10 -
TCT101-2ABC - User manual
5.1.d
Potentiometer connection
10
9
8
Potentiometer 5..10 Kohm
Accuracy 1000 points
Potentiometer:
To modify Set1 or Set2 by external potentiometer follow the
steps below:
1 use potentiometers 5kOhm to 10kohm
2 connect cursor to pin I3; a wrong connection may damage
the potentiometer and lead to lock of the device.
3 accuracy on input is max 1000 points, therefore set the
parameters “Upper limit” and “Lower limit” with a max
difference of 1000 units. (Ex.:
LoS1
to 50,0 and
u PS1
to
150,0 to modify time value related to Set1 between 50 and
150 with steps of one tenth). Greater differences would
make unstable the less significant digit.
4 To calibrate the scale of potentiometer enter the
configuration mode and select:
Hin .3
as Pot
Fin .3
as Set1 or Set2
P. tAr
as Enable
Exit configuration mode and place potentiometer at
minimum level and press
¶
key, then place potentiometer
at max level and press premere
§
key: the device
automatically exit the calibration procedure.
N.B.: a switch-off of the device would interrupt the calibration.