background image

6

installation manual

NOTE

CAUTION

>30cm

>200cm

>30cm

>60cm

(Wall or Obstacle)

Air Outlet

Air Inlet

M

P

Air Inlet

Maintain Channel

N

Side Air Outlet Outdoor Unit

Fig.6-4

6.2   Moving and Installation

All pictures in this manual are for explanatory purposes 
only. They may slightly differ from the air conditioner that 
you purchased (dependent on model). The actual shape 
shall prevail.

NOTE

All pictures in this manual are for explanatory purposes 
only. They may slightly differ from the air conditioner that 
you purchased (dependent on model). The actual shape 
shall prevail.

Since  the  center  of  gravity  of  the  unit  is  not  at  its  actual 
physical center, please be careful when lifting it using a sling.

Never  directly  hold  onto  the  inlet  of  the  outdoor  unit,  to 
prevent it from deforming.

Do not touch the fan with your hands or any other objects.

Do not lean the unit more than 45, and do not lay it sideways.

Create  a  concrete  foundation  accoding  to  the  specifications 
of the outdoor units. 

(Refer to Fig. 6-5)

Firmly fasten the feet of this unit with bolts, to prevent it from 
collapsing  in  case  of  earthquake  or  strong  winds. 

(Refer to 

Fig. 6-5)

 

7.    INSTALL THE CONNECTING PIPE

Check  to  ensure  that  the  height  drop  between  the  indoor  unit 
and outdoor unit, the length of refrigerant pipe, and the number 
of bends meet the following requirements:

All  field  piping  must  be  performed  by  a  licensed 
refrigeration  technician,  and  must  comply  with  the 
relevant local and national codes.
Do not let air, dust, or other impurities fall into the pipe 
system  during  the  process  of  installation.  Connecting 
pipes  should  not  be  installed  until  the  indoor  and 
outdoor units have already been fixed into place.
Keep  the  connecting  pipes  dry,  and  do  not  let  moisture 
inside during installation.
Heat  insulation  work  should  be  installed  properly  and 
fully,  on  both  sides  of  the  gas  piping  and  the  liquid 
piping. Otherwise, there can be a risk of water leakage.

   Pipe Connection Procedure

7.1

Table 7-1

Capacity (Btu/Hr)

Max Height Drop

Length of Refrigerant Pipe

Number of Bends

12000

5m

Less than 10m

Less than 5

16000~18000

10m

Less than 20m

Less than 8

Fig.6-5

>60cm

Fix with Bolts

CAUTION

Drill a hole into the wall (suitable for just the size of the wall 
conduit), and set the fittings (such as the wall conduit and its 
cover) onto the wall.

Bind the connecting pipe and the cables together tightly with 
the use of binding tape.
Pass the bound connecting pipe through the wall conduit from 
outside.  Be  careful  with  the  pipe  movement,  to  avoid  doing 
damage to the tubing.
 
Connect  the  pipes.  Refer  to  "How  to  Connect  the  Pipes"  for 
further details.

Expel all air with a vacuum pump. Refer to "How to Expel the 
Air with a Vacuum Pump" for details.

Open the stop valves of the outdoor unit, to set the refrigerant 
pipe connecting the indoor unit with the outdoor unit in fluent 
flow.

Check  for  leakage.  Check  all  joints  with  a  leak  detector  or 
soapy water.

Cover  the  joints  of  the  connecting  pipe  with  soundproof/ 
insulating sheaths (fittings), and bind it well with the tapes to 
prevent leakage.

1

2

3

5

6

7

4

Be  sure  that  the  insulating  materials  cover  all  of  the 
exposed parts of the flare pipe joints and refrigerant pipes 
on  the  liquid-side  and  the  gas-side.  Ensure  that  there  is 
no gap between these layers.
Improper insulation may cause water condensation.

Summary of Contents for FAB Series

Page 1: ...his manual carefully before installing or operating your new air conditioning system Make sure to save this manual for future reference Installation Manual FAB FYB Series FAB Cooling Only Version FYB Cooling and Heating Version Inverter and Inverter Models 9 000 BTU h through 12 000 BTU h ...

Page 2: ...If used as a part of a MULTI Split System please refer to the Installation Operation manuals packed with the multi split outdoor unit ...

Page 3: ...nsufficient or the installation is improperly done the set can possibly drop and cause injury The appliance shall not be installed in or near the laundry room Before obtaining access to the terminals all supply circuits must be disconnected The appliance must be positioned so that the plug is easily accessible The enclosure of the appliance shall be marked by words or by symbols with the direction...

Page 4: ...ended for use by young children or infirm persons without supervision Don t install the air conditioner in the following locations Anywhere that contains unsealed petrolatum Areas with salt saturated air such as near the coast Areas with caustic gas sulfide for example existent in the air such as near a hot spring Areas with fluctuations in incoming power supply or unstable power where the voltage...

Page 5: ...sitive and negative poles are in their proper positions when loading batteries This manual is subject to changes due to technological improvement without further notices Cautions regarding Remote Controller installation Remote Controller Remote Controller Holder Mounting Screw B ST2 9x10 C H Table 3 1 QUANTITY SHAPE NAME 1 Hook 6 Owner s Manual 7 Installation Manual 2 Remote Controller 3 Frame 5 A...

Page 6: ...ent image interference and noise coming from those electrical appliances Noise may be generated depending on the conditions under which the electric wave is generated even if a 1 meter distance is kept There is sufficient room for installation and maintenance Refer to Fig 5 1 and Fig 5 2 The outlet and the inlet are not impeded and the influence of external air is minimized The air flow has reach ...

Page 7: ...he drain hole and drained away to an appropriate place so as not to affect other nearby people Select the best position that will not be subject to snow drifts accumulation of leaves or other seasonal debris If unavoidable please cover the unit with a shelter Install the unit in a location that is as close as possible to the indoor unit If possible remove all nearby obstacles so as to prevent air ...

Page 8: ...installation Connecting pipes should not be installed until the indoor and outdoor units have already been fixed into place Keep the connecting pipes dry and do not let moisture inside during installation Heat insulation work should be installed properly and fully on both sides of the gas piping and the liquid piping Otherwise there can be a risk of water leakage Pipe Connection Procedure 7 1 Tabl...

Page 9: ... Refer to Fig 7 3 Fig 7 2 Fig 7 3 How to take outdoor unit apart to connect the pipes Remove the water tray Refer to Fig 7 4 Remove the water tray Refer to Fig 7 4 Flaring 1 Cut pipe using a pipe cutter Refer to Fig 7 5 Insert a flare nut into the pipe then flare the pipe Refer to Table 7 2 for the dimension of flare nut spacings 90 Lean crude burr Fig 7 5 Fig 7 4 How to Connect the Pipes Water Tr...

Page 10: ... 32 Ø 3 8 Ø 1 2 Ø 5 8 Hexagonal wrench 6 mm Ø 3 4 Hexagonal wrench 10 mm Ø 1 Service Port Cap 26 32 17 20 13 16 4 5 6 7 5 10 12 20 25 8 5 10 2 10 12 MC MC BLUE Low Pressure Side of Manifold Gauge RED High Pressure Side of Manifold Gauge YELLOW Common Side of Manifold Gauge BLUE Low Pressure Gauge RED High Pressure Gauge Low Pressure Valve High Pressure Valve Preparations and Precautions can cause ...

Page 11: ...Valve Fig 6 2 9 Insert hexagonal wrench into the service valve LIQUID Side Valve and open the valve by turning the wrench in a 1 4 counterclockwise turn Listen for the sound of gas exiting the system then close the valve after 5 seconds 10 Watch the Pressure Gauge for a few minutes to make sure that there is no drop in the pressure value indicating a leak The Low Pressure Gauge should now show a p...

Page 12: ... must be heat insulated or it as well as the connections of the indoor unit will condense dew Hard PVC binder must be used for the pipe connection Make sure there is no leakage With the connection part to the indoor unit please ensure not to apply pressure on the side of indoor unit pipes When the declivity of the drain pipe downwards is over 1 100 there should not be any winding The total length ...

Page 13: ...ly The power connection for the air conditioner has to be done at the main power distribution source The distribution has to be of a low impedance normally the required impedance is reached at a 32A fusing point No other equipment should be connected with this power line For detailed installation exceptions please refer to your power supplier to confirm if restrictions apply for products like wash...

Page 14: ...nnected correctly The length of the tubing and the added stow capacity of the refrigerant have been recorded The power voltage fits the rated voltage of the air conditioner There is no obstacle at the outlet and inlet of the outdoor and indoor units The gas side and liquid side stop valves are both open The air conditioner is pre heated by turning on the power Set the air conditioner to COOLING mo...

Page 15: ...8 000 BTU hr OUTDOOR UNIT POWER WIRING STRONG ELECTRIC SIGNAL WEAK ELECTRIC SIGNAL Wiring Figure The power supply included in the above mentioned can be applied to the table Before obtaining access to terminals all supply circuits must be disconnected CAUTION Fig 9 4 Ground Wiring Ground Wiring Power Supply Switch Fuse Available locally Power Wiring Indoor Power Linking Wiring Outdoor Strong elect...

Page 16: ...Unit Ground the air conditioner properly to ensure its anti interference function Fig 10 6 Ground Wiring Ground Wiring Power Supply Switch Fuse Available locally Power Wiring indoor Power linking Wiring Outdoor Weak electric signal link wiring Indoor Unit Outdoor Unit Power Supply Ground the air conditioner properly to ensure its anti interference function Magnetic Ring optional Hitch onto the com...

Page 17: ...nding chart or it may lead to damage The signs of the indoor terminal block in some of following fugures may be replaced by L N L1 N1 CAUTION Fig 9 7 Ground Wiring Ground Wiring Power Supply Switch Fuse Available locally Power Wiring Outdoor Strong electric signal link wiring Weak electric signal link wiring Indoor Unit Outdoor Unit Ground the air conditioner properly to ensure its anti interferen...

Page 18: ...with the sales agency for manufa cturer for details is a registered trademark of Parker Davis HVAC International Inc Parker Davis HVAC International Inc 2250 NW 102 Place Doral FL 33172 USA Tel 305 513 4488 Fax 305 513 4499 email info pd hvac com Website www pd hvac com Copyright 2017 Parker Davis HVAC International Inc All rights reserved ...

Page 19: ......

Reviews: