DRR450 - User manual
9
ma.p.b.
Maximum Proportional Band
Selects the max. proportional band value selectable by the
automatic tuning.
Word modbus 2009
0…3000 tenths of degree.>
Default
: 500.
Es. 500 = 50.0°C/°F
10
mn.i.t.
Minimum Integral Time
Selects the min. integral time value selectable by the
automatic tuning.
Word modbus 2010
0…9999 seconds.>
Default
: 100.
Es. 100 = 10.0 seconds
11
p.b.
Proportional Band
Process inertia in units (Ex: if temperature in °C)
Word modbus 2011
0…3000 tenths of second. >
Default
0.
0 = ON/OFF if also
t.i.
is equal to 0.
Es. 100 = 10.0°C/°F
12
t.i.
Integral Time
Process inertia in seconds
Word modbus 2012
0…9999 tenths of second. >
Default
: 0.
0 = Integral action disabled. Es. 400 = 40.0 seconds
13
t.d.
Derivative Time
Normally ¼ of integral time
Word modbus 2013
0…9999 tenths of second. >
Default
: 0.
0 = Derivative action disabled.
Es. 100 = 10.0 seconds