI type minimum load capacity for the temperature Parameters Description CO2 Emissions You may set up threshold current to avoid floating power triggered warning reaction The warning will be dismissed by system when power current is lower than threshold current Temp Scale You can choose either Celsius or Fahrenheit Released Temp Range You may set up threshold temp to avoid floa...

Page 55: ...sing Locked Time System will log out automatically after timeout you set as no operation is processing as LED panel stay in switch setup status Timeout In alarm setting status LCD panel will show the initial picture of the first phase automatically as no operation is processing 4 3 8 Other This menu is mainly for setting device web page language operation timeout and device date format Parameters ...

Page 56: ...ect Port for MQTT Default is 1883 Parameters Description IP Lock up Period Min The period of such IP has been locked up IP Login Times The number of times that user logs in 4 4 Firewall In this tab you may set up permitted IP or Mac address to access this remote power manager 4 4 1 IP Filter User can set up permitted IP section on this page ...

Page 57: ...filter and press the Save button to store the setting after permitted Mac address is built System will reject people who try to access this remote power manager from other Mac addresses Unmark the square and press the Save button if you expect to cancel this function Allowed MAC Address Enter permitted MAC number Please click ADD to implement this action To delete a specific IP address please clic...

Page 58: ...sic Info To set up account password and user type Parameters Description Account The account to log in to this device Password The password to log in to this device User Level User authority operation can be grouped into General Manage and Administrator as shown below General Only Switch control is permitted but not authorized to change system settings Manage Parameter setting is permitted and con...

Page 59: ... Outlet Authority Outlet Authority tab is mainly to open up outlet authority to other users 4 5 3 Email System would send email when alarm occurs Parameters Description Enable Alert Check to open email alarm system informed by email Send To Enter the mail address of Receiver ...

Page 60: ...heck to enable warning as abnormal condition of switch operation occurs Outlet Check to enable warning as abnormal condition of outlet occurs Temp Use the checkbox to enable the setting When abnormal device temperature occurs system will send a warning message to manager RH Check to enable warning as abnormal condition of humidity occurs Daisy Chain Check to enable warning as abnormal condition of...

Page 61: ...rmal condition of infeed happens system will send a warning message by the way you command Outlet Control Check to enable warning as abnormal condition of switch operation occurs Outlet Check to enable warning as abnormal condition of outlet occurs Temp Use the checkbox to enable the setting When abnormal device temperature occurs system will send a warning message to manager RH Check to enable wa...

Page 62: ...r Manual Setting Synchronization with Time Server Select this time method if you want the system time of this power switch to be the same as Greenwich Mean Time GMT Time Server You can build a new NTP server and then sync with it to be the same date and time If not click Time Server List and choose one from the drop down list Time Zone The time here is following Greenwich Mean Time as most NTP ser...

Page 63: ...nday to Saturday 4 7 Chart This menu is mainly for query infeed device temperature and statistic data Parameters Description Category You may either scroll down to select infeed or device temperature Time Interval You may either scroll down to select 1 min or 30 mins Search See the reference date chart as shown in the table Export Download this data chart ...

Page 64: ...he Refresh button to refresh the screen Download Click the Download button to save the event log information The event log is saved in txt format Delete Click the Delete button to delete the Event logs 4 9 Upgrade This web page is for upgrading the device firmware and the configuration files You can download the latest firmware from the suppliers web page to upgrade the firmware of IPM series ...

Page 65: ...M 8220 65 Parameters Description Upload firmware To update the firmware online click Browse to select the firmware Then click Upgrade to proceed Upload configuration Upgrade from previous saved setting Download configuration Download the current setting to PC ...

Page 66: ...ters through Console When learning console operation users should firstly set the type of device UART1 as Console and set relevant parameters As for the setting of UART1 please refer to 4 3 6 Serial Port UART 5 1 Online Set Use the building HyperTerminal or similar programs to IPM Console related parameter setting of terminal program Comport should be the same with UART1 set values ...

Page 67: ...admin and admin established in device daemon After entering finished operation menu will be displayed to control power switch and set network data Operation method of the menu is as follows 1 Press or W can drift the menu drift upward 2 Press or Z can drift the menu drift downward 3 Press or D can select the data of the next menu 4 Press or A can select the data of the precious menu ...

Page 68: ... press or D to enter power control operation Move Up and Down keys to move the cursor to the power outlet to be operated When the Outlet is ON press Tab for deciding the state of this line Reboot or Off After selection press Enter or E to enter the Query window to decide any operation of this outlet if yes press Y otherwise No ...

Page 69: ...g SYS from the main menu press or D to enter System Preferences setting 5 3 1 Network Preferences After selecting NetWork from the main menu press or D to enter System Preferences setting 5 3 2 Account Preference After selecting Account from the main menu press or D to enter System Preferences setting this ...

Page 70: ...Switched Power Manager Power IPM 4220 IPM 8220 70 setting is modifying the system administrator password 5 4 Firewall Preference After selecting Firewall from the main menu press or D to enter System Preferences setting ...

Page 71: ...PM 8220 71 5 5 RELOAD Preference After selecting RELOAD from the main menu press or D to enter the query windows to reload all data if yes press Y then the device will reload network user and firewall data and the data revised on the terminal before canceling ...

Page 72: ... Manager Power IPM 4220 IPM 8220 72 5 6 Parameter Saving After selecting SAVE from the main menu press or D to enter the query windows to save and reboot the device if yes press Y then the device will save the revised data and reboot ...

Page 73: ... Power Manager Power IPM 4220 IPM 8220 73 5 7 Logout After selecting LOGOUT from the main menu press or D to enter the query windows if press Y then the terminal program will be logged out and the sign in menu will be displayed ...

Page 74: ... then asked fill out the admin account and password as admin add a new account if no admin account Device IP will be automatically acquired through DHCP if there is no DHCP server the device IP should be preset as 192 168 0 10 The acquired IP is displayed on theLCD panel Step 2 Press and hold RESET for more than 10 seconds When LED is on release RESET to clear all the data of the device Default DH...

Page 75: ... Optional Tag Description Required depid Company Code Required username User s Account Required password User s password Required dstaddr Objective gate number Separated by commas for delivery to multiple gate numbers repeated gate number is not accepted during each delivery Required IPMbody Message content using standard URL encoding Transform the above format into message server parameters and t...

Page 76: ...COUNT The account will send the message PASSWORD The password will send the message GSMNUM The number will send the message MSG Message content will show when sending a message IP Device IP will show when sending a message Message Format Explanation depid xxxxxx username ACCOUNT password PASSWORD dstaddr G SMLWNUM IPMbody IP MSG If you fill out the above info in the Message Format the system would...

Page 77: ...essage format Description Company code depid xxxxxx Required User s Account account ACCOUNT Required User s password password PASSWORD Required Cellphone number dstaddr GSMLWNUM Required Device IP Message content IPMbody IP MSG This format is changeable with the content ...