Operating 

Instructions  for 

Electrical Heater Units 

 

 

PITSAN 

 

Page 13 / 16 

 

 

PİTSAN MAK. SAN. VE TİC. LTD ŞTİ, 

Esenyurt Yolu Üzeri No: 66 - 68 Bağlar Mevkii,  TR – 34850 Avcılar - İSTANBUL

 

Tel.: 0212/4281885, Fax: 0212/4281661, Email:

[email protected]

http: //www.pitsan.com

 

 

9   MAINTENANCE AND REPAIRS 

 
 

 
Maintenance and repair must be carried out by qualified personnel only. Before 
any maintenance or repair activity heater must be

 DISCONNECTED

 from supply 

circuit 
 

 

  Once a year remove the dust accumulation inside the heater using a vacuum cleaner 

or compressed air. Be careful not to bend the fan blades 

  The electric motors are permanently lubricated and thermally protected . There is no 

need for lubrication. 

  Check periodically motor and fan for smooth running operation 

  Annually check for tightness of visible bolts and nuts 

  Periodically inspect electrical cable insulations, contactors to avoid any short circuits 

  Be sure that all clearances for air intake are kept as installation 

 
 
 

10    POSSIBLE  PROBLEM CAUSES AND SOLUTIONS 

 

 

PROBLEM 

POSSIBLE CAUSE 

SOLUTION 

Fan is not operating 

The fan is not plugged 

Plug in the fan control  wiring 

The fan switch is OFF 

Switch the button ON position 

The motor is defected 

Replace the motor 

Heater is not operating 

Set thermostat temperature 
is higher than room 
temperature 

Set thermostat temperature to 
higher position 

There is abnormal heating 
fan is not working 

Check fan connections 

There is abnormal heating 
air inlet is not sufficient 

Increase the clearance between 
wall/ceiling and the fan 

Not sufficient air is 

blowing 

The clearance is not right 

Check the clearance between 
wall/ceiling and the fan 

Heating output is reduced 

The inlet air temperature is 
low 

Perform mechanical checks to 
see if heating elements are 
working properly. If yes it's OK 

If one or more heating 
elements are burned 

 
Replace the heating elements 

 
 

Summary of Contents for EKI 400x200-10.5-3/3x3.5 kw

Page 1: ...senyurt Yolu zeri No 66 68 Ba lar Mevkii TR 34850 Avc lar STANBUL Tel 0212 4281885 Fax 0212 4281661 Email pitsan pitsan com http www pitsan com INSTALLATION OPERATION MAINTENANCE INSTRUCTIONS ELECTRIC...

Page 2: ...n com CONTENTS 1 GENERAL 3 2 SAFETY 3 2 1 Safety instructions 3 2 2 Correct use 3 3 DESCRIPTION OF THE UNIT 5 4 OPERATING PRINCIPLE 7 5 APPLICATION AND INTENDED USE 7 6 PACKAGING HANDLING STORAGE 8 7...

Page 3: ...ccordance with local electrical codes This equipment requires a ground as precaution against electrical shock Basic precautions should always be followed to reduce the risk of fire electric shock and...

Page 4: ...working properly in threephase models Hot Furface The surface temperature of the heater may rise up to temperatures which will cause inquiry Do not touch the surface while the heater is operating In...

Page 5: ...PITSAN Page 5 16 P TSAN MAK SAN VE T C LTD T Esenyurt Yolu zeri No 66 68 Ba lar Mevkii TR 34850 Avc lar STANBUL Tel 0212 4281885 Fax 0212 4281661 Email pitsan pitsan com http www pitsan com 3 DESCRIPT...

Page 6: ...ater Units PITSAN Page 6 16 P TSAN MAK SAN VE T C LTD T Esenyurt Yolu zeri No 66 68 Ba lar Mevkii TR 34850 Avc lar STANBUL Tel 0212 4281885 Fax 0212 4281661 Email pitsan pitsan com http www pitsan com...

Page 7: ...evices that rotate the fan to move the heated air from the heater to the space When the unit heater wattage is over loaded one or more CONTACTORS are employed to switch the electrical current to the e...

Page 8: ...ents on pallets It is essential that great care is exercised when handling the unit When handling the equipment care should be taken with corners and edges and that the weight distribution within the...

Page 9: ...imum recommended mounting height to bottom of heater 4 5meters Minimum clearance from walls and ceiling are Z 250mm VERTICAL DISCHARGE To ensure proper heating of floor surfaces observe the following...

Page 10: ...ctrical Heater Units PITSAN Page 10 16 P TSAN MAK SAN VE T C LTD T Esenyurt Yolu zeri No 66 68 Ba lar Mevkii TR 34850 Avc lar STANBUL Tel 0212 4281885 Fax 0212 4281661 Email pitsan pitsan com http www...

Page 11: ...ctrical Heater Units PITSAN Page 11 16 P TSAN MAK SAN VE T C LTD T Esenyurt Yolu zeri No 66 68 Ba lar Mevkii TR 34850 Avc lar STANBUL Tel 0212 4281885 Fax 0212 4281661 Email pitsan pitsan com http www...

Page 12: ...gh limits of the motor and or heater 9 Check out and repost any unusual or questionable operating characteristics such as noise vibration etc 10 Set the fan switch and temperature control on desired o...

Page 13: ...lectrical cable insulations contactors to avoid any short circuits Be sure that all clearances for air intake are kept as installation 10 POSSIBLE PROBLEM CAUSES AND SOLUTIONS PROBLEM POSSIBLE CAUSE S...

Page 14: ...ate of normal service when installed and operated in accordance with the instructions provided by the Company and subject to the following conditions 1 Since the paint finish may be damaged in use no...

Page 15: ...212 4281885 Fax 0212 4281661 Email pitsan pitsan com http www pitsan com 12 APPENDIX The customers confirm by their signatures that they have received read and understood the operating and maintenance...

Page 16: ...t to internal manufacturing checks with monitoring of the final assesment by PITSAN MACHINE MODEL LIST ETA EKI series electrical heating units APPLICABLE DIRECTIVES 2006 42 EC MACHINERY SAFETY DIRECTI...

Reviews: