16.3.9 High temperature protection of compressor top diagnosis and solution (P2)
Error Code
P2
Malfunction
decision
conditions
If the sampling voltage is not 5V, the LED will display the failure.
Supposed causes
●
Power supply problems.
●
System leakage or block
●
PCB faulty
Trouble shooting:
Check the air flow system
of indoor and outdoor units
Clear up the air inlet and outlet or the heat
exchanger of indoor and outdoor units.
Yes
No
Yes
Yes
Power off, then restart the unit
10 minutes later
Check if the temperature
of compressor
No
Check refrigerant system
Yes
Check the overload
protector
Correct the connection.
No
Measure the resistance
between the two ports of
the OLP. Is it zero?
Yes
Replace the OLP.
No
Replace the outdoor control PCB.
Yes
Summary of Contents for YN009GMFI22RPD
Page 8: ...5 2 2 Part names of Indoor Outdoor units Ceiling Cassette Unit ...
Page 9: ...6 Ducted Concealed Units ...
Page 10: ...7 Floor Console Units ...
Page 11: ...8 Ceiling Floor Units ...
Page 24: ...21 Console Units 16 Drain pipe 195 Hanging arm Unit mm 700 600 210 ...
Page 28: ...25 Console Unit Ceiling floor Units ...
Page 32: ...29 FB009GMFILCFHD FB012GMFILCFHD UB018GMFILCFHD ...
Page 33: ...30 UB018GMFILCFHD CB036GMFILCFHD CB048GMFILCFHD ...
Page 34: ...31 RB036GMFILCFHD RB048GMFILCFHD ...
Page 35: ...32 UB036GMFILCFHD UB048GMFILCFHD ...
Page 36: ...33 UB036GMFILCFHD UB048GMFILCFHD ...
Page 37: ...34 6 2 Outdoor Unit YN009GMFI22RPD YN012GMFI22RPD ...
Page 38: ...35 YN018GMFI22RPD ...
Page 39: ...36 YN024GMFI22RPD ...
Page 40: ...37 YN036GMFI17RUD ...
Page 41: ...38 YN048GMFI17RUD ...
Page 42: ...39 Outdoor Controller Set of For YN009GMFI22RPD YN012GMFI22RPD For YN018GMFI22RPD ...
Page 44: ...41 RB009GMFILCFHD Code 0 Code 1 Code 2 Code 3 Code 4 ...
Page 45: ...42 RB012GMFILCFHD Code 0 Code 1 Code 2 Code 3 Code 4 ...
Page 46: ...43 RB018GMFILCFHD Code 0 Code 1 Code 2 Code 3 Code 4 ...
Page 47: ...44 RB024GMFILCFHD Code 0 Code 1 Code 2 Code 3 Code 4 ...
Page 48: ...45 RB036GMFILCFHD Code 0 Code 1 Code 2 Code 3 Code 4 ...
Page 49: ...46 RB048GMFILCFHD Code 0 Code 1 Code 2 Code 3 Code 4 ...
Page 58: ...55 12 Field Wiring 36 000 and 48 000 BTU Models ...
Page 100: ...97 P U P V ...
Page 101: ...98 P W P N ...