26  Encoder/Counter setup 1

27  Encoder/Counter setup 2

28  Encoder/Counter setup 3

29  Encoder/Counter setup 4

Determines the mode of operation of the encoder input or mono-directional counter.

Disabled (

Default

).

Encoder X2 phase A-B (calculation on the fronts of signal A).

Encoder X4 phase A-B (calculation on the fronts of signal A and B).

Encoder X2 phase A-B-Z (calculation on the fronts of signal A).

Encoder X4 phase A-B-Z (calculation on the fronts of signal A and B).

Counter Up.

Counter Down.

30  Encoder/Counter 1 setup value

32  Encoder/Counter 2 setup value

34  Encoder/Counter 3 setup value

36  Encoder/Counter 4 setup value

Determines the value that will be loaded in the register of the calculations for the encoder or 

counter when the loading command is given. The register value is 32 bit (see paragraph “Encoder 

/ Counter commands”).

-2147483648..+2147483647 [digit], 

Default

: 0.

Command and operation variable table

 

I 0 block digital input status

 

I 1 block digital input status

Reading of these variables lets you recover the status of digital inputs of the device. Each bit of 

these variables corresponds to a precise digital input according to the order below:

I 0 block digital input status

bit 0  Digital input status I0.0

...

bit 7  Digital input status I0.7

...

I 1 block digital input status

bit 0  Digital input status I1.0

...

bit 7  Digital input status I1.7

...

 

Q 0 block digital output value

 

Q 1 block digital output value

Writing these variables lets you set the value of the digital outputs. Each bit of these variables 

corresponds to a precise digital output according to the order below:

Q 0 block digital output value

bit 0  Q0.0 digital output value

...

bit 7  Q0.7 digital output value

Q 1 block digital output value

bit 0  Q1.0 digital output value

...

bit 7  Q1.7 digital output value

Default

: 0.

 

AI.0 analog input value

 

AI.1 analog input value

Reading these variables lets you recover the value assumed by the corresponding normalized 

analog input.

 

AQ.0 analog output value

 

AQ.1 analog output value

Writing these variables lets you set the value of the corresponding analog output. The value 

passed to this variable should range between the minimum and the maximum limit declared for 

the output (parameters from 13..20 and 21..22).

Default

: 0.

Summary of Contents for PLE500-6AD

Page 1: ...PLE500 6AD PL500 expansion module Modulo espansione per PL500 User manual Manuale d uso...

Page 2: ......

Page 3: ...on parameter table 10 8 Command and operation variable table 12 Indice degli argomenti 1 Norme di sicurezza 17 1 1 Organizzazione delle note di sicurezza 17 1 2 Note di sicurezza 17 1 3 Precauzioni pe...

Page 4: ...verheating may lead to risk of fire and can shorten the lifecycle of electronic components 1 1 Organization of safety notices Safety notices in this manual are organized as follows Safetynotice Descri...

Page 5: ...l Controller wiring Using shielded cables and using separate conduits or ducts is recommended Attach a surge suppressor or noise filter to peripheral devices that generate noise in particular motors t...

Page 6: ...ately 130 g 3 2 Hardware characteristics Module power supply 12 24 VDC provided by PLE DIN Bus Digital output power supply 12 24 VDC 15 Max consumption 100 W Analog inputs 2 AI 0 1 Configurable via so...

Page 7: ...I O module connected to the right of the PL500 the number 2 to the following one and so on always moving towards the right side The position of the various modules shall thus reflect the sequence set...

Page 8: ...industrial environments it is a good rule to follow the precautions below Distinguish the power supply line from the power lines Avoid the proximity with contactor units electromagnetic contactors hig...

Page 9: ...the polarity C Sensor output B Sensor mass A Power supply 12 24 VDC Externalsupply Alimentazioneesterna P 0 100mbar Pmax 3bar T 0 70 C OUT 4 20mA IN 9 33V DC PRESSURETRANSMITTER SENSOREDIPRESSIONE C B...

Page 10: ...ng the network node numbering procedure I O It indicates that the corresponding input or output are active high logic level 6 Configuration parameter table 1 AI 0 type sensor 2 AI 1 type sensor Sensor...

Page 11: ...of samples to average in the process calculation 1 30 Default 10 17 AO 0 type output 18 AO 1 type output Selects the operating mode of the analog output 0 4 20 mA Default 1 0 20 mA 2 Proportional tim...

Page 12: ...bles lets you recover the status of digital inputs of the device Each bit of these variables corresponds to a precise digital input according to the order below I 0 block digital input status bit 0 Di...

