User manual - CNV580 - 17
4.c
Input AI1 4...20 mA
3
+V
AI1
5
mA
For linear signals
• Rispect polarity
• When using shielded cable, only one shield end
must be grounded.
• Pin AI1: 4...20 mA signal input
4.d
Pin +V
3
+V
Output for sensor supply (Max. 70mA).
If device supply is DC, +V = supply voltage.
If device supply is AC, +V = supply voltage x 1,41 V
DC , hence rectified supply output. With supply 24 V
AC, +V will be approx. 34 V DC.