Analogue input configuration.
For a correct functioning of the device, use sensors
insulated from the ground. Otherwise, use a single
transformer isolated for each instrument.
tck
|
tc k
Tc-K
-260 °C .. 1360 °C (
default
)
3
tc.s
|
tc. s
Tc-S
-40 °C .. 1760 °C
3
tc. r
|
tc. r
Tc-R
-40 °C .. 1760 °C
3
tc. j
|
tc. j
Tc-J
-200 °C .. 1760 °C
3
pt
|
pt
PT100
-200 °C .. 600 °C
pt1
|
pt 1
PT100
-200 °C .. 140 °C (restricted range)
ni
|
ni
Ni100
-60 °C .. 180 °C
n tc
|
n tc
NTC 10KΩ -40 °C .. 125 °C
ptc
|
ptc
PTC 1KΩ -50 °C .. 150 °C
pts
|
pts
PT500
-100 °C .. 600 °C
p1k
|
pk1k
PT1000
-100 °C .. 600 °C
0.10
|
0.10
0..10V
0.20
|
0.20
0..20mA
4.20
|
4.20
4..20mA
po1
|
po t1
Potent. ≤ 6KΩ F.S.
po2
|
po t2
Potent. ≤ 150KΩ F.S.
03
d. p.
Decimal point
Selects number of displayed decimal points.
0
|
0
No decimal (
default
)
0.0
|
0.0
1 decimal
0.00
|
0.00
2 decimals
- |
0.000
3 decimals (only ATR141)
04
Lo.s
Lower Limit Setpoint
-199 .. 999 | -999 .. 9999
Value expressed in degrees.tenths for temperature sensors
or in digits
4
for linear sensors and potentiometers (
default
0.0).
3
On ATR121 version the upper limit is 999.