Page 13: ...he last second by the inputs connected to the encoders counters These variables are updated automatically every second Calculations at the tenth second encoder counter 1 Calculations at the tenth seco...

Page 14: ...onding bit in the variable Mask of status for digital outputs in error Q 0 1 block is set to 1 If the bit in the variable Mask of status for digital outputs in error Q 0 1 block is set to 0 the bit va...

Page 15: ...11 20 AO 1 output lower limit 11 21 AO 0 output upper limit 11 22 AO 1 output upper limit 11 23 AO 0 output cycle time 11 24 AO 1 output cycle time 11 25 Digital input filter 11 26 Encoder Counter se...

Page 16: ...th second encoder counter 1 13 Calculations at the tenth second encoder counter 2 13 Calculations at the tenth second encoder counter 3 13 Calculations at the tenth second encoder counter 4 13 Action...

Page 17: ...le specifiche tecniche dichiarate in questo manuale Non smontare modificare o riparare il prodotto n toccare nessuna delle parti interne Lo strumento va installato e utilizzato esclusivamente nei limi...

Page 18: ...tta Non collegare i terminali non utilizzati Per evitare disturbi induttivi mantenere il cablaggio dello strumento lontano da cavi di potenza con tensioni o corren ti elevate Inoltre non collegare lin...

Page 19: ...g 3 2 Caratteristiche hardware Alimentazione modulo 12 24 VDC fornito da PLE DIN Bus Alimentazione delle uscite digitali 12 24 VDC 15 Consumo max 100 W Ingressi analogici 2 AI 0 1 Configurabili via s...

Page 20: ...odulo I O collegato alla destra del PL500 il numero 2 a quello seguente e cos via procedendo sempre verso destra La posizione dei vari moduli dovr quindi rispecchiare la sequenza impostata nel progett...

Page 21: ...uenti precauzioni Distinguere la linea di alimentazioni da quelle di potenza Evitare la vicinanza di gruppi di teleruttori contattori elettromagnetici motori di grossa potenza e comunque usare apposit...

Page 22: ...pettare le polarit C Uscita sensore B Massa sensore A Alimentazione sensore 12 24 VDC Externalsupply Alimentazioneesterna P 0 100mbar Pmax 3bar T 0 70 C OUT 4 20mA IN 9 33V DC PRESSURETRANSMITTER SENS...

Page 23: ...dei nodi della rete I O Indica che l ingresso o l uscita corrispondente sono attivi livello logico alto 6 Tabella parametri di configurazione 1 Tipo sensore AI 0 2 Tipo sensore AI 1 Configurazione ing...

Page 24: ...nti da mediare nel calcolo del processo 1 30 Default 10 17 Tipo uscita AO 0 18 Tipo uscita AO 1 Seleziona la modalit di funzionamento dell uscita analogica 0 4 20 mA Default 1 0 20 mA 2 Proportional t...

Page 25: ...ispositivo Ciascun bit di queste variabili corrisponde ad un preciso ingresso digitale secondo il seguente ordine Stato ingressi digitali blocco I 0 bit 0 Stato ingresso digitale I0 0 bit 7 Stato ingr...

Page 26: ...ondo dagli ingressi collegatiagliencoder contatori Questevariabilisonoaggiornateautomaticamenteognisecondo Conteggi al decimo secondo encoder contatore 1 Conteggi al decimo secondo encoder contatore 2...

Page 27: ...to uscite digitali in errore blocco Q 0 1 impostato a 1 Se il bit della variabile Maschera stato uscite digitali in errore blocco Q 0 1 impostato a 0 il valore del bit di questa variabile risulta inin...

Page 28: ...28 PLE500 Manuale d uso...

Page 29: ...24 20 Limite inferiore uscita AO 1 24 21 Limite superiore uscita AO 0 24 22 Limite superiore uscita AO 1 24 23 Tempo ciclo uscita AO 0 24 24 Tempo ciclo uscita AO 1 24 25 Filtro ingressi digitali 24 2...

Page 30: ...er contatore 1 26 Conteggi al decimo secondo encoder contatore 2 26 Conteggi al decimo secondo encoder contatore 3 26 Conteggi al decimo secondo encoder contatore 4 26 Azione in caso di errore di comu...

Page 31: ......

Page 32: ...utilizzare il dispositivo leggere con attenzione le informazioni di sicurezza e settaggio contenute in questo manuale 2300 10 272 RevC 020719 PIXSYS s r l www pixsys net sales pixsys net support pixsy...

Reviews: