69
2. Pump drainage mode
2.1 Disconnect the plug of water level switch,
remove the cover of water test hole and slowly
infuse about 2000ml water through the water
test hole, be sure that the water will not touch
the motor of drainage pump.
2.2 Power on and let the air conditioner
operate for cooling. Check operation status
of drainage pump, and then connect the
plug of water level switch, check the
operation sound of water pump and
observe whether the water can discharge
through the transparent hard pipe at
drainage outlet. (In light of the length of
drainage pipe, water shall be discharged
about 1 minute delayed)
2.3 Stop the operation of air conditioner, power
off the power supply and put the cover of
water test hole back to the original place.
a. After stopped the air conditioner 3 minutes,
check whether there is anything abnormal.
If drainage pipes have not been distributed
properly, over back-flow water shall cause
the flashing of alarm indicator at
remote-controlled receiving board and
even water shall run over the water
collector.
b. Continuously infusing water until water
level alarmed, check whether the drainage
pump could discharge water at once. If
water level does not decline under warning
water level 3 minutes later, it shall cause
shutdown of unit. When this situation
happens, the normal startup only can be
recovered by turning down power supply
and eliminating accumulated water.
Note:
Drain plug at the main water-containing
plate is used for eliminating accumulated water
in water-containing plate when maintaining air
conditioner fault. During normal operation, the
plug shall be filled in to prevent leakage.
12.5.4 Insulation work of drainage pipe
Refer the introduction to the insulation
engineering parts.
12.6 Vacuum Drying and Leakage
Checking
12.6.1 Purpose of vacuum drying
Eliminating moisture in system to prevent
the phenomena of ice-blockage and copper
oxidation.
Summary of Contents for YN009GMFI22RPD
Page 8: ...5 2 2 Part names of Indoor Outdoor units Ceiling Cassette Unit ...
Page 9: ...6 Ducted Concealed Units ...
Page 10: ...7 Floor Console Units ...
Page 11: ...8 Ceiling Floor Units ...
Page 24: ...21 Console Units 16 Drain pipe 195 Hanging arm Unit mm 700 600 210 ...
Page 28: ...25 Console Unit Ceiling floor Units ...
Page 32: ...29 FB009GMFILCFHD FB012GMFILCFHD UB018GMFILCFHD ...
Page 33: ...30 UB018GMFILCFHD CB036GMFILCFHD CB048GMFILCFHD ...
Page 34: ...31 RB036GMFILCFHD RB048GMFILCFHD ...
Page 35: ...32 UB036GMFILCFHD UB048GMFILCFHD ...
Page 36: ...33 UB036GMFILCFHD UB048GMFILCFHD ...
Page 37: ...34 6 2 Outdoor Unit YN009GMFI22RPD YN012GMFI22RPD ...
Page 38: ...35 YN018GMFI22RPD ...
Page 39: ...36 YN024GMFI22RPD ...
Page 40: ...37 YN036GMFI17RUD ...
Page 41: ...38 YN048GMFI17RUD ...
Page 42: ...39 Outdoor Controller Set of For YN009GMFI22RPD YN012GMFI22RPD For YN018GMFI22RPD ...
Page 44: ...41 RB009GMFILCFHD Code 0 Code 1 Code 2 Code 3 Code 4 ...
Page 45: ...42 RB012GMFILCFHD Code 0 Code 1 Code 2 Code 3 Code 4 ...
Page 46: ...43 RB018GMFILCFHD Code 0 Code 1 Code 2 Code 3 Code 4 ...
Page 47: ...44 RB024GMFILCFHD Code 0 Code 1 Code 2 Code 3 Code 4 ...
Page 48: ...45 RB036GMFILCFHD Code 0 Code 1 Code 2 Code 3 Code 4 ...
Page 49: ...46 RB048GMFILCFHD Code 0 Code 1 Code 2 Code 3 Code 4 ...
Page 58: ...55 12 Field Wiring 36 000 and 48 000 BTU Models ...
Page 100: ...97 P U P V ...
Page 101: ...98 P W P N ...