Installation and Commissioning

The pressure tapping points should be prepared in accordance with the indications given for
the sockets. For more details, see e.g. rule VDE/VDI 3512, sheet3.

Suitable for sealing are sealing washers to DIN 16258.

The correct tightening torque is depending on material and shape of the used seal. It should
not exeed 80 Nm.

The mounting position should not be subject to strong vibration and radiation heat.

The mounting position which the transmitter is adjusted for, is indicated on the rating plate.

If the device is installed in a different position, the zero point may be offset. In this case, the
zero point should be readjusted as described here under.

The transmitters are immediatly ready for service after the pressure and electrical connecti-
ons have been made.

Pressure-connection variants

           

Connection G ½ B male

Connection G ¼ female

          Socket DIN 16288

Connector

PUM04, PUM06 Instruction manual  12/2017

page  3

*

*

*

* 101 mm at thin-film technic (from range R79: 0...40 bar)

** 65 mm at thin-film technic (from range R79: 0...40 bar)

**

**

Summary of Contents for PUM04

Page 1: ...truction Manual PUM04 PUM06 Pressure transmitter of stainless steel PKP Prozessmesstechnik GmbH Borsigstra e 24 D 65205 Wiesbaden Nordenstadt Tel 49 0 6122 7055 0 Fax 49 0 6122 7055 50 Email info pkp...

Page 2: ...ed as the sole agents to prevent danger ous conditions occurring in plant or machinery Machinery and plant need to be designed so that faulty conditions do not arise that could pose a safety risk for...

Page 3: ...adiation heat The mounting position which the transmitter is adjusted for is indicated on the rating plate If the device is installed in a different position the zero point may be offset In this case...

Page 4: ...ront flush membrane Connecton for front flush membrane up to measuring range R78 0 25 bar from measuring range R79 0 40 bar and for all ranges of PUM04 Socket Connector PUM04 PUM06 Instruction manual...

Page 5: ...g plate Significance of applied terminal designations supply voltage Ub Ub output signal S S cable shield case earth shield PE Current output Voltage output Output signal 4 20 mA 2 wire system Output...

Page 6: ...d on the site Repairs can only be carried out at the factory Depending on working conditions the pressure transmitters should be checked about once a year to ensure that they are within their specific...

Page 7: ...ly placed between the transmitter and the plug and displays the measured value without additional supply voltage Typical applications The robust design of the PUM04 pressure transmitter offers the use...

Page 8: ...G 3 4 B male thread front flush membrane 3 G 1 4 female thread inside membrane 9 special connection please specify in plain text Measuring range Overrange limit R16 1 0 bar 2 0 bar not at PUM04 S R69...

Page 9: ...hese two techniques covers all DIN measuring ranges from 1 0 bar to 0 2500 bar with constant accuracy Typical applications The robust design of the PUM06 pressure transmitter offers the user the abili...

Page 10: ...R13 0 25 0 bar 0 6 bar R14 0 4 0 bar 2 0 bar R15 0 6 0 bar 2 0 bar R16 1 0 bar 2 0 bar R43 1 1 5 bar 4 bar R45 1 5 bar 13 bar R63 0 0 1 bar 0 6 bar R64 0 0 16 bar 0 6 bar R65 0 0 25 bar 0 6 bar A65 0...

Reviews: