PKP DU06 Series Instruction Manual Download Page 8

Leak flow volume cut off 

Low Flow Cut-Off

If the absolute value of flow is smaller than 

Max Flow Limit

 * 

Low_Flow_Cut_Off

, indic-

ated flow value is 0. Low flow cut off can be adjusted between 0 % and 10 % of 

Max Flow

Limit

.

It is recommended to adjust at least 1-2 %.

Checking power value 

BatCheck

If  

BatCheck

 is activated, a possible power failure is registered. If power comes back an

alert is sounding and the message   <Pwr.Supply fail> is appearing. It is necessary to
press <P> and <arrow up>at the same time to get back to the standard measuring mode. 
This function is recommended to use when totalizator is in operation and shall inform the
user that it could be that due to the power failure totalizator level is not correct because
flow passing the DU06 during power failure was not counted.

Parameter protection -

 

Pin

 

Pin Code is for protecting parameter of the device. Changing them without authority will be
avoided. If the Pin is activated DU06 requires the 4 digit pin if anybody tries to exchange
any parameter. The Pin function is working until it is de-activated

Advice: 

It is recommended to make a note of the code a save location. If the Pin is forgotten user
has to ask
at the manufacturer for a master-pin.

Interface RS-232 or RS-485 – COM Interface

For selection of following interface standards: RS-232 or RS-485.

Following options are available: 
DU06 with RS-232
DU06 with RS-485, Half Duplex
 

Advice:

If you use RS-485 interface , DU06 demands for a valid Bus address. 

Restore of Factory Settings – Restore Factory Settings

Puts back the DU06 into the condition of delivery due to manufacturer (software adjust-
ment). 

DU06 Instruction manual 09/2019

page  8

Summary of Contents for DU06 Series

Page 1: ...Instruction Manual DU06 Ultrasonic flowmeter with display PKP Prozessmesstechnik GmbH Borsigstra e 24 D 65205 Wiesbaden Nordenstadt Tel 49 0 6122 7055 0 Fax 49 0 6122 7055 50 Email info pkp de...

Page 2: ...vent of damage due to improper use non observance of this operating manual use of insufficiently qualified personnel and unauthorized modification of the device Proper Usage The ultrasonic flow meter...

Page 3: ...on versions are available version made of brass or stainless steel flow max 80 l min 1 version made of stainless steel flow max 180 l min 2 version made of stainless steel flow max 1000 l min All vers...

Page 4: ...urrent voltage frequency output 4 pole plug included in delivery Pin 1 4 20mA 0 10V Freq Out Pin 2 GND Pin 3 GND Pin 4 24VDC 15 Relay outputs 6 pol plug included in delivery Pin 1 Relay 2 normally ope...

Page 5: ...parameter Output Parms Menu 1 Relay 1 setting switch point of relay 1 Relay 2 setting switch point of relay 2 If the actual measured flow exceeds falls below one of the adjusted switch points the re...

Page 6: ...erated Freq Out 0 Hz is generated Assignment of analog output signal If the analogue output is used the following assignment must be observed 20 mA corresponds to the Max Flow Limit 4 mA corresponds t...

Page 7: ...c Litre per second l min Litre per minute l h Litre per hour m min Cubic meter per minute m h Cubic meter per hour gal sec Gallons per second gal min Gallons per minute gal h Gallons per hour Percent...

Page 8: ...e flow passing the DU06 during power failure was not counted Parameter protection Pin Pin Code is for protecting parameter of the device Changing them without authority will be avoided If the Pin is a...

Page 9: ...fset This function is used for adaption of the characteristic diagram up to formula Qkorr Qist DynOffset Qist QmaxPhys With Qist measured flow Qkorr corrected flow QmaxPhys max flow in pipe at v 5m se...

Page 10: ...s and protected due to manufacturers code 4 20 mA K value of current output 4 20 mA K Value This function is for special applications and protected due to manufacturers code 0 10 V K value of voltage...

Page 11: ...dium The DU06 indicates no negative flow If there is 0 flow indication while there is flow flow direction has to be changed in the program Functional check It is the responsibility of the operator to...

Page 12: ...time difference is proportional to the flow rate In contrast to other types of ultrasonic flowmeters the sensors are oriented parallel to the flow stream This results in an extremely compact meter wh...

Page 13: ...Dimensions Order Code Order number DU06 Ultrasonic flowmeter and counter with local indication E V R025 0 0 Material version M brass housing sensors st steel with R male connection only E st steel ho...

Reviews: