Pittway NOTIFIER NET MET-1 Manual Download Page 2

WARNING:

 This equipment generates, uses, and can radiate radio frequency

energy and if not installed and used in accordance with the instruction manual, may

cause interference to radio communications. It has been tested and found to comply

with the limits for class A computing device pursuant to Subpart B of Part 15 of FCC

Rules, which is designed to provide reasonable protection against such interference

when operated in a commercial environment. Operation of this equipment in a

residential area is likely to cause interference, in which case the user will be required

to correct the interference at his own expense.

Installation Precautions 

 

-   Adherence to the following will aid in problem-free installation with long-term reliability:

WARNING 

Several different sources of power can be connected to the fire alarm

control panel.

  Disconnect all sources of power before servicing.  Control unit and

associated equipment may be damaged by removing and/or inserting cards,

modules, or interconnecting cables while the unit is energized.  Do not attempt to

install, service, or operate this unit until this manual is read and understood.

CAUTION - 

System Reacceptance Test after Software Changes:

     To ensure

proper system operation, this product must be tested in accordance with NFPA 72-

1993 Chapter 7 after any programming operation or change in site-specific software.

Reacceptance testing is required after any change, addition or deletion of system

components, or after any modification, repair or adjustment to system hardware or

wiring.

All components, circuits, system operations, or software functions known to be

affected by a change must be 100% tested.  In addition, to ensure that other

operations are not inadvertently affected, at least 10% of initiating devices that are

not directly affected by the change, up to a maximum of 50 devices, must also be

tested and proper system operation verified.

This system  

meets NFPA requirements for operation at 0-49

O

 C/32-120

O

 F

and at a relative humidity of 85% RH (non-condensing) at 30

C/86

O

 F.

However, the useful life of the system's standby batteries and the electronic

components may be adversely affected by extreme temperature ranges and

humidity.  Therefore, it is recommended that this system and its peripherals be

installed in an environment with a nominal room temperature of 15-27

O

 C/60-80

O

F.

Verify that wire sizes are adequate

 for all initiating and indicating device loops.

Most devices cannot tolerate more than a 10% I.R. drop from the specified device

voltage.

Like all solid state electronic devices,

 this system may operate erratically or can

be damaged when subjected to lightning induced transients.  Although no system is

completely immune from lightning transients and interferences, proper grounding will

reduce susceptibility.

 Overhead or outside aerial wiring is not recommended, due to

an increased susceptibility to nearby lightning strikes.

  Consult with the Technical

Services Department if any problems are anticipated or encountered.

Disconnect AC power and batteries

 prior to removing or inserting circuit boards.

Failure to do so can damage circuits.

Remove all electronic assemblies

 prior to any drilling, filing, reaming, or punching

of the enclosure. When possible, make all cable entries from the sides or rear.

Before making modifications, verify that they will not interfere with battery,

transformer, and printed circuit board location.

Do not tighten screw terminals

 more than 9 in-lbs.  Over tightening may damage

threads, resulting in reduced terminal contact pressure and difficulty with screw

terminal removal.

This system 

contains static-sensitive components.  Always ground yourself with a

proper wrist strap before handling any circuits so that static charges are removed

from the body.  Use static suppressive packaging to protect electronic assemblies

removed from the unit.

Follow the instructions

 in the installation, operating, and programming manuals.

These instructions must be followed to avoid damage to the control panel and

associated equipment. FACP operation and reliability depend upon proper

installation.

Fire Alarm System Limitations

While installing a fire alarm system may make lower insurance

rates possible, it is not a substitute for fire insurance!

An automatic fire alarm system

 - typically made up of smoke detectors, heat

detectors, manual pull stations, audible warning devices, and a fire alarm control

with remote notification capability can provide early warning of a developing fire.

Such a system, however, does not assure protection against property damage or

loss of life resulting from a fire.

Any fire alarm system

 may fail for a variety of reasons:

Smoke detectors

 may not sense fire where smoke cannot reach the detectors such

as in chimneys, in walls, or roofs, or on the other side of closed doors.  Smoke

detectors also may not sense a fire on another level or floor of a building.  A second

floor detector, for example, may not sense a first floor or basement fire.  Further-

more, all types of smoke detectors - both ionization and photoelectric types, have

sensing limitations.  No type of smoke detector can sense every kind of fire caused

by carelessness and safety hazards like smoking in bed, violent explosions,

escaping gas, improper storage of flammable materials, overloaded electrical

circuits, children playing with matches, or arson.

IMPORTANT! 

 Smoke detectors  

must be installed in the same room as the

control panel and in rooms used by the system for the connection of alarm

transmission wiring, communications, signaling, and/or power.

  If detectors are

not so located, a developing fire may damage the alarm system, crippling its

ability to report a fire.

Audible warning devices

 such as bells  may not alert people if these devices are

located on the other side of closed or partly open doors or are located on another

floor of a building.

A fire alarm system

 will not operate without any electrical power.  If AC power fails,

the system will operate from standby batteries only for a specified time.

Rate-of-Rise heat detectors

 may be subject to reduced sensitivity over time.  For

this reason, the rate-of-rise feature of each detector should be tested at least once

per year by a qualified fire protection specialist.

Equipment used in the system

 may not be technically compatible with the control.

It is essential to use only equipment listed for service with your control panel.

Telephone lines

 needed to transmit alarm signals from a premise to a central

monitoring station may be out of service or temporarily disabled.

The most common cause

 of fire alarm malfunctions, however, is inadequate

maintenance.  All devices and system wiring should be tested and maintained by

professional fire alarm installers following written procedures supplied with each

device.  System inspection and testing should be scheduled monthly or as required

by National and/or local fire codes. Adequate written records of all inspections should

be kept.

FCC Warning

Canadian Requirements

This digital apparatus does not exceed the Class A limits for radiation noise

emissions from digital apparatus set out in the Radio Interference Regulations of the

Canadian Department of Communications.

Le present appareil numerique n'emet pas de bruits radioelectriques depassant les

limites applicables aux appareils numeriques de la classe A prescrites dans le

Reglement sur le brouillage radioelectrique edicte par le ministere des Communica-

tions du Canada.

Technical Publishing

        Document PRECAULG.P65  12/31/96

www.PDF-Zoo.com

Summary of Contents for NOTIFIER NET MET-1

Page 1: ...EDIA EDIA EDIA EDIA EDIA E E E E EV V V V VAL AL AL AL ALU U U U UA A A A ATION TION TION TION TION T T T T TOOL OOL OOL OOL OOL MET MET MET MET MET 1 1 1 1 1 DOCUMENT 50480 08 06 97 REVISION P N50480...

Page 2: ...f with a proper wrist strap before handling any circuits so that static charges are removed from the body Use static suppressive packaging to protect electronic assemblies removed from the unit Follow...

Page 3: ...or MIB W example 13 Figure 3 2 2 Testing For Threshold Levels In The First Position 14 Figure 3 2 3 Testing For Threshold Levels In The Second Position 14 Figure 3 2 4 Testing For Threshold Levels In...

Page 4: ...MET 1 50480 A 04 11 97 4 NOTES www PDF Zoo com...

Page 5: ...NNUNCIATOR CONTROL SYSTEM 2 4 8 5 1 LIQUID CRYSTAL DISPLAY 0 8 D C L 7 3 0 5 1 LAMP DRIVER MODULES M D L 5 8 8 5 1 NETWORK REPORTING TERMINAL T R N 0 9 0 5 1 VOICE ALARM MULTIPLEX 9 8 8 5 1 INTELLIGEN...

Page 6: ...MET 1 50480 A 04 11 97 6 NOTES www PDF Zoo com...

Page 7: ...r internal to the MET 1 which determines if the data port is terminated with a 120 Ohm resistor The data ports must be terminated for point to point operation and may or may not need to be unterminate...

Page 8: ...depending on usage The battery will recharge within eight hours using the power adaptor The power adaptor shipped with the MET 1 possesses a safety ground which is electrically bonded to the output r...

Page 9: ...nclosure in doing so be careful to pull the enclosure over the power switch and the SELECT and START push buttons Plug the keyed battery connector into the header with the keyed side up refer to Figur...

Page 10: ...MET 1 50480 A 04 11 97 10 NOTES www PDF Zoo com...

Page 11: ...nated bus mode 1 and the TRANSMIT LED illuminates Press the START button on the transmit MET 1 The transmit MET 1 checks for activity on both ports and then begins transmitting data SEnd will appear i...

Page 12: ...n o l o o t m u i d e M h t i w d e w o l l a e c n a t i c a p a c d n a e c n a d e p m i h t g n e l m u m i x a m r o f e r i w e h t k c e h C T E N E R I F I T O N y l n o s d n e h t o b t a r...

Page 13: ...LED is illuminated If not press the SELECT button until this is so Press the START button on the receive MET 1 The receive MET 1 analyzes the data on port A and gives a result then analyzes the data...

Page 14: ...11 97 14 Figure 3 2 2 Testing For Threshold Levels In The First Position Figure 3 2 3 Testing For Threshold Levels In The Second Position Figure 3 2 4 Testing For Threshold Levels In The Third Positio...

Page 15: ...ress the START button Once the MET 1 detects no other source of data transmissions SEnd will repeatedly flash on the display while the MET 1 outputs test data 3 Disconnect the network connector of eac...

Page 16: ...ating Steps 2 and 3 atTransmitting Location B and Receiving Location A Figure 3 3 2 Bus Mode EvaluationTesting Steps 1 2 and 3 atTransmitting Location A and Receiving Location B Figure 3 3 3 Bus Mode...

Page 17: ...epeating Steps 2 and 3 at Receiving Location B Figure 3 3 5 Bus Mode EvaluationTesting Repeating Steps 2 and 3 at Receiving Location C Figure 3 3 6 Bus Mode EvaluationTesting Repeating Steps 2 3 and 4...

Page 18: ...MET 1 50480 A 04 11 97 18 NOTES www PDF Zoo com...

Page 19: ...itutes the only warranty made by NOTIFIER with respect to its products NOTIFIER does not represent that its products will prevent any loss by fire or otherwise or that its products will in all cases p...

Reviews: