62
Model
B
C
D
mm
inch
mm
inch
mm
inch
9K
549 21.61 325 12.80 350 13.78
12K
549 21.61 325 12.80 350 13.78
18K
560 22.05 335 13.19 360 14.17
24K
640 25.20 405 15.94 448 17.64
36K
640 25.20 405 15.94 448 17.64
48K
634 24.96 404 15.91 448 17.64
14.3.3 Install the Unit
Since the gravity center of the unit is not at its
physical center, so please be careful when
lifting it with a sling.
Never hold the inlet of the outdoor unit to
prevent it from deforming.
Do not touch the fan with hands or other
objects.
Do not lean it more than 45, and do not lay it
sidelong.
Make concrete foundation according to the
specifications of the outdoor units.
Fasten the feet of this unit with bolts firmly to
prevent it from collapsing in case of earthquake
or strong wind.
12.4 Refrigerant pipe installation
12.4.1 Maximum pipe length and height
drop
Considering the allowable pipe length and
height drop to decide the installation position.
Make sure the distance and height drop
between indoor and outdoor unit not exceeded
the date in the following table.
Model
Max. Length
Max. Elevation
m
Ft.
m
Ft.
9,000Btu/h
25
82.2
10
32.9
12,000Btu/h
25
82.2
10
32.9
18,000Btu/h
30
98.7
20
65.8
24,000Btu/h
50
164.5
25
82.2
36,000Btu/h
65
213.8
30
98.7
48,000Btu/h
65
213.8
30
98.7
12.4.2 The procedure of connecting pipes
1. Choose the pipe size according to the
specification table.
2. Confirm the cross way of the pipes.
3. Measure the necessary pipe length.
4. Cut the selected pipe with pipe cutter
Make the section flat and smooth.
90
Lean
Crude
Burr
o
5. Insulate the copper pipe
Before test operation, the joint parts should
not be heat insulated.
6. Flare the pipe
Insert a flare nut into the pipe before flaring
the pipe
According to the following table to flare the
pipe
Pipe
diameter
Flare
dimension A
(mm)
Flare shape
Min
Max
1/4"
(6.35)
8.3
8.7
A
45¡ ã
90
°
4
-+
3/8"
(9.52)
12.0
12.4
Summary of Contents for YN009GMFI22RPD
Page 8: ...5 2 2 Part names of Indoor Outdoor units Ceiling Cassette Unit ...
Page 9: ...6 Ducted Concealed Units ...
Page 10: ...7 Floor Console Units ...
Page 11: ...8 Ceiling Floor Units ...
Page 24: ...21 Console Units 16 Drain pipe 195 Hanging arm Unit mm 700 600 210 ...
Page 28: ...25 Console Unit Ceiling floor Units ...
Page 32: ...29 FB009GMFILCFHD FB012GMFILCFHD UB018GMFILCFHD ...
Page 33: ...30 UB018GMFILCFHD CB036GMFILCFHD CB048GMFILCFHD ...
Page 34: ...31 RB036GMFILCFHD RB048GMFILCFHD ...
Page 35: ...32 UB036GMFILCFHD UB048GMFILCFHD ...
Page 36: ...33 UB036GMFILCFHD UB048GMFILCFHD ...
Page 37: ...34 6 2 Outdoor Unit YN009GMFI22RPD YN012GMFI22RPD ...
Page 38: ...35 YN018GMFI22RPD ...
Page 39: ...36 YN024GMFI22RPD ...
Page 40: ...37 YN036GMFI17RUD ...
Page 41: ...38 YN048GMFI17RUD ...
Page 42: ...39 Outdoor Controller Set of For YN009GMFI22RPD YN012GMFI22RPD For YN018GMFI22RPD ...
Page 44: ...41 RB009GMFILCFHD Code 0 Code 1 Code 2 Code 3 Code 4 ...
Page 45: ...42 RB012GMFILCFHD Code 0 Code 1 Code 2 Code 3 Code 4 ...
Page 46: ...43 RB018GMFILCFHD Code 0 Code 1 Code 2 Code 3 Code 4 ...
Page 47: ...44 RB024GMFILCFHD Code 0 Code 1 Code 2 Code 3 Code 4 ...
Page 48: ...45 RB036GMFILCFHD Code 0 Code 1 Code 2 Code 3 Code 4 ...
Page 49: ...46 RB048GMFILCFHD Code 0 Code 1 Code 2 Code 3 Code 4 ...
Page 58: ...55 12 Field Wiring 36 000 and 48 000 BTU Models ...
Page 100: ...97 P U P V ...
Page 101: ...98 P W P N ...