20 - ATR902 - User manual
10 Table of confi guration parameters
10.1 1st level parameters
1
Sen.
Sensor
Select type of sensor.
tc. k
Thermocouple type K. Range: -260..1360°C >
Default
tc. S
Thermocouple type S. Range: -40…1760°C
tc. r
Thermocouple type R. Range: -40…1760°C
tc. J
Thermocouple type J. Range: -200…1200°C
tc. t
Thermocouple type T. Range: -260…400°C
tc. E
Thermocouple type E. Range: -260…1000°C
tc. n
Thermocouple type N. Range: -260…1280°C
2
o.caL.
Offset Calibration
Number added to visualized process (normally it corrects ambient
temperature value).
-99.9…+99.9 tenths of degree.
Default
: 0.0.
3
G.caL.
Gain Calibration
Number multiplied with process value to calibrate working point.
-99.9%…+99.9%.
Default
: 0.0.
4
up.L.s.
Upper Limit Setpoint
Setpoint upper limit.
0…+3200 degrees.
Default
: 1250.
5
dEGr.
Degree
Select type of degree.
Centigrade. >
Default
.
Fahrenheit.
6
Tune
Tune
Select autotunig type.
Dis.
Disabled. >
Default
.
Auto.
Automatic. Controller checks constantly the process value and
modifies P.I.D. values (if necessary).
Man.
Manual. Started by keys.
7
s.d.tu.
Setpoint Deviation Tune
Selects deviation from command setpoint as threshold used by manual
tuning to calculate P.I.D. parameters.
0.0…500.0 tenths of degree. >
Default
: 5.0.