Pittway NOTIFIER NET MET-1 Manual Download Page 15

15

MET-1

50480:A

04/11/97

3.3

B

US

 M

ODE

 T

ESTING

In order to test 

NOTI•FIRE•NET™

NOTI•FIRE•NET™

NOTI•FIRE•NET™

NOTI•FIRE•NET™

NOTI•FIRE•NET™

 bus links, the following steps must be accomplished (refer to

Figures 3.3-1 through 3.3-7

):

1. At each node/repeater, disconnect all wiring not associated with the bus link to be tested.
2. Beginning at one end of the bus, select one node/repeater as the first data source location.  Place a

transmit MET-1 here, or if a network node is present, configure it to transmit by assigning a non-zero

node address (repeaters should not be used as data sources when evaluating bus links).  Set all other node

addresses on the bus to zero.
If a transmit MET-1 is used, press the SELECT button until the SELECTION window displays "1."

(terminated, refer to Section 2.4) and the transmit indicator illuminates.  Press the START button.  Once

the MET-1 detects no other source of data transmissions, "SEnd" will repeatedly flash on the display

while the MET-1 outputs test data.

3. Disconnect the network connector of each node/repeater (one at a time) and plug it into a receive MET-1.

Terminate the MET-1 in the same way as the node/repeater it replaces.  Press the SELECT button until

the SELECTION window displays either "1" (unterminated) or "1." (terminated).  Press the START

button.  Refer to Table 3.1-1 for a detailed description of test messages.  

Only the high data threshold

is acceptable for bus links.

4. When each receiving node/repeater location has been tested using the first transmitting location, discon-

nect the MET-1 transmitter, or set the transmitter node address to zero, and repeat steps two and three

for each node/repeater location.  Hint: use several MET-1 units (one at each bus node/repeater location)

to avoid constantly moving and reconfiguring the test equipment.

Figure 3.3-1 Bus-Mode Evaluation Testing Step 1

www.PDF-Zoo.com

Summary of Contents for NOTIFIER NET MET-1

Page 1: ...EDIA EDIA EDIA EDIA EDIA E E E E EV V V V VAL AL AL AL ALU U U U UA A A A ATION TION TION TION TION T T T T TOOL OOL OOL OOL OOL MET MET MET MET MET 1 1 1 1 1 DOCUMENT 50480 08 06 97 REVISION P N50480...

Page 2: ...f with a proper wrist strap before handling any circuits so that static charges are removed from the body Use static suppressive packaging to protect electronic assemblies removed from the unit Follow...

Page 3: ...or MIB W example 13 Figure 3 2 2 Testing For Threshold Levels In The First Position 14 Figure 3 2 3 Testing For Threshold Levels In The Second Position 14 Figure 3 2 4 Testing For Threshold Levels In...

Page 4: ...MET 1 50480 A 04 11 97 4 NOTES www PDF Zoo com...

Page 5: ...NNUNCIATOR CONTROL SYSTEM 2 4 8 5 1 LIQUID CRYSTAL DISPLAY 0 8 D C L 7 3 0 5 1 LAMP DRIVER MODULES M D L 5 8 8 5 1 NETWORK REPORTING TERMINAL T R N 0 9 0 5 1 VOICE ALARM MULTIPLEX 9 8 8 5 1 INTELLIGEN...

Page 6: ...MET 1 50480 A 04 11 97 6 NOTES www PDF Zoo com...

Page 7: ...r internal to the MET 1 which determines if the data port is terminated with a 120 Ohm resistor The data ports must be terminated for point to point operation and may or may not need to be unterminate...

Page 8: ...depending on usage The battery will recharge within eight hours using the power adaptor The power adaptor shipped with the MET 1 possesses a safety ground which is electrically bonded to the output r...

Page 9: ...nclosure in doing so be careful to pull the enclosure over the power switch and the SELECT and START push buttons Plug the keyed battery connector into the header with the keyed side up refer to Figur...

Page 10: ...MET 1 50480 A 04 11 97 10 NOTES www PDF Zoo com...

Page 11: ...nated bus mode 1 and the TRANSMIT LED illuminates Press the START button on the transmit MET 1 The transmit MET 1 checks for activity on both ports and then begins transmitting data SEnd will appear i...

Page 12: ...n o l o o t m u i d e M h t i w d e w o l l a e c n a t i c a p a c d n a e c n a d e p m i h t g n e l m u m i x a m r o f e r i w e h t k c e h C T E N E R I F I T O N y l n o s d n e h t o b t a r...

Page 13: ...LED is illuminated If not press the SELECT button until this is so Press the START button on the receive MET 1 The receive MET 1 analyzes the data on port A and gives a result then analyzes the data...

Page 14: ...11 97 14 Figure 3 2 2 Testing For Threshold Levels In The First Position Figure 3 2 3 Testing For Threshold Levels In The Second Position Figure 3 2 4 Testing For Threshold Levels In The Third Positio...

Page 15: ...ress the START button Once the MET 1 detects no other source of data transmissions SEnd will repeatedly flash on the display while the MET 1 outputs test data 3 Disconnect the network connector of eac...

Page 16: ...ating Steps 2 and 3 atTransmitting Location B and Receiving Location A Figure 3 3 2 Bus Mode EvaluationTesting Steps 1 2 and 3 atTransmitting Location A and Receiving Location B Figure 3 3 3 Bus Mode...

Page 17: ...epeating Steps 2 and 3 at Receiving Location B Figure 3 3 5 Bus Mode EvaluationTesting Repeating Steps 2 and 3 at Receiving Location C Figure 3 3 6 Bus Mode EvaluationTesting Repeating Steps 2 3 and 4...

Page 18: ...MET 1 50480 A 04 11 97 18 NOTES www PDF Zoo com...

Page 19: ...itutes the only warranty made by NOTIFIER with respect to its products NOTIFIER does not represent that its products will prevent any loss by fire or otherwise or that its products will in all cases p...

Reviews: