Turbine flow sensors with analogue output, option Ax:
PN 10
PN 50
Characteristics measurement device
Measuring range
(scaling see type plate)
0...60 l/min*
0...100 l/min*
0...160 l/min*
Signal output from
< 1 l/min
Sensor
Hall effect sensor
Characteristics analogue output
Output signal
4...20 mA
Signal current
~ 26 mA
Load
max. 250 Ω
Residual ripple
0.2 mA
ss
over the entire range
Type
3-wire, galvanic not insulated,
common GND of power supply and output signal
Electrical characteristics
Supply voltage
18...30 V DC
Current consumption
max. 30 mA
Electrical connection
4-pin plug M12x1
Degree of protection
(EN 60529)
IP 54
Process variables
Medium temperature, max.
- Brass
80 °C
80 °C
- Plastic
80 °C (2 bar)
60 °C (5 bar)
30 °C (10 bar)
-/-
- Stainless steel
-/-
80 °C
Medium temperature, min.
0 °C, non-freezing
Ambient temperature
0…80 °C
Nominal diameter
DN 25
Nominal pressure
PN 10
PN 50
Particle size in the medium
< 0.63 mm
Process connection**
G 1¼ male thread
* Not suitable for continuous operation.
** For brass / stainless steel additional fitting required.
DR08-25 Instruction manual 09/2020
page 14