20
DRR450 - User manual
8
Table of configuration parameters
1
sen.1
Sensor 1
Analogue input configuration/sensor selection (AI1)
Word modbus 2001
0
Tc-K 0…1000°C
1
Tc-J 0…740°C >
Default
2
Tc-T 0…400°C
3
Tc-E 0…540°C
2
o.ca.1
Offset Calibration AI1
Value added/subtracted to visualized process value (nor-
mally used to correct ambient temperature value)
Word modbus 2002
-999…+999
tenths of degree. >
Default
: 0.
Es. 10 = 1.0°C/°F
3
G.ca.1
Gain Calibration AI1
% value multiplied with displayed number to calibrate
process value.
Word modbus 2003
-999%…+999 %
in tenths. >
Default
: 0.
Es.10=1.0%
4
c. Hy.
Command Hysteresis
Hysteresis in ON/OFF or dead band in P.I.D.
Word modbus 2004
-999…+999
tenths of degree. >
Default
: 0.
Es. 10 = 1.0°C/°F