53
These special markers select the type of
sensor connected to analog inputs AI1..AI6
(It is also necessary to set properly the
dipswitches). At starting AI1..AI4 are
automatically set as linear input 0..10V-
10bit, while AI5..AI6 are not enabled.
0
Desabled input
1
Linear input 0÷10V (ris. 10 bit)
2
Linear input 0÷10V (ris. 16 bit)
3
Linear input 0÷1V
4
Linear input 0÷20mV
5
Linear input 0÷20mA
6
Linear input 4÷20mA
7
Input thermocouple type K
8
Input thermocouple type S
9
Input thermocouple type T
10
Input thermocouple type R
11
Input thermocouple type J
12
Input thermocouple type E
13
Not available
14
Input PT100 PT100
15
Input PT100 NI100
16
Compensation input PT100/NI100
(only for PT100/NI100 3wires. Option
valid only for AI2 and AI3, respectively
compensation for AI1 and AI4)
17
Not available
18
Input NTC-10K
β
=3435
19
Input for conversion countings
20
PT1000
21
PT500
22
PTC-1K (KTY 1000 ohm)
23
Light sensor Lux Fi
24
Light sensor Lux Rs
R/W
SM129 1129
Minimum value for analog input AI1 linear
SM130 1130
Minimum value for analog input AI2 linear
SM131 1131
Minimum value for analog input AI3 linear
SM132 1132
Minimum value for analog input AI4 linear
Summary of Contents for TD240 series
Page 1: ...Manuale operatore...
Page 2: ...2...
Page 6: ...6 3 Mechanical dimensions and installation...
Page 24: ...24 7 1 Starter Kit Connection of the terminal to the PC...
Page 27: ...27 7 2 1 Creation of a new project...
Page 89: ...89 11 Notes Updates...
Page 90: ...90...
Page 91: ...91